PS5000 Environmental Requirements

You must meet these environmental requirements:
Only operate an enclosure from a power source with a voltage range of 100 to
240 VAC.
Make sure each power source has sufficient electrical overload protection.
Have sufficient space for air flow in front of and behind the array.
Make sure the location is properly vented.
Follow the PS5000 technical specifications shown in Table 2-2.
Table 2-2: PS5000 Technical Specifications
Component
Weight of fully-loaded array
Operating temperature
Storage temperature
Maximum operating altitude
Operational relative humidity
Thermal output (fully-loaded array) 1700 BTU/hour (SAS disks)
Operational shock
Operational vibration
Input voltage
Input frequency
System input power
Height/Width/Depth
Each power supply
2–4
Requirement
77.6 pounds or 35 kilograms
41 to 95 degrees F / 5 to 35 degrees C
-22 to 140 degrees F / -30 to 60 degrees C
10,000 feet (3048 meters)
20 to 80% non-condensing
1550 BTU/hour (SATA disks)
5 G for 10 ms 1/2 sin
Random 0.21grms 5 - 500 Hz
100 to 240 VAC (auto-sensing)
48 - 62 Hz
530 VA (maximum)
5.12" x 19" x 21.7" (13 x 48.26 x 55.1 cm)
450 watts DC output
Maximum input power: 0.7 KVA
Input current: 7 – 3.5A