Page 1
Air handling unit controller USER MANUAL LEGGI E CONSERVA QUESTE ISTRUZIONI READ AND SAVE THESE INSTRUCTIONS k.Air +030220981 - ENG Up to date version available on www.carel.com...
Page 3
The technical specifications shown in the manual may be changed innovations to products, procedures and strict quality processes without prior warning. The liability of CAREL in relation to its with in-circuit and functional testing on 100% of its products, and...
Page 4
Warranty on materials: 2 years (from the production date, excluding consumables). Approval: the quality and safety of CAREL products are guaranteed by the ISO 9001 certified design and production system, as well as by the and marks Dangerous voltage. Caution, hot surface.
Page 5
3.4 Power supply 9. FUNCTIONS 3.5 pGDE terminal connection 9.1 Dampers 3.6 Universal input/output connections 9.2 Activation Insulation type on k.Air mini and c.pCOe 9.3 Shutdown Insulation type on k.Air large 9.4 Types of control 9.5 PID control 4. USER INTERFACE 9.6 Temperature control...
Page 6
12.2 Alarm parameters 12.3 Generic alarm input and output contacts. 12.4 Alarm table 13. SOFTWARE UPDATE 13.1 Update via USB cable 13.2 Update via USB pen drive 13.3 Update with file transfer via FTP 6 | k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 7
P/N P+DA00FHD*FK and large P/N P+5A00SFC*LK. Both models share the same software functions, however they differ in terms of the number and characteristics of the available inputs/outputs and serial communication ports.
(up to 6 devices); dehumidification by cooling coil (with dew point control) and reheating; control with 0- 10 V input for humidifier or Modbus connection for CAREL humiSonic and humifog humidifiers;...
Fig.1.d Below is a list of devices that are suitable for use with k.Air. CAREL has passive and active temperature 1.3 Series of probes and differential pressure probes, for duct installation, designed specifically for heat recovery units accessories for and small air handling units.
Page 12
4 to 20 mA 0-3000 Pa 0-5000 Pa Tab.1.e Note: the k.Air mini +Vdc terminal provides a supply voltage of 12 Vdc ± 8%. If a higher voltage is required, use an external power supply. 12 | 1. Introduction k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 13
Range Output Range Output DCFL000100 1-9 m/s ON/OFF Tab.1.g Air quality sensor for rooms and ducts Fig.1.i SENSORS Range Output Range Output DPWQ402000 0-2000 ppm 0-10 V DPDQ402000 0-2000 ppm 0-10 V Tab.1.h 1. Introduction | 13 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 14
The touch screen display guarantees simple human- machine interaction, making it easier to browse between the various screens. The pGDx terminal can be used to fully browse the k.Air webserver, thus acting as a unit terminal. In the version with built-in T/H probe, it can be used as a room terminal, getting the temperature and humidity values directly from the main controller.
Page 15
In the Compact version, it has a capacity of 0.5 kg/h to 1 kg/h, and is designed to be built into compact units, such as heat recovery units, fan heaters, fan coils, etc. See manual +0300056EN. Fig.1.n 1. Introduction | 15 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 16
Fig.1.o uChiller μChiller is Carel’s solution for the complete management of direct expansion units. The maximum configuration manages 2 compressors per circuit (On/Off or BLDC), up to a maximum of 2 circuits (using an expansion card for circuit 2). The distinctive element of μChiller is complete control of high-efficiency...
2. Communication ports See the c.pCO manual +0300057EN for the hardware characteristics of the serial ports. The k.Air controller manages the protocols on the serial ports shown in the table. Ref. Type/connectors Model Specifications Protocol Integrated on main board pLAN...
3. Hardware installation 3.1 Assembly The k.Air controllers are available in the DIN rail mounting version. See the technical documentation +0300057EN. The th- Tune terminal is available in the flush- mounted and wall- mounted versions. For and dimensions assembly, see the technical leaflets +0500016IE, +0500017IE.
Page 21
LED and red +VDC overload LED VG: power at voltage A (*) for opto-isolated analogue output VG0: power for opto-isolated analogue output, 0 Vac/Vdc Analogue outputs 3. Hardware installation | 21 k.Air +030220981 rel. 1.1 – 31.03.2020...
90 degrees, always avoiding running the controller cables parallel to the power cables; reduce the path of probe cables as much as possible, and avoid spiral paths that enclose power devices; in the event of any malfunctions, do not attempt to repair the device, rather contact a CAREL service centre. Electrical installation Important: before carrying out any maintenance, disconnect the controller from the power supply by moving the main system switch to “off”.
Use the accessory cable P/N S90CONN0S0, as shown in the figure. The maximum distance allowed between controller and terminal is 10 m. pGDE terminal Note: for connection cable lengths > 10 m or to connect multiple terminals, use the TCONN6J000 connection accessory. See manual +0300057EN. Fig.3.i 24 | 3. Hardware installation k.Air +030220981 rel. 1.1 – 31.03.2020...
Note: the table indicates the maximum number of inputs that can be connected. For example, with k.Air mini, a maximum of two 4- 20 mA inputs from probes powered by the controller and a maximum of four 4-20 mA inputs probes powered externally can be connected. The maximum total number of inputs of both types is however four.
Page 26
For the operating range, see the technical specifications table in manual +0300057EN. Fig.3.k Controller terminals NTC probe Wire 1 Wire 2 Wire 1 Wire 2 Wire 1 Wire 2 Wire 1 Wire 2 Tab.3.d 26 | 3. Hardware installation k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 27
For the operating range, see the probe data sheets. The controller can be connected to all CAREL DP* series active temperature and humidity probes configured with 4-20 mA signal. Note: the k.Air mini models do not accept 0-10 Vdc signals as inputs from probes powered by the controller. Fig.3.l...
Page 28
Connection of active probes with 0-10 V output powered externally See the table at the beginning of the paragraph for the maximum number of probes that can be connected. For the operating range, see the probe data sheets. Fig.3.n 28 | 3. Hardware installation k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 29
Tab.3.i Maximum number of analogue outputs that can be connected Analogue outputs (not opto-isolated) k.Air mini k.Air large c.pCOe 0-10 Vdc (class 2) (maximum current 2 mA) max 5 max 5 Tab.3.j 3. Hardware installation | 29 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 30
Vterm k.Air large: 24 Vdc ± 10% - To be used to power an external terminal as an alternative to the one connected to J10, Pmax = 1.5 W. Max connection cable length: 30 m; if the length exceeds 10 m, use a shielded cable with the shield connected to earth.
3.6.2 Digital inputs The controller features digital inputs for monitoring safety devices, alarms, device states and remote enabling signals. See manual +0300057EN. Maximum connection cable length: k.Air mini 10 m, k.Air large 30 m. Important: the k.Air controller does not provide any protection, limitation or functional safety for the controlled devices.
Connection of digital inputs There are no specific constraints on the maximum number of inputs that can be connected. For the k.Air mini controller, see the figure above, while for k.Air large, a possible connection example is shown below. See manual +0300057EN.
Tab.3.q The following tables apply in relation to the type of insulation. Insulation type on k.Air mini and c.pCOe Between relays in group 1 (R1, R2) and 2 (R3, R4, R5) basic Between relays in group 3 (R6) and relays in group...
Important: the current running through the common terminals must not exceed the rated current of a single terminal: k.air mini: 5 A for groups 1 and 2, 1 A for group 3; k.Air large: 8 A Remote control of digital outputs The cable sizes based on the current are shown in the following table.
For details on mounting the c.pCOe expansion cards, see technical leaflet +0500059IE. The k.Air controller is designed to be able to host up to four c.pCOe cards with serial addresses from 2 to 5; to assign the serial address to the c.pCOe card, the dipswitches on the card must be set as shown in the figure;...
4. User interface 4.1 Introduction The k.Air system uses the user terminal (P/N PGNE000*) for displaying alarms and some key values, and for setting the parameters. The terminal comprises a display and 6- button keypad for configuring and programming the unit. The main information can also be displayed on the pGDX graphic terminal.
Page 37
31 LOW SUPPLY T Minimum supply limit control 32 HIGH SUPPLY T Maximum supply limit control 33 HIGH H SAT High humidity control (VDI) 34 START INACT. Start due to inactivity (VDI) Tab.4.b 4. User interface | 37 k.Air +030220981 rel. 1.1 – 31.03.2020...
1. Press Esc one or more times to go to the standard display; 2. Press Prg: after entering the user password, the main menu is shown; 3. Press UP/DOWN and select category X: Settings; press Enter to confirm; 4. User interface | 39 k.Air +030220981 rel. 1.1 – 31.03.2020...
The quick access menu screens are identified by an alphanumeric code at the top right, the first letter Q indicates the quick access menu, the second lowercase letter indicates the submenu branch: a. Info, b. On/Off, c. Set point; finally, the number identifies the screen in the menu. 40 | 4. User interface k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 41
Damper status based on opening time Outside air, mixing and exhaust damper status Bypass damper status and request, unit status. Air quality probe measurement and set point. Request and % activation of the supply/return fans 4. User interface | 41 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 42
Scheduler active from c.pCO controller or from th- Tune room terminal. Scheduler active: daily programming, holiday program or special days. The next two screens show information on the software version and operating system, the size of the k.Air controller and the cycle time.
Page 43
Comfort, Economy, etc.) and/or unit is switched off. In this case, the reference set points will depend on the profile and will be shown on the screens in menu Aa. Also see the chapter on the Scheduler. 4. User interface | 43 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 44
Note: see technical leaflets +0500016IE/+ 0500017IE for assembly of the terminal. Once connected to the k.Air controller and enabled, th- Tune allows the user to control the room temperature and relative humidity (NOTE: the room humidity set point can however only be set on the pGDE terminal) and change some settings, such as operating mode and time bands.
Page 45
5.3 Display During normal operation, the display shows, in addition to the current day of the week and time, the status of the fans, the room probe measurement and the operating mode. 5. th-Tune (accessory) | 45 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 46
OFF from digital input OFF by FAN OFF due to fan alarm OFF by COND OFF due to alarm during start-up STRT UP Unit starting SHUT DOWN Shutting down OPERATING MODE ICON Cooling Heating Automatic 46 | 5. th-Tune (accessory) k.Air +030220981 rel. 1.1 – 31.03.2020...
See the paragraph at the end of the chapter. The time bands set on the th- Tune terminal are only effective when the k.Air controller is in Comfort mode. In Economy mode, the unit set point depends on Setting the time the set point configured on the corresponding screen on the controller.
Page 48
Tab.5.f The resulting room temperature set point is shown in the figure, where it can be seen that the th-Tune set point is only considered when the pGDE is in “Comfort” mode. 48 | 5. th-Tune (accessory) k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 49
Press the knob 1 to 4 times to display the temperature/humidity values: Main data 1. room temperature set point, display 2. relative humidity reading; 3. supply probe reading; 4. outside probe reading. 5. th-Tune (accessory) | 49 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 50
Main scheduler on k.air point th-Tune scheduler (active only if the k.air scheduler is not active or it is in Comfort mode) Change set point using the control knob. The control knob can always be used to change the main control set point (temperature). This set point will then be permanently active if no scheduler is active, or temporary if one or both schedulers are active.
(*) manual: manual mode, see chap. “Commissioning” and parameters in group Ad. Automatic: normal operating mode 5.10 Procedure for setting the time bands on th-Tune To set the time bands, the unit must be ON. Procedure: 5. th-Tune (accessory) | 51 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 52
7. Press the knob: the display flashes on the start 8. Turn the knob and set the hours 9. Press the knob: the display flashes on the start hours for the first time band minutes for the first time band. 52 | 5. th-Tune (accessory) k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 53
16. Press the knob (ESC) or the Power button one or more times to go back to the standard display. Press Clock to activate the time bands (the home icon is displayed). 5. th-Tune (accessory) | 53 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 54
MAC Address. Fig.6.b Network connection of the pGDx terminals and k.air Procedure 1. connect the pGDx terminal to the power supply and the Ethernet cable. See technical leaflet +050001895;...
Page 55
If needing to use the temperature and humidity probes included in the pGDx terminal: go to screen Y065 and enter the last 4 digits of the MAC Address. In this way, k.air will acquire the values read by the temperature and humidity probe, which can be assigned as a room temperature and humidity probe for the space where the terminal is located.
Page 56
DNS (xxx.xxx.xxx.XXX) IR565 PIV3879 The main programming menu provides access to all of the k.Air controller parameters, also using the function that simulates the user terminal, available by selecting “Service”. Note: when simulating the user terminal, the k.Air controller user menu can also be accessed. For further details, see the c.pCO manual +0300057EN.
→ F. Humidifiers G. Filters H. Auxiliary control I. IEC J. VDI T. Alarm logger a. View b. Export U. Compressor a. Configuration b. BLDC c. Power+ V. EXV W. In/Out 7. Menu description | 57 k.Air +030220981 rel. 1.1 – 31.03.2020...
Note: parameters Bb07 to Bb22 refer to the ebm-papst EC fan (fan type = Modbus). a. Return fan. See Bb. Note: parameters Bc07 to Bc22 refer to the ebm-papst EC fan (fan type = Modbus). 58 | 7. Menu description k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 59
Heat recovery unit: PID parameters, activation thresholds, defrost parameters; Modulating bypass damper: minimum and maximum limits, operating hours; 7. F Humidifier: type (modulating or CAREL humiSonic controlled via serial), set operating hours before alarm; Enable humidification control, PID parameters; Humidifier operating times: time between washing cycles, read variables;...
K; select the type of fans, heating device (heater/water coil) and the type (ON/OFF, modulating); select the type of heat exchanger (plate/rotary), outside air damper and bypass damper; select the type of humidifier (modulating/humiSonic/Humifog); 60 | 7. Menu description k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 61
Note: k.Air is factory set for correct display on a pGDE terminal with address 32 in the pLAN network (default); for more details on using the terminal, see manual +0300057EN.
+3000204. All k.Air models are equipped with a USB or micro USB host (Master) port that a USB mass storage device can be plugged into (typically a USB pen drive or portable hard disk) so as to load a custom Upload configuration.
For each device, sensor or contact (referred to as “points”), an acquisition channel needs to be selected from those available on the main board or expansions. Input/output Menu W.In/Out is used to configure and check the inputs and outputs connected to the k.air controller. configuration There are four configuration screens:...
Note: the minimum and maximum conversion values rescale the output signal. Specifically, the minimum value is also active when the unit is OFF. The k.Air controller is configured to display International System units of measure. Access screen Wc01 to 8.6 Unit of set a different unit of measure, if desired.
The k.Air software manages the devices that communicate via the FieldBus (mini model) or Fieldbus2 (large model) serial network using the Modbus protocol, with the following frame: FieldBus serial baud rate: 19200; port parity: none; configuration stop bits: 2. The device addresses must be set as shown in the table: Addr.
Page 67
Important: when loading a configuration, all of the parameters are set to the value saved in the file, and therefore any subsequent changes will be lost. Important: unplug any USB cables connected to the USB device port (k.Air large) before loading a configuration.
1. connect a USB pen drive with micro USB connector; 2. access screen Ac99; 3. select “Import”, “USB”; 4. type in the exact file name and confirm; 5. a confirmation message is shown to indicate that the operation was successful. 68 | 8. Commissioning k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 69
9. Functions 9.1 Dampers k.air manages up to six types of dampers, on/off or modulating, with the following specific control functions: Damper Relationship Control Air quality Fresh air Unit activation and main control functions Frost protection Exhaust Temperature control Mixing...
Page 70
Air Quality - Damper PID parameters - Integral R/W HR1641 PIV3136 time Fresh air damper - Minimum control value 0.0 100.0 % R/W HR1642 AV3137 Ca06 Fresh air damper - Maximum control value 100.0 0.0 100.0 % R/W HR1643 AV3138 70 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Note: when the unit is Off, the bypass damper will be open. The k.air software enables the unit to be switched on only if all of the enabled commands are set to ON 9.2 Activation (from pGDE/thTune, BMS, digital input, scheduler). When the unit is switched on, a procedure is activated to verify all of the safety conditions and activate the devices following a certain sequence;...
Page 72
On start-up, the fresh air, exhaust and bypass dampers are opened completely. The next phase starts after a delay (opening time - “Ca01") to allow complete opening. If the return fan is fitted, this is started, and 72 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 73
PIV3134 Shutdown In the same way as when switching on, the k.Air software enables the unit to be switched off if at least one of the enabled commands is set to OFF (PGD1/th-Tune, BMS, DI, Scheduler). Once the command is received, the unit goes into shutdown status, during which the devices follow a specific sequence until the unit is completely switched OFF.
1. humidity: the humidity request is sent by the controller to a humidifier via the 0-10 V output or via the Modbus serial port (CAREL humiSonic, Carel Humifog); 2. dehumidification: the controller sends the request, either directly or via the dew point calculation, to the main coil.
Page 77
9.5.2 Sequential PID The k.Air controller has different functions and devices that can act alone or in a coordinated way to ensure the best indoor comfort conditions. Each of these devices may either be present or absent, or enabled or disabled on the unit; therefore, depending on the situation, it will have a different impact on energy consumption during operation.
Page 78
Diff_1. Fig.9.k Request Request Reg_var Control variable Offset Set point Diff_1/2 Differential 1/2 78 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 79
9.5.3 Incremental PID Incremental PID is the most common control mode on k.air. It is used for a single point control and is based on a PID controller designed to avoid variations in the output in the event of variations to the set point.
Page 80
When the signal moves outside of the dead band, the output is increased, or decreased, without sudden variations. Fig.9.m Request Alarm Alarm Set point diff Differential Dead band Control probe 80 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
The PID parameters relating to cascade control, used to calculate the supply set point The minimum and maximum supply limits, used as the control range for calculating the supply set point Room or return set point 9. Functions | 81 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 82
For adiabatic humidification, the production of humidity is also limited as the last stage of the low supply temperature limit function. This accessory function is also active, as the only limit stage, in the main supply temperature control function. Below is a summary of the limit action. 82 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Low supply temp: integral time 120 0 R/W HR1361 PIV2869 The k.Air controller is extremely flexible in adapting to the temperature control demands and characteristics of the system so as to respond to changes in season or over a day. Cooling and...
Page 84
Cooling/heating unit type enabled DI700 BV1158 Unit cooling/heating mode configuration R/W HR1311 PIV2819 Cooling outside temperature threshold 28.0 99.9 °C R/W HR1312 AV2820 99.9 Ac24 Heating outside temperature threshold 18.0 99.9 °C R/W HR1313 AV2821 99.9 84 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 85
Heating: outside temperature compensation 0.0 -50.0 90.0 °C R/W HR1182 AV2692 threshold Heating: outside temperature compensation delta -8.0 -30.0 30.0 °C R/W HR1183 AV2693 Aa90 Heating: maximum compensation offset -2.0 -20.0 10.0 °C R/W HR1184 AV2694 9. Functions | 85 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 86
9.9 Coils k.air can manage up to three coils, called preheating, main and reheating. Each of these has different characteristics and requirements. The table below summarises the main features, while the details are described in the chapters corresponding to each control function.
Page 87
A further option available is control of the coil supply water temperature. k.air activates an alarm on exceeding a high or low temperature threshold, after a settable delay. An action can be set in response to the alarm, selected from the following:...
Page 88
Each load connected to the digital outputs must have twice the power as the previous one. The table and image below show the activation sequence with two outputs and three steps. Request Digital output 1 Digital output 2 100% Fig.9.r 88 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 89
Direct expansion coil with integrated management This configuration, available only on k.air mini, involves the installation of a refrigerant circuit using the inputs/outputs, unipolar expansion valve and communication with the Power+ inverter on the controller, so as to integrate direct expansion architecture with high efficiency.
R/W HR1914 PIV3940 9.10.1 Compressor management 9.10 Direct expansion k.air manages ON/OFF compressors with direct starting or modulating BLDC compressors. For BLDC with integrated compressors, more than 200 models can be selected. A BLDC compressor is always driven by a Power+ management...
Page 91
MOP and DeltaP minimum ExV opening management parameters set point control parameters (BLDC only) alarm prevention parameters Note: to view the graphs of BLDC compressor envelopes, see the CAREL document “BLDC compressor envelopes”, available on ksa.carel.com 9.10.4 BLDC compressor start-up procedure k.air manages the start-up of BLDC compressors in accordance with the manufacturer’s specifications: on...
Page 92
A high compression ratio is a thermal limit of compressor operation: normally control is activated at the limit of the envelope, reducing capacity when the limit is exceeded; if a probe is fitted to measure discharge temperature and if the temperature approaches the limits, as the critical condition involves 92 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Compressor delay at start-up/in operation Compressor start-up is a critical phase and for this reason k.air has differentiated control for some alarms to exceed the transient phase from compressor start- up and allow it to reach steady operation. The...
Page 95
Carel’s Power+ and ExV system. uChiller can be easily integrated with k.air via the managed by Fieldbus serial port to develop air handling units with a direct expansion main coil. k.air sends the start- up and capacity modulation commands, making available the main operating status information directly uChiller on the pGDE display, such as active compressors and active faults.
Page 96
Evaporation pressure Suction temperature Close contact Compressor 1 thermal protector High pressure switch Compressor 2 thermal protector Remote alarm (close contact if not used) Compressor 1 Compressor 2 Reversing valve Alarm Condenser fan 96 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 97
4. Using the Applica or uChiller display app, configure the parameters relating to the refrigeration unit. 5. Set parameter Hd00 (supervisor address) to 10. 6. On the k.air pGDE terminal, enable the main coil as uChiller on screen Ac08, and set the operating mode on Da01.
Page 98
For example, if set to 30%, it means when the fresh air damper is fully closed, IEC is limited by 30%. By default the parameter is set to 0%, i.e. the limit is disabled. 98 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Control can be performed using the relative humidity value or the absolute humidity value. To assist commissioning, the set point will still be the relative humidity value, and k.air will then calculate the equivalent in absolute humidity by taking into account the temperature set point; the result is shown on the info screen.
Page 100
Humidification/Dehumidification: Control 20.0 99.0 %rh R/W HR1321 AV2829 band Ac36 Humidification/Dehumidification: Control min R/W HR1322 PIV2830 change delay time Note: absolute humidity control, once enabled, applies to both dehumidification and humidification 100 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 101
Humidifier output reduction second stage. Humidifier output reduction The heating devices are controlled to keep the supply Supply temp. control Humidifier output reduction temperature constant, if sufficiently sized, humidifier output is not reduced. 9. Functions | 101 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 102
BV253 reset request Note: if CAREL humiSonic or Humifog humidifiers are used, the humidifier must be configured according to the commissioning procedure, as described in the specific manuals or technical leaflets. Dehumidification is controlled by a main cooling or mixed coil, when appropriately enabled (Ac04).
Page 103
Note: for both control functions, dehumidification mode acts on the cooling coil only when the unit is in dehumidification status. This status is activated when the humidity control request is greater than 20%. Dehumidification status is visible in the unit status information on the main screen. 9. Functions | 103 k.Air +030220981 rel. 1.1 – 31.03.2020...
The heat recovery unit, if enabled on Ac01, is always available as a control stage in the main sequential temperature control PID. However, the freecooling/freeheating conditions must not be true at the same time, as these are mutually exclusive. k.air can manage the following types of heat recovery unit: Type Signal/actuator Control...
Page 106
Maximum defrost heat exchanger duration 999 min R/W HR1466 PIV2973 E016 Exhaust temperature threshold for defrost 20.0 90.0 °C R/W HR1468 AV2974 50.0 Stratification correction factor of the room E020 0.0 10.0 R/W HR1469 AV2975 temperature 106 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 107
9.18 k.air manages up to two fans, one for supply and one for return, which may be: On/off. Fans Modulating. 3-speed modulating; Modulating via Modbus (EBMPapst); The return fan is optional, and if enabled it will be the same type as the supply fan. The configuration is available on screen Ac01 and subsequently in menu B.Fans.
Page 108
The fan speed is automatically modulated based on the differential pressure/air flow-rate set points. The PI control parameters are the same for both. The differential pressure sensor is used in both pressure and flow-rate mode; the conversion between the values depends on the coefficient K. Fig.9.af 108 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 109
R/W HR1899 AV3379 9.18.2 Flow and thermal overload alarm On k.air the following digital contacts can be enabled to check correct functioning of the fans Supply fan thermal protector, total unit shutdown Return fan thermal protector, fans stopped Fan thermal protector, total unit shutdown. The thermal protectors for the two fans must be...
Page 110
Priority between minimum ventilation and night Ba21 freecooling (FALSE: minimum ventilation; TRUE: FALSE 0 R/W CS249 BV249 freecooling) 9.18.5 Filters k.air can manage the following filters: Supply filter 1 alarm Supply filter 2 alarm 110 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 112
5. If the fan with flow-rate or pressure control is enabled, set the maximum air quality limit in m3/h or Pa 6. Set the air quality set point in the set point menu. 112 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
“enable quick menu”. This allows the set point to be defined by the end user with unprotected access. 9. Functions | 113 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 114
The On/Off heater features “direct- heating” activation, with the trend shown in the figure, while for the modulating heater, the action depends on the PID parameters. 114 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
“Frost Off” status, if enabled. Deactivation Frost protection is deactivated when the frost protection thermostat switches or the value read by the frost protection probe is greater than the frost protection threshold plus a settable differential. 9. Functions | 115 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 116
Supply probe threshold Fig.9.al Control If the condition for ending frost protection does not occur before the “Warning delay” time, the unit goes into frost protection status and the corresponding procedure is started. 116 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Frost protection heater request P_vent_T Post-ventilation time Al_delay Alarm delay time Ext/Exh_ Fresh air/exhaust damper damp Min_lim Fresh air damper min limit Min_sp Minimum fan speed Frost protection warning delay Low_s_thr Low temperature threshold Fig.9.am 9. Functions | 117 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 118
HEAT EXCHANGE Bypass damper closed Thermal wheel at maximum speed The controller therefore opens the bypass damper and adjusts the speed of the thermal wheel using the same modulating output, to prevent defrosting. 118 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 119
9.22.2 Thermal wheel To prevent activation of frost protection, the thermal wheel, starting from the minimum bypass damper opening threshold, decreases speed until stopping, reducing heat exchange between exhaust air (warm) and fresh air (cool). 9. Functions | 119 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 120
Note: when the outside temperature is very low, and the minimum time has elapsed between successive defrosts, defrosting starts again. Fig.9.ap Exh_T Exhaust temperature Ext_T Outside temperature Byp_Damp_Max_Op_thr Start defrost threshold Exh_T_thr End defrost threshold 120 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 121
3. evaporation temperature (conversion from suction pressure) < start defrost threshold During defrosting, the fans operate at the speed set for “Defrost fan request”. End defrost conditions The unit ends the defrosting procedure if one of these conditions occurs: 9. Functions | 121 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 122
(end defrost threshold not reached). The time between defrosts is needed to prevent the unit from defrosting too frequently and thus only partly meeting demand. 122 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 123
Evaporation temperature delta On/off compressor D_b_cycle_rev Delay before reversing cycle CMP_BLDC BLDC compressor Defrost by reversing the cycle Post-dripping Cmp_off_t Compressor OFF time Def_reg Defrost request time Byp_dmp Heat recovery bypass damper Dripping 9. Functions | 123 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 124
Outside temperature Fig.9.au Condition for entering defrost mode The unit starts defrosting when the following condition occurs: Outside temperature < Bypass damper maximum opening threshold (default = 5°C); Exhaust temperature < Exhaust temperature threshold 124 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 125
Reversing valve delta P bar R/W HR1537 AV3038 Defrost: delay time R/W HR1538 PIV3039 before changeover Ua27 Defrost: delay time after R/W HR1539 PIV3040 changeover Fan request during Ua30 % R/W HR1540 PIV3041 evaporator defrost 9. Functions | 125 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 126
R/W CS250 BV250 temperature alarm The k.Air controller software features specific device management and/or control functions in the event of probe errors. 9.24 Probe error Normally, the device or function associated with a probe alarm is deactivated, so as to avoid control being...
Page 127
50.0 0.0 100.0 % R/W HR1376 AV2884 error Reheating coil request in the event of control probe 50.0 0.0 100.0 % R/W HR1377 AV2885 error Ac74 Supply fan speed request in the event of control % R/W HR1378 PIV2886 9. Functions | 127 k.Air +030220981 rel. 1.1 – 31.03.2020...
%rh R/W HR1178 AV2688 Comfort - High limit value The time bands are managed by the k.air controller Scheduler function; this function features a weekly 9.26 schedule, special days (up to 15) and vacations (up to 3). For each of these three groups, either a fixed...
Page 135
4. press UP/DOWN to check the box; 5. press Enter and UP/DOWN to set the hour and minutes for the start of the first time band and the corresponding operating mode: OFF, ECONOMY, PRECOMFORT, COMFORT; 9. Functions | 135 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 136
Go to screens Ab18, Ab21, Ab24 and set the special days. Special days last just one day, have priority over the time bands and vacations, and the selected operating mode can be: OFF, ECONOMY, PRECOMFORT, COMFORT 136 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 137
Current hour IR306 PIV3687 Current minute IR307 PIV3688 Day of week IR383 PIV3760 Ab01 Current day IR358 PIV3739 Current month month IR359 PIV3740 Current year IR360 PIV3741 Scheduler: configuration - Enabled FALSE CS064 BV64 9. Functions | 137 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 138
R/W HR1221 PIV2729 Tuesday program R/W HR1222 PIV2730 Wednesday program R/W HR1223 PIV2731 Ab12 Thursday program R/W HR1224 PIV2732 Friday program R/W HR1225 PIV2733 Saturday program R/W HR1226 PIV2734 Sunday program R/W HR1227 PIV2735 138 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 139
Day 5 R/W HR1257 PIV2765 Month 5 R/W HR1258 PIV2766 Program R/W HR1259 PIV2767 Enable special day 6 CS214 BV214 Day 6 R/W HR1260 PIV2768 Month 6 R/W HR1261 PIV2769 Program R/W HR1262 PIV2770 9. Functions | 139 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 140
Ab27 Party mode duration 10080 R/W HR1291 PIV2799 k.air provides a function, based on the VDI 6022-1 standard, to improve system hygiene. 9.27 VDI 6022-1 Both operational and maintenance functions are provided. management VDI management, enabled on screen Ac86, includes: 1.
Measure bacterial colonies in recirculating water the water, if > 1000 CFU/ml 6.2.6 Adiabatic humidifier proceed with disinfection, Determine number of CFU in the clean and rinse in general. humidifier water 9. Functions | 141 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 142
The characteristics of each single counter can be customised on screens Ja02 to Ja42, after setting the type as “CUSTOM” on Ja02. To restore the default values, reset the type to “VDI 6022”. 142 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 147
R/W CS361 BV361 inspection Jb12 Countdown before VDI_Conf[9].CntDwn 0 65535 IR527 PIV3841 the next inspection Reset timers after VDI_Conf[9].ResCmd R/W CS362 BV362 inspection Countdown before Jb15 VDI_Conf[10].CntDwn 0 65535 IR528 PIV3842 the next inspection 9. Functions | 147 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 148
0 65535 IR541 PIV3855 the next inspection Reset timers after VDI_Conf[23].ResCmd R/W CS376 BV376 inspection Countdown before VDI_Conf[24].CntDwn 0 65535 IR542 PIV3856 the next inspection Jb36 Reset timers after VDI_Conf[24].ResCmd R/W CS377 BV377 148 | 9. Functions k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 149
Shared pGDX terminal The pGDX terminal can be shared in a network of 1 k.water and up to 10 k.air units. The webserver HMI can easily switch between the k.water and k.air controllers, meaning only one graphic terminal needs to be installed in the room.
Page 150
Shared outside temperature signal between k.air to k.water k.water provides the outside temperature value, which can be used as an input channel by k.air. On k.air, configuration screen Wb01, select the “kwater text” input channel. Shared unit status When k.air and k.water are connected together, they exchange information useful for commissioning the...
Page 151
At the end of the procedure, the integrated HMI, available as webserver and pGDx, will show the k.air navigation menu. Fig.9.az Description DEV Min Max UoM Dir Modbus BACnet UNIT Unit type (0: COOLING; 1: HEATING; 2: COOL/HEAT) R/W HR1310 PIV2818...
10. Parameter table The k.Air controller can be programmed in three levels, with access to different parameters based on the password entered (see the parameter table): 1) U = user (password=0000); 2) S = service (password=1234); 3) M = manufacturer (password=5678).
Page 155
Unit setpoints - Room temperature - Cooling - Economy - High limit 28.0 LowLimVal 100.0 °C R/W HR1102 AV2612 value Unit setpoints - Room temperature - Heating - Economy - High limit 23.0 LowLimVal 100.0 °C R/W HR1103 AV2613 value 10. Parameter table | 155 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 156
Unit setpoints - Supply air flow - Low limit value 3000 HiLimVal m^3/h R/W HR1129 PIV2639 Unit setpoints - Supply air flow - High limit value 7000 LowLimVal 65535 m^3/h R/W HR1130 PIV2640 156 | 10. Parameter table k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 157
Unit setpoints - Return air flow - Low limit value 3000 HiLimVal m^3/h R/W HR1159 PIV2669 Unit setpoints - Return air flow - High limit value 7000 LowLimVal 65535 m^3/h R/W HR1160 PIV2670 10. Parameter table | 157 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 158
Actual minute IR307 PIV3688 Day of week IR383 PIV3760 Ab01 Actual day IR358 PIV3739 Actual month month R IR359 PIV3740 Actual year IR360 PIV3741 Scheduler: configuration - Enabled FALSE R/W CS064 BV64 158 | 10. Parameter table k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 159
R/W HR1221 PIV2729 Tuesday program R/W HR1222 PIV2730 Wednesday program R/W HR1223 PIV2731 Ab12 Thursday program R/W HR1224 PIV2732 Friday program R/W HR1225 PIV2733 Saturday program R/W HR1226 PIV2734 Sunday program R/W HR1227 PIV2735 10. Parameter table | 159 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 160
R/W HR1257 PIV2765 Month 5 R/W HR1258 PIV2766 Program R/W HR1259 PIV2767 Enable special day 6 R/W CS214 BV214 Day 6 R/W HR1260 PIV2768 Month 6 R/W HR1261 PIV2769 Program R/W HR1262 PIV2770 160 | 10. Parameter table k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 163
Enable function that allows th-Tune to keep unit ON for 'thTunePartyDT' FALSE R/W CS233 BV233 Ac78 Time to keep the unit ON after th-Tune disables the R/W HR1388 PIV2896 scheduler/timeband which was OFF (minutes) 10. Parameter table | 163 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 165
Humidifier - Working hours IR413 PIV3776 Humidifier - Working hours threshold (1000hrs) R/W HR1409 PIV2917 Ae21 Humidifier - Working hours left to the maintenance IR415 PIV3777 Humidifier - Working hours reset R/W HR1410 PIV2918 10. Parameter table | 165 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 166
Pre-heat coil step 1 - Working hours threshold (1000hrs) R/W HR1435 PIV2943 Ae57 Pre-heat coil step 1 - Working hours left to the maintenance IR467 PIV3803 Pre-heat coil step 1 - Working hours reset R/W HR1436 PIV2944 166 | 10. Parameter table k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 167
UoM Dir Modbus BACnet FANS Only for mask usage TRUE DI701 BV1159 Fan regulation type (0: Static pressure; 1: Air flow; 2: Fixed Ba01 R/W HR1491 PIV2992 speed) Supply fan configuration error DI702 BV1160 10. Parameter table | 167 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 168
Automatically generated - Time in [s]for a positive change R/W HR1565 PIV3065 for Ebmpapst fan Bb09 Automatically generated - Time in [s] for a negative R/W HR1566 PIV3066 change of set value for Ebmpapst fan 168 | 10. Parameter table k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 169
IR517 PIV3831 parameter changing procedure Bc01 Return fan request in case of air pressure probe error 35.0 100.0 R/W HR1470 AV2976 Bc03 Return fan offset request 10.0 -100.0 100.0 R/W HR1471 AV2977 10. Parameter table | 169 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 170
- Baudrate [bps] for the communication with the fan. R/W HR1489 PIV2990 Bc30 (0=4800, 1=9600, 2=19200, 3=38400, 4=115200) Serial interface parameters (timeout, command delay, etc.) R/W HR1490 PIV2991 - Parity configuration (0= 8N1; 1= 8O1; 2= 8E1;) 170 | 10. Parameter table k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 171
Pre heating PID parameters - Proportional gain 999.9 HR1671 AV3166 Db03 Pre heating PID parameters - Integral time HR1672 PIV3167 Db06 PreHeating coil request during antifreeze off status 50.0 100.0 HR1673 AV3168 10. Parameter table | 171 k.Air +030220981 rel. 1.1 – 31.03.2020...
Parameters for device configuration - Timings for washing operations - Delay time R/W HR1557 IV3058 between two consecutive washes (mins) F020 Parameters for device configuration - Timings for washing operations - No production R/W HR1558 IV3059 time for inactivity wash (hours) 172 | 10. Parameter table k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 175
Reset type (FALSE: Blocker Alarm; TRUE: Warning) TRUE CS317 BV317 Ja15 Enable of the VDI function TRUE CS318 BV318 Month selection variable HR1702 PIV3197 Reset type (FALSE: Blocker Alarm; TRUE: Warning) TRUE CS319 BV319 10. Parameter table | 175 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 176
Reset type (FALSE: Blocker Alarm; TRUE: Warning) TRUE CS351 BV351 Enable of the VDI function TRUE CS352 BV352 Ja42 Month selection variable HR1719 PIV3214 Reset type (FALSE: Blocker Alarm; TRUE: Warning) TRUE CS353 BV353 176 | 10. Parameter table k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 177
BV376 Countdown before the next inspection 65535 IR542 PIV3856 Reset timings after the inspection CS377 BV377 Jb36 Countdown before the next inspection 65535 IR543 PIV3857 Reset timings after the inspection CS378 BV378 10. Parameter table | 177 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 178
% R/W HR1547 AV3048 Fans request during evaporator defrost: post dripping % R/W HR1548 PIV3049 Ua33 Disable Low supply temperature alarm TRUE R/W CS250 BV250 Enable compressor during night ventilation FALSE R/W CS251 BV251 Ua36 178 | 10. Parameter table k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 179
BLDC envelope configuration - Min speed permitted to 20.0 99.9 R/W HR1870 AV3352 control compressor working conditions inside envelop BLDC envelope configuration - Out of envelop alarm Ub13 32000 R/W HR1871 IV3353 delay time 10. Parameter table | 179 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 189
-999.0 999.0 PIV2 Heating exchanger type PIV2 Heating exchanger type IR15 AV35 Bypass damper -999.0 999.0 IR16 AV35 Thermal wheel -999.0 999.0 R DI37 BV82 Bypass damper - Hardware value writes from board 10. Parameter table | 189 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 190
PIV3 Percentage of activation of ebmpapst supply fan DI41 BV86 Supply fan - Hardware value writes from board CS22 BV22 Enable return fan Return fan request -999.0 999.0 % R IR21 AV36 190 | 10. Parameter table k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 191
Enable main coil regulation DI65 BV11 Enable post heating coil IR22 AV36 Post-heating request from PID Seq -999.0 999.0 % R DI65 BV11 Enable post heating coil IR22 AV36 Post-heating request -999.0 999.0 % R 10. Parameter table | 191 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 192
EVD parameters - Status variables - Superheat -999.0 999.0 IR23 AV36 EVD parameters - Status variables - Superheat -9.9 IR24 AV36 Inverter Power Plus Info - Current rotor speed [rps] -999.0 999.0 192 | 10. Parameter table k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 193
Dew point set point for dehumidification -999.9 999.9 °C R IR25 AV36 Dehumidification request -999.9 999.9 % R PIV3 Auxiliary Regulation 1 - Input selection IR25 AV36 Auxiliary regulation 1: Informations - Regulation value -999.9 999.9 10. Parameter table | 193 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 194
-999.9 999.9 IR25 AV36 KWater modbus variables - KAir circuit temperature -999.9 999.9 IR26 PIV3 Unit status kwater IR26 AV36 Power request 100.0 % R IR26 AV36 Actual production of rack (kg/h-lb/h) 100.0 194 | 10. Parameter table k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 195
Split an int value into digits - Show the Compressor info circuit 2 on user interface Unitstatus IR27 IV36 (0=OffByDI;1=OffByKeyb;2=OffBySched;3=OffByBMS;4=OffByChgOvr;5=OffByAl;6=Dfr;7=StdBy;14 =FCOn;15=CoolOn;16=HeatOn;20=Offline) IR22 AV36 Compressor request 100.0 % R IR27 PIV3 Current version of the application according to standard - X version of the application 10. Parameter table | 195 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 196
9999 rpm R limited to this value for Ebmpapst fan 6553 IR32 PIV3 Working hour counter for Ebmpapst fan IR32 PIV3 Fan speed informations - Actual speed [rpm] of the Zhiel-Abegg fan 9999 196 | 10. Parameter table k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 197
9999 6553 IR34 PIV3 Fan electrical informations - Supply voltage (peak voltage) IR34 PIV3 Fan speed informations - Maximum set speed 9999 6553 IR34 PIV3 Fan speed informations - Minimum set speed 10. Parameter table | 197 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 198
Lists of variables of the device not managed by default IR35 PIV3 Alarm code read from device IR35 PIV3 Actual day IR35 PIV3 Actual month IR36 PIV3 Actual year IR36 PIV3 cpCO real time clock 198 | 10. Parameter table k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 199
"..." may differ depending on the configuration, and the options are shown on the user terminal; an entire row of "..." indicates similarly parameters that are repeated; Modbus variables: HR (holding registers), DI (Discrete inputs), IR (input registers), CS (Coils); 10. Parameter table | 199 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 200
11.1 Supervisor The k.Air controller can be connected to supervisory systems using the Modbus protocol. The BMS serial ports are used for the connection (see the chapter on Communication ports). variable table Meaning of the variables: Coils: read/write, 1 bit (off/on);...
Page 227
HR176 PIV1699 Scheduler_Cfg.Vac[2].EndDay Scheduler: configuration - Vacation period - End day HR177 PIV1700 Scheduler_Cfg.Vac[2].EndMonth Scheduler: configuration - Vacation period - End month HR178 PIV1701 Scheduler_Cfg.Vac[2].mode Scheduler: configuration - Vacation period - Mode HR179 PIV1702 | 227 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 228
Room humidity - Filter channel HR234 PIV1757 ExtTemp.Board_RW Fresh air temperature - Board selected HR235 PIV1758 ExtTemp.Ch_Id_RW Fresh air temperature - Channel id selected HR236 PIV1759 ExtTemp.Ch_Type_RW Fresh air temperature - Probe type used HR237 PIV1760 228 | k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 229
HR292 PIV1815 SupplyAirP.Ch_Type_RW Supply air pressure - Probe type used HR293 PIV1816 SupplyAirP.MinVal_RW Supply air pressure - Minimum analogue input value HR294 AV1817 SupplyAirP.MaxVal_RW Supply air pressure - Maximum analogue input value HR295 AV1818 | 229 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 230
Fresh air preheat coil water temperature - Probe type used HR349 PIV1872 Fresh air preheat coil water temperature - Minimum analogue input FreshAirPreHeatWaterTemp.MinVal_RW HR350 AV1873 value Fresh air preheat coil water temperature - Maximum analogue input FreshAirPreHeatWaterTemp.MaxVal_RW HR351 AV1874 value 230 | k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 231
AV1929 Ain_SetP.MaxVal_RW Set point by AIN - Maximum analogue input value HR407 AV1930 Ain_SetP.Offset_RW Set point by AIN - Analogue input offset HR408 AV1931 Ain_SetP.ChFilter_RW Set point by AIN - Filter channel HR409 PIV1932 | 231 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 233
Main coil alarm - Board selected HR522 PIV2045 MainHeatCoilAlrm.Ch_Id_RW Main coil alarm - Channel id selected HR523 PIV2046 FreshAirPreHeatAlrm.Board_RW Fresh air preheat alarm - Board selected HR524 PIV2047 FreshAirPreHeatAlrm.Ch_Id_RW Fresh air preheat alarm - Channel id selected HR525 PIV2048 | 233 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 234
Mixing damper - Time off cycle relay HR580 PIV2103 MixingDamp_Dout.Ch_Type_RW Mixing damper - Digital output type HR581 PIV2104 SupplyAirDamp_Dout.Board_RW Supply air damper - Board selected HR582 PIV2105 SupplyAirDamp_Dout.Ch_Id_RW Supply air damper - Channel id selected HR583 PIV2106 234 | k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 235
Cool/Heat status - Channel id selected HR638 PIV2161 CoolHeat_Dout.T_On_RW Cool/Heat status - Time on cycle relay HR639 PIV2162 CoolHeat_Dout.T_Off_RW Cool/Heat status - Time off cycle relay HR640 PIV2163 CoolHeat_Dout.Ch_Type_RW Cool/Heat status - Digital output type HR641 PIV2164 | 235 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 236
HR696 PIV2219 MainVlv_Close.Board_RW Main floating valve close - Board selected HR697 PIV2220 MainVlv_Close.Ch_Id_RW Main floating valve close - Channel id selected HR698 PIV2221 MainVlv_Close.T_On_RW Main floating valve close - Time on cycle relay HR699 PIV2222 236 | k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 237
Preheat heater 1 - Time on cycle relay HR754 PIV2277 PreHeatCoil_Step1.T_Off_RW Preheat heater 1 - Time off cycle relay HR755 PIV2278 PreHeatCoil_Step1.Ch_Type_RW Preheat heater 1 - Digital output type HR756 PIV2279 PreHeatCoil_Step2.Board_RW Preheat heater 2 - Board selected HR757 PIV2280 | 237 k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 238
HR812 PIV2335 ReHeatPmp_1.Ch_Id_RW Reheating pump 1 - Channel id selected HR813 PIV2336 ReHeatPmp_1.T_On_RW Reheating pump 1 - Time on cycle relay HR814 PIV2337 ReHeatPmp_1.T_Off_RW Reheating pump 1 - Time off cycle relay HR815 PIV2338 238 | k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 239
Mixing damper - Analogue output type HR870 PIV2393 FreshAirDamp_Aout.Board_RW Fresh air damper - Board selected HR871 PIV2394 FreshAirDamp_Aout.Ch_Id_RW Fresh air damper - Channel id selected HR872 PIV2395 FreshAirDamp_Aout.MinOut_RW Fresh air damper - Minimum analogue output signal HR873 AV2396 | 239 k.Air +030220981 rel. 1.1 – 31.03.2020...
12. Alarms and signals 12.1 Types of The k.Air controller manages three types of alarms, depending on the reset mode: automatic: the alarm is reset and the unit restarts automatically when the alarm condition is no longer alarms present; semi- automatic: if the alarm occurs several times, reset becomes manual and an operator needs to physically restart the unit;...
Page 246
To clear the alarm log, access screen Xe01. On the second row, it is possible to clear the event counter for requiring manual reset of semi-automatic alarms. Example:alarm A14; CO probe is shown in the alarm list, and the Start and Stop times are recorded in the log. 246 | 12. Alarms and signals k.Air +030220981 rel. 1.1 – 31.03.2020...
Ae03 - fan operating hours: alarm threshold, hours elapsed, reset hours; See the Parameter table for the complete list. For greater installation flexibility, k.air features three generic alarm inputs and three signal outputs. These 12.3 Generic contacts are always available, simply associate an activation channel using the I/O configuration menus alarm input and Wb03 and Wb04.
Page 250
Immediate return fan shutdown DI1164 AL162 EBM return fan-DC - link undervoltage (UzLow) Manual Immediate return fan shutdown DI1165 AL163 EBM return fan-Motor overheated (TFM) Manual Immediate return fan shutdown DI1166 250 | 12. Alarms and signals k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 251
VDI alarm - Check condensate precipitation in the humidifier chamber Automatic Unit shutdown / Display only (parameter) DI1222 AL220 VDI alarm - Check steam distribution system for deposits Automatic Unit shutdown / Display only (parameter) DI1223 12. Alarms and signals | 251 k.Air +030220981 rel. 1.1 – 31.03.2020...
For details on the procedure for saving and loading the user configurations, see the chapter “Commissioning”. On k.Air models equipped with a USB device (Slave) port, the application program can be updated by 13.1 connecting a computer to the controller via USB cable:...
Page 255
1. Return to the system menu and run the Application → Wipe retain command, or alternatively go to screen Ac30 and run the “Clear permanent memory” command. k.Air controllers include an FTP server that allows access to the public partition of the file system. It is thus 13.3 possible to read, modify, create and remove files and folders.
Page 256
Note: after uploading the update file to the upgrade folder via FTP, the update can also be started remotely via a virtual terminal. For further details, see the c.pCO manual +0300057EN. 256 | 13. Software update k.Air +030220981 rel. 1.1 – 31.03.2020...
Page 260
Delete this text and replace it with your own content. CAREL INDUSTRIES S.p.A. - Headquarters Via dell'Industria, 11 35020 Brugine - Padova (Italy) CAREL can accept no responsibility for possible errors in this manual. CAREL reserves the right to modify its products without notice. Tel. (+39) 049.9716611 Fax (+39) 049.9716600...
Need help?
Do you have a question about the k.Air and is the answer not in the manual?
Questions and answers