Class 'A' Abnormal; Channel Failure Abnormal; Channel Initialization Abnormal - Simplex 4100 Series Manual

Fire products - fault & assistance guide
Table of Contents

Advertisement

1.1.2.3.1

Class 'A' Abnormal

Description:
The addressable loop or RUI Bus has an open circuit.
Possible causes:
Open circuit in the wiring loop
Bad connection at addressable point (on addressable loop faults).
Bad connection at remote transponder or LCD Annunciator (for RUI Bus faults)
Faulty addressable loop or RUI card
-
Check this fault by „looping out‟ the A and B terminals on the RUI/Mapnet/IDNet card to clear
the fault. If fault does not clear then card may be faulty
1.1.2.3.2

Channel Failure Abnormal

Description:
The Loop card cannot communicate with any device on the loop. Be aware all devices associated with this
loop will indicate a „Normal‟ state to prevent multiple faults per display.
Possible causes:
The Loop has a Short circuit
The Loop has an Earth fault
The Loop is not connected or incorrectly connected
1.1.2.3.3

Channel Initialization Abnormal

Description:
This fault typically occurs at startup with IDNet loops and will normally clear after a couple of minutes if a lot
of Isolators are fitted.
Possible causes:
If the fault continually re-appears the loop length maybe too long or too noisy – Contact your local
Simplex® branch for assistance
Possible bad device causing communication errors
-
Disconnect devices at half way points until the fault clears to locate the faulty device
Page 11 of 60

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 4100 Series and is the answer not in the manual?

Questions and answers

Denis Lamarche
January 21, 2025

I keep receiving "in control ref P401-P432 Lamp trouble" far right corner says "abnormal"

User image 67902bae0b395

This manual is also suitable for:

4100a4100u4100+4100 classic

Table of Contents

Save PDF