Page 1
XBOXER XBC UNIT SIZES 10 - 65 WITH ECOSMART CONNECT CONTROL (CO) INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS FOR THE COMPLETE VENTILATION SOLUTION COMPLIANT 2016...
Page 2
XBOXER XBC ECOSMART CONNECT CONTROL (CO) CONTENTS - INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS PAGE 1.0 Introduction 2.0 XBOXER XBC Unit Access Concepts 3.0 Delivery of Equipment 4.0 Erection and Assembly 5.0 Dimensions and Weights 6.0 Installing XBC Fan Units and Attenuators 7.0 Commissioning and Setting To Work 8.0 Description Of Control Strategy (SW-FAC2612-2-12A) 9.0 Networking Example...
Page 3
XBOXER XBC 10-65 (CO Control) Supply & Extract Ventilation Unit with Heat Recovery The EMC Directive 2014/30/EU The Low Voltage Installation and Maintenance Directive 2014/35/EU 1.0 Introduction Code description: XBOXER XBC Ventilation Unit The information contained in this document provides details of XBC 45 - H - L - CO - WP - R - BA installation, operation and maintenance for installers and users of the XBOXER XBC Supply and Extract Ventilation Unit with Heat...
Page 4
LPHW or Electric Heater Battery LPHW or Electric Heater Battery Note: The unit is shipped with four G4 filters in place, two of which are included as spares. For F7 filters contact Nuaire. Figure 4. Standard Unit Format (Top view).
Page 5
• That all appropriate risk assessments have been carried out and the and vermin. required safety measures have been taken. If the storage period is to exceed two months, contact Nuaire for • That you understand the work required. guidance on the appropriate “mothballing” procedures.
Page 6
Figure 9. Plan view of unit with 4 hanging brackets attached (two each side of the unit). Unit Code Dimensions to Hole Centres (mm) XBC10-H-LES 1059 XBC15-H-LES 1059 XBC25-H-NBC 1207 XBC45-H-NBC 1309 1008 XBC55-H-NBC 1619 1058 XBC65-H-NBC 1619 1058 Compatible with 20mm Mez. nuaire.co.uk 029 2085 8200...
Page 8
XBC55-HE-MS12* 1250 XBC55-HS-MS16* 1600 XBC55-HE-MS16* 1600 XBC65-HS-MS10* 1050 XBC65-HE-MS10* 1050 XBC65-HS-MS12* 1250 XBC65-HE-MS12* 1250 XBC65-HS-MS16* 1600 XBC65-HE-MS16* 1600 2 attenuator flange connections are attached to every unit. Add 50mm to dimension 'A' to include both flanges. nuaire.co.uk 029 2085 8200...
Page 9
XBOXER XBC 10-65 Ecosmart Connect (CO) Control 5.5 XBOXER XBC Bend Attenuator Dimensions (mm) and Weights (kg) Figure 12. Bend attenuator dimensions (mm). Side view Plan view HS-MBS-S HS-MBS-L HE-MBS-L HE-MBS-S Duct Connection Duct Connection Attenuator Unit Attenuator Code Dimensions (mm) Weights (kg) XBC15-HS-MBS-S*...
Page 10
Foam Sealing Strip. 6. Secure the attenuators to the attenuator flange connector on the end of the fan unit. (see fig 10). Four piece support brackets. nuaire.co.uk 029 2085 8200...
Page 11
Exhaust RT Inlet RT IMPORTANT Unit Codes for Optional Exhaust and Inlet Terminals Isolation - Before commencing work, make sure that the unit, XBC10-EXHAUST-RT switched live and Nuaire control are electrically isolated from the XBC10-INTAKE-RT mains supply. XBC15-EXHAUST-RT XBC15-INTAKE-RT XBC25-EXHAUST-RT...
Page 12
Figure 16. Motorised damper installation options. Internal version (example: XBC15-MD-CO). External weather proof version (example: XBC15-MD-CO-WP). If matching length Nuaire silencers (example codes: XBC15-HS-MS16 & XBC15-HE-MS16) are being fitted to the fan unit, the motorised damper (example code XBC15-MD-CO) should to be fitted after the Fan unit silencers (as Figure 16).
Page 13
1 - NC XBC 25-85 Nuaire recommend the pressure switch be set to trigger when the Connect T29 T30 filters experience a 125 Pa increase above the clean filter resistance for Adapt Trend &...
Page 14
Isolation - Before commencing work, make sure that the unit, if not already doing so. switched live and Nuaire control are electrically isolated from the Piped connections should be made to the unit using appropriate mains supply.
Page 15
XBOXER XBC 10-65 Ecosmart Connect (CO) Control This page has been intentionally left blank 21. 07. 20. Leaflet Number 671748...
Page 16
Whenever a fan-speed override Room Module is connected, the display will automatically show the fan speed status at all times. 8.2 The Nuaire Unit Contains The Following Controllable A timeout can be set for the fan mode to revert back to auto after a Items: predetermined time period.
Page 17
XBOXER XBC 10-65 Ecosmart Connect (CO) Control 8.5 Plate Heat Exchanger Bypass Function Description Available Ranges The plate heat exchanger bypass damper runs on the FAC relay 5. Energised = 0-10V 0-10V is scaled as defined by the 0-2,000ppm Bypass. CO2 Sensor network input 0-4,000ppm...
Page 18
Vent Only Heatin g Bypass Room Deadband Point Bypass Free Heating Cooling Vent Only Min Supply O utside Outside Max Supply Boost Band Outside Air Temp Outside Air Temp Air Temp. Air Temp. Air Temp. Air Temp. nuaire.co.uk 029 2085 8200...
Page 19
XBOXER XBC 10-65 Ecosmart Connect (CO) Control 8.9 Trickle Mode 8.14 Alarms When trickle mode is active, the fans will run at their minimum speed even when 8.14.1 Critical Alarm Latching there is no enable signal. Heating and cooling will also function in this mode if available.
Page 21
XBOXER XBC 10-65 Ecosmart Connect (CO) Control 8.15 Exposed BACnet Object List (By Category) ENABLE LCD Browser BACnet Object Description Object Type Object ID Default Units Page Value Enable Software enable switch 10218 (1)Off (2)On SL Enable The state of the enable input (IN8) 10161 (0)Off (1)On Run-on (Enable)
Page 22
Set the type of heating fitted. 10206 As per Build (1)None (2)LPHW (3)Electric (4)3rd-Party Heating Output The 0-10v signal to the heating output 10179 Percent Heating Demand The state of the heating demand relay. 10197 (0)Off (1)On nuaire.co.uk 029 2085 8200...
Page 23
XBOXER XBC 10-65 Ecosmart Connect (CO) Control COOLING/ CONFIGURABLE OUTPUTS LCD Browser BACnet Object Description Object Object Default Units Page Type Value Cooling Type Set the type of cooling fitted. 10203 None (1)None (2)Chilled Water (3)3rd-Party Cooling Demand The state of the cooling demand relay. 10194 (0)Off (1)On OUT4 Mode...
Page 24
Purge Fan Speed 10304 Percent Purge Min Temp The minimum temperature that will stop 10305 Degrees-Celsius night cooling Purge Time Schedule Purge Time Schedule 10499 Purge Time Schedule State of the Purge Time Schedule 10512 (1)Off (2)On nuaire.co.uk 029 2085 8200...
Page 25
XBOXER XBC 10-65 Ecosmart Connect (CO) Control NIGHT COOL MODE LCD Browser BACnet Object Description Object Object Default Units Page Type Value Night C Mode This input will enable night cool mode. 10242 (1)Off (2)On Night C Fan Speed The night cool fan speed 10281 Percent Nigh C Min Temp...
Page 26
The voltage required to start the extract fan 17274 Volts SF Max Volt The upper voltage for the supply fan 17275 Volts SF Start Volt The voltage required to start the extract fan 17276 Volts SW-FAC2612-2-12A Strategy Version 17340 (1)Off (2)On nuaire.co.uk 029 2085 8200...
Page 27
XBOXER XBC 10-65 Ecosmart Connect (CO) Control 9.0 Networking Example 9.1 Network Connection Diagram Figure 24. Ethernet IP MTSP to IP Router (Field Controller) FC Bus (Sensor Actuator) SA Bus (Sensor Actuator) SA Bus For best results, use a linear network and switch on the EOL resistors at each end of the FC bus. 21.
Page 28
The shield must be earthed at the control panel end only and be made continuous along the bus length. Room Modules must not be fitted more than 150metres (cable length) from the controller. nuaire.co.uk 029 2085 8200...
Page 29
Cancel – Quit and moves Network Settings to the previous section Device Name FAD0351 TL-BRTRP-0 Device ID Home – Shortcut to the Nuaire BPS ESC 0909501 MAC Address configured Home Page Descriptions Field Advanced Display Nuaire BPS ESC 0909502 Baud Rate 38400 Back –...
Page 30
10.5 Quick Setup The following section explains how to quickly set-up the FAD with a target MAC Address object and some favourites. TL-BRTRP-0 Nuaire BPS ESC 0909501 10.5.1 Setting Up A Target Object Nuaire BPS ESC 0909502 Target objects allow the user to view a “target” device and object within the entire network.
Page 31
Note: If the target page is selected as the home page and a security password is set the home page will be locked. The only way to exit the target screen in this case is to press the Nuaire logo to the top right of the screen for 5 seconds.
Page 32
The only • Change the user password a 4 digit number way to exit the target screen in this case is to press the Nuaire logo to • The user password will now be requested each time a locked object the top right of the screen for 5 seconds.
Page 33
The text in parentheses denotes the alarm the event applies to. The log can hold up to 40 events. Nor(A CIR 2) Nuaire BPS 09:47 16-10-15 Logged alarm events can be deleted by using the delete icon. If all events are...
Page 34
It adjusts settings related to the Day, Month and Year of the FAD integrated clock. Time It adjusts settings related to the Hour and Minute of the FAD integrated clock. Day Of Week It adjusts settings related to the Day of Week (1-7) of the FAD integrated clock. nuaire.co.uk 029 2085 8200...
Page 35
XBOXER XBC 10-65 Ecosmart Connect (CO) Control Select Target Device Page 10.6.3 Parameter Name Description Default Setting Device Name Name of the device where the object resides MAC Address The MSTP address of the device where the object resides Device ID The BACnet ID of the device where the object resides Object Type The object type...
Page 36
Room Modules are electronic, wall-mountable sensors designed to work the current room temperature. The occupancy status is also displayed on the directly with the Nuaire control panel. LCD. On fan speed override models the fan speed and override status is also displayed.
Page 37
XBOXER XBC 10-65 Ecosmart Connect (CO) Control 11.4 Room Modules Wiring Screw terminal wiring: If RJ12 cables are not used, the screw terminal connections on the Room Modules can be used. Figure 34. Standard Sensor Wiring. SA Bus Screw Terminal Block Network Sensor SA+ SA- Bus Com...
Page 39
XBOXER XBC 10-65 Ecosmart Connect (CO) Control 11.6 AVAILABLE ROOM MODULES The following room modules are available. Group Nuaire Size Temper- Humidity LCD, Network Notes Part (mm) ature Sensor Setpoint Speed Status Sensor Address Number Sensor Adjust & Override Display...
Page 40
-20 to 60°C, t to 95% RH CO2 Sensor Warm Up Time Less than 1 Minute; less than 10 minutes for full accuracy. (Closed) (Open) 200-203 Address Switch Settings Address Switch Settings Switch 4 Switch 2 Switch 1 Not Supported (Closed) (Open) nuaire.co.uk 029 2085 8200...
Page 41
XBOXER XBC 10-65 Ecosmart Connect (CO) Control 11.9 Interconnection The sensors or other devices on the SA bus network connect either by modular RJ12 connections or by screwed terminals using plain ended cable. All sensors are fitted with both. 11.9.1 Modular Cable (Up To 30 Metres) The Room Modules can connect using a 24AWG twisted 3-pair cable with RJ12 connections over the Sensor Actuator (SA) bus, the following items are available.
Page 42
Room Modules must not be fitted more than 150metres (cable length) from the controller. Terminal Network Figure 37. Controller Screwed Terminal SA Bus Screwed Terminal (Brown) Room Module Screwed Terminal Screwed Terminal Room Module Room Module Cable Type: Plain-ended shielded 2 twisted pair 22AWG nuaire.co.uk 029 2085 8200...
Page 43
XBOXER XBC 10-65 Ecosmart Connect (CO) Control 12.0 Appendix To Software Strategy 12.1 BACnet Object List (By Instance Number) Please note: The numbers in parentheses before each multi state object is the enumerated object value for use with BACnet browsers. LCD Browser Name Description...
Page 44
SL2 Input The state of the configurable input (IN9) 10164 (0)Off (1)On Alarm Circuit 1 The state of Alarm Circuit 1 10167 (0)Alarm (1)Normal Alarm Circuit 2 The state of Alarm Circuit 2 10170 (0)Alarm (1)Normal nuaire.co.uk 029 2085 8200...
Page 45
XBOXER XBC 10-65 Ecosmart Connect (CO) Control LCD Brows- Name Description Type BACnet Object Units Default er Page Instance Number Value Bypass Damper Cmd The controller’s signal to the HX bypass. (Active = Bypass, 10185 (0)Inactive (1)Active Inactive = Heat Exchange) Fault Relay Cmd The state of the fault relay.
Page 46
Heater Test (Factory Use Only) 10247 (1)Off (2)On Test (Override Fan) Overtemp Test (Factory Use Only) 10248 (1)Off (2)On Test (Wiring) Wiring Test (Factory Use Only) 10249 (1)Off (2)On Trickle Mode Enable trickle mode 10250 (1)Off (2)On nuaire.co.uk 029 2085 8200...
Page 47
XBOXER XBC 10-65 Ecosmart Connect (CO) Control Name Description Type BACnet Object Units Default Browser Instance Value Page Number Purge Time Schedule State of the Purge Time Schedule 10512 (1)Off (2)On RM199 Fan Display Fan Speed Override Display at RM address 14703 (1)No Status (2)Off (3)Low (4) Medium (5)High (6)Auto-Off (7)
Page 48
This is a special object with the ability to have a Priority 16 Priority 16 Object changing value depending on the time of date or day of the week. Relinquish Relinquish Default Default Present Value Present Value nuaire.co.uk 029 2085 8200...
Page 49
XBOXER XBC 10-65 Ecosmart Connect (CO) Control Case 1 12.3 Inter-networking The object looks down the list until it gets to the first non-null value. In this case, Inter-networking is used to connect two BACnet networks operating on different all priority levels are empty so the (relinquish) default value of 0 is used as the physical mediums (e.g.
Page 65
XBOXER XBC 10-65 Ecosmart Connect (CO) Control 21. 07. 20. Leaflet Number 671748...
Page 66
LCD is disconnected. The correct installation procedure has See ESCO-LCD section for more connection information, see been carried out in accordance to Nuaire’s sections 8.15 & 12.1 for BACnet object lists. recommendations. 14.1.1 Setting The Min/Max Air Flow Anti-vibration mounts are adjusted accordingly.
Page 67
The product warranty applies to the UK mainland and in accordance service visits. with Clause 14 of our Conditions of Sale. Customers purchasing from outside of the UK should contact Nuaire International Sales office for Note: The unit application may require particular attention to this further details.
Page 68
UNIT CONTROL TYPE NOTES 21. 07. 20. Leaflet Number 671748...
Page 69
GENERAL In addition to the particular requirements given for the individual product, the following general requirements The equipment referred to in this Declaration of Incorporation is supplied by Nuaire to be assembled into a should be noted. ventilation system which may or may not include additional components.
Page 70
CF83 1NA +44 (0)29 2085 8200 +44 (0)29 2085 8222 info@nuaire.co.uk www.nuaire.co.uk As part of our policy of continuous product development Nuaire reserves the right to alter specifications without prior notice. Telephone calls may be recorded for quality and training purposes.