Appendix; Check Items By Error Code - Samsung AVR-M100FHAX Installation Manual

Base heater control kit
Table of Contents

Advertisement

Check items by error code

Symptom
During the Heat mode or the heater test run, the temperature on the heater does not increase.
1) Connection error
2) Outside temperature sensor error
Cause
3) Heater power connection error
4) Relay operation error
The connector is properly
connected between the heater
control box and outdoor unit
control box?
The outside temperature
sensor operates normally?
The heater power is connected
properly?
The relay operates normally?
Replace the heater.
CAUTION
Be sure to maintain the base heater periodically because it has no error code.
Yes
Yes
Yes
Yes
Check operation after connecting the
connector.
Check for connection of the outside
temperature sensor or replace it.
Check operation after connecting the heater
power.
Replace the relay.
English