ABB ACS150 Quick Installation And Start-Up Manual page 2

Mirco drives

Advertisement

POWER-UP
Apply input power.
The panel powers up into the Output mode.
ENTRY OF START-UP DATA
9902
Select the application macro (parameter
)
according to how the control cables are
connected. The default value 1 (ABB STANDARD)
is suitable in most cases.
The general parameter setting procedure in the
Short parameter mode is described below.
1. To go to the Main menu, press
if the
bottom line shows OUTPUT; otherwise press
repeatedly until you see MENU at the
bottom.
/
2. Press keys
until you see
"PAr S" on the display.
3. Press
. The display shows a parameter
of the Short parameter mode.
4.Find the appropriate parameter with keys
/
.
5. Press and hold
for about two seconds
until the parameter value is shown with
SET
under the value.
/
6.Change the value with keys
. The value changes faster while you
keep the key pressed down.
7. Save the parameter value by pressing
.
Enter the motor data from the motor nameplate.
• motor nominal voltage (
9905
)
• motor nominal current (
9906
)
• motor nominal frequency (
9907
)
Set the maximum value for external reference
REF1 (
1105
).
Set constant speeds 1, 2 and 3 (
1202, 1203, 1204)
.
Set the minimum value (%) corresponding to the
1301
minimum signal for AI(1) (
). Typical settings:
0% for 0...20 mA (or 0...10 V) signal
20% for 4...20 mA (or 2...10 V) signal
Set the maximum limit for the drive output
frequency (
2008
). This is equal to power line
frequency, typically. That is: 50 or 60 Hz.
Select the motor stop function (
2102
).
1 = Stop by cutting off the motor power supply.
Motor coasts to stop.
2 = Stop along ramp defined by parameter.
DIRECTION OF THE MOTOR ROTATION
Check the direction of the motor rotation.
1. Turn the potentiometer fully
counterclockwise.
2. If the drive is in remote control (REM shown on
the left), switch to local control by pressing
LOC
.
REM
3. Press
to start the motor.
4.Turn the potentiometer slightly clockwise until
the motor rotates.
5. Check that the actual direction of the motor is
the same as indicated on the display (FWD
means forward and REV reverse).
6.Press
to stop the motor.
To change the direction of the motor rotation:
1. Disconnect input power from the drive, and
wait 5 minutes for the intermediate circuit
capacitors to discharge. Lock out and tag out.
Measure the voltage between each input
terminal (U1, V1 and W1) and earth with a
multimeter to ensure that the drive is
discharged.
2. Exchange the position of two motor cable
phase conductors at the drive output
terminals or at the motor connection box.
3. Verify your work by applying input power and
repeating the check as described above.
ACCELERATION/DECELERATION TIMES
Set the acceleration time 1 (
2202
) and
deceleration time 1 (
2203
).
FINAL CHECK
The start-up is now completed. If you want to
save your setting as a user macro, scroll to
Parameter 9902 and select value -1 (USER S1
SAVE).
Check that there are no faults or alarms shown
on the display.
The drive is now ready for use.
Related documents
ACS150 user's manual
ACS150 manual list
3AFE68576032
9AKK107680A5637
3AXD50000625970 Rev A EN 2020-04-21
© Copyright 2020 ABB. All rights reserved.
Fault codes
This is a short list of fault messages.
LOC
00
.
Hz
Fault
Description
OUTPUT
FWD
F0001
OVERCURRENT - Output current has exceeded trip level.
F0002
DC OVERVOLT - Excessive intermediate circuit DC voltage.
F0003
DEV OVERTEMP - Drive IGBT temperature is excessive.
LOC
9902
S
F0004
SHORT CIRC - Short-circuit in motor cable(s) or motor.
PAR
FWD
F0006
DC UNDERVOLT - Intermediate circuit DC voltage is not sufficient.
F0009
MOT OVERTEMP - Motor temperature estimation is too high.
F0016
EARTH FAULT - Drive has detected earth (ground) fault in motor or motor cable.
F0022
INPUT PHASE LOSS - Intermediate circuit DC voltage is oscillating due to
LOC
rEF
missing input power line phase or blown fuse.
MENU
FWD
Ratings
LOC
PAr S
ACS150-
MENU
FWD
1)
x = E/U
9902
LOC
S
U
1-phase
= 230 V (200...240 V)
N
PAR
FWD
01x-02A4-2
01x-04A7-2
9907
LOC
S
01x-06A7-2
01x-07A5-2
PAR
FWD
01x-09A8-2
LOC
500
3-phase
U
= 230 V (200...240 V)
.
N
03x-02A4-2
Hz
PAR
SET
FWD
03x-03A5-2
03x-04A7-2
LOC
600
.
03x-06A7-2
Hz
PAR
SET
FWD
03x-07A5-2
03x-09A8-2
LOC
9907
S
U
3-phase
= 400/480 V (380...480 V)
N
03x-01A2-4
PAR
FWD
03x-01A9-4
9905
LOC
S
03x-02A4-4
03x-03A3-4
PAR
FWD
03x-04A1-4
03x-05A6-4
1105
LOC
S
03x-07A3-4
03x-08A8-4
PAR
FWD
I
continuous rms input current (for dimensioning cables and fuses)
1N
1202
LOC
S
I
(480 V) continuous rms input current (for dimensioning cables and fuses) for drives with
1N
480 V input voltage
PAR
FWD
I
continuous rms current. 50% overload is allowed for one minute every ten
2N
minutes.
I
maximum (50% overload) current allowed for one minute every ten minutes
LOC
1301
S
2,1/10
I
maximum output current. Available for two seconds at start, otherwise as long
2max
as allowed by the drive temperature.
PAR
FWD
P
typical motor power. The kilowatt ratings apply to most IEC 4-pole motors. The
N
horsepower ratings apply to most NEMA 4-pole motors.
LOC
2008
S
Fuses and typical power cable sizes
PAR
FWD
The table list the fuses for protection against short-circuits in the input power
LOC
2102
S
cable or drive. The table also shows typical power cable sizes.
ACS150-...x
PAR
FWD
= E/U
LOC
1202
S
1-phase
U
= 230 V (200...240 V)
N
PAR
FWD
01x-02A4-2
01x-04A7-2
01x-06A7-2 16/20
01x-07A5-2 20/25
forward
reverse
01x-09A8-2 25/35
U
3-phase
= 230 V (200...240 V)
N
03x-02A4-2
03x-03A5-2
03x-04A7-2
03x-06A7-2
03x-07A5-2
03x-09A8-2
U
3-phase
= 400/480 V (380...480 V)
N
03x-01A2-4
03x-01A9-4
03x-02A4-4
03x-03A3-4
03x-04A1-4
03x-05A6-4
2202
LOC
S
03x-07A3-4
03x-08A8-4
PAR
FWD
1)
If 50% overload capacity is needed, use the larger fuse alternative.
Ambient conditions
9902
LOC
S
Requirement
PAR
FWD
Installation altitude
Surrounding air
temperature
Relative humidity
Contamination levels
(IEC 60721-3-3: 2002)
Shock (IEC 60068-2-27,
ISTA 1A)
Free fall
Dimensions and weights
Frame
H1
size
mm
R0
169
R1
169
R2
169
Frame
H4
size
mm
R0
257
R1
257
R2
257
1)
200 V unit weight / 400 V unit weight
IP20 (cabinet) / UL open
H1
height without fastenings or clamping plate
H2
height with fastening and without clamping plate
H3
height with fastenings and clamping plate
W
width
D
depth
IP20 / NEMA 1 (drive with optional MUL-xx kit installed)
H4
height with fastenings and connection box
H5
height with fastenings, connection box and hood
Input
Output
I
I
I
I
I
1N
1N
2N
2,1/10
2max
(480 V)
A
A
A
A
A
kW
6.1
-
2.4
3.6
4.2
0.37
11.4
-
4.7
7.1
8.2
0.75
16.1
-
6.7
10.1
11.7
1.1
16.8
-
7.5
11.3
13.1
1.5
21.0
-
9.8
14.7
17.2
2.2
4.3
-
2.4
3.6
4.2
0.37
6.1
-
3.5
5.3
6.1
0.55
7.6
-
4.7
7.1
8.2
0.75
11.8
-
6.7
10.1
11.7
1.1
12.0
-
7.5
11.3
13.1
1.5
14.3
-
9.8
14.7
17.2
2.2
2.2
1.8
1.2
1.8
2.1
0.37
3.6
3.0
1.9
2.9
3.3
0.55
4.1
3.4
2.4
3.6
4.2
0.75
6.0
5.0
3.3
5.0
5.8
1.1
6.9
5.8
4.1
6.2
7.2
1.5
9.6
8.0
5.6
8.4
9.8
2.2
11.6
9.7
7.3
11.0
12.8
3
13.6
11.3
8.8
13.2
15.4
4
Fuses
Size of CU conductor in cablings
gG
UL
Supply
Motor
PE
Class T
(U1, V1, W1)
(U2, V2, W2)
(600 V)
2
2
2
A
A
mm
AWG
mm
AWG
mm
AWG
10
10
2.5
14
0.75
18
2.5
16
20
2.5
14
0.75
18
2.5
1)
25
2.5
10
1.5
14
2.5
1)
30
2.5
10
1.5
14
2.5
1)
35
6
10
2.5
12
6
10
10
2.5
14
0.75
18
2.5
10
10
2.5
14
0.75
18
2.5
10
15
2.5
14
0.75
18
2.5
16
15
2.5
12
1.5
14
2.5
16
15
2.5
12
1.5
14
2.5
16
20
2.5
12
2.5
12
2.5
10
10
2.5
14
0.75
18
2.5
10
10
2.5
14
0.75
18
2.5
10
10
2.5
14
0.75
18
2.5
10
10
2.5
12
0.75
18
2.5
16
15
2.5
12
0.75
18
2.5
16
15
2.5
12
1.5
14
2.5
16
20
2.5
12
1.5
14
2.5
20
25
2.5
12
2.5
12
2.5
During operation (installed for stationary use)
0...2000 m (0...6562 ft) above sea level (with output derating
above 1000 m [3281 ft])
-10...+50 °C (14...122 °F). If the temperature is more than 40 °C
(104 °F), output derating is necessary. No frost permitted.
0...95% without condensation
No conductive dust permitted
Not permitted
Not permitted
IP20 (cabinet) / UL open
H2
H3
W
D
in
mm
in
mm
in
mm
in
mm
in
6.65
202
7.95
239
9.41
70
2.76
142
5.59
6.65
202
7.95
239
9.41
70
2.76
142
5.59 1.3/1.2
6.65
202
7.95
239
9.41
105
4.13
142
5.59
IP20 / NEMA 1
H5
W
D
-
in
mm
in
mm
in
mm
in
-
-
10.12
280
11.02
70
2.76
142
5.59
-
-
10.12
280
11.02
70
2.76
142
5.59
-
-
10.12
282
11.10
105
4.13
142
5.59
-
-
Free space requirements
Above
mm
in
75
3
Markings
The applicable markings are shown on the type designation label
CE
UL
Frame
size
P
N
hp
0.5
R0
1
R1
1.5
R1
2
R2
3
R2
0.5
R0
0.75
R0
1
R1
1.5
R1
2
R1
3
R2
0.5
R0
0.75
R0
1
R1
1.5
R1
2
R1
3
R1
4
R1
5
R1
00353783.xls J
Brake
(BRK+ and
BRK-)
2
mm
AWG
14
2.5
14
14
2.5
14
10
2.5
12
10
2.5
12
10
6
12
14
2.5
14
14
2.5
14
14
2.5
14
12
2.5
12
12
2.5
12
12
2.5
12
14
2.5
14
14
2.5
14
14
2.5
14
12
2.5
12
12
2.5
12
12
2.5
12
12
2.5
12
12
2.5
12
00353783.xls J
Weight
kg
lb
1.1
2.4
1)
1)
2.9/2.6
1.5
3.3
Weight
kg
lb
1.5
3.3
1)
1)
1.7/1.6
3.7/3.5
1.9
4.2
3AXD00000353783 L
Below
Sides
mm
in
mm
in
75
3
0
0
3AXD00000353783 L
RCM
EAC
WEEE
EIP