6 Configuration, Parametrization
ErrorCode
Error codes for BadDeviceAdr 0-125, i.e. for the corresponding
Profibus slave
err_
event
2
3
9
17
18
21
Table 6-3: PROFIBUS-DP master / Parameter ErrorCode 1
Error codes for BadDeviceAdr 255, i.e. for Profibus master
err_
event
0
50
51
52
53
54
55
page 40
Signification
station reports overflow
request function of master
is not activated in the
station
no answer-data, although
the slave must response
with data
no response of the station
master not into the logical
token ring
faulty parameter in request
signification
no mistakes appear
USR_INTF-Task not found
no global data-field
FDL-Task not found
PLC-Task not found
non existing master parameters
faulty parameter-value in the
master parameters
field bus PROFIBUS-DP
error
Help
Source
master
check length of configured
telegram
slave configuration or
parameter data
master
check slave if
telegram
PROFIBUS_DP norm
compatible
slave
check configuration data of
the station and compare it
with the physical I/O data
length
slave
check bus cable, check bus
address of slave
DEVICE
check FDL-Address of
master or highest-station-
Address of other master
systems. examine bus
cabling to bus short circuits
master
contact hotline
telegram
error
source
DEVICE
contact
technical support
DEVICE
contact
technical support
DEVICE
contact
technical support
DEVICE
contact
technical support
DEVICE
execute download of
data base again
project
contact
planning
technical support