Input Specifi Cations - Mitsubishi Electric PUHZ-W50VHA Technical Manual

Air to water (atw) heat pump, interface (i/f) and flow temp. controller (ftc)
Hide thumbs Also See for PUHZ-W50VHA:
Table of Contents

Advertisement

6. Input specifi cations
Demand control is available by external input.
It is possible to set the outdoor unit's power consumption by setting the switch of the interface controller.
• REMOTE SWITCH Type A (4bit - 8 setting) / Type B (1bit -1 setting)
TB142
TB142
TB142
10-11
10-12
10-13
(COM-IN5)
(COM-IN6)
(COM-IN7)
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
OFF
OFF
OFF
Demand control is available by connecting remote switches with termi-
nal No.10 - 14.
Make sure to use the non-voltage switch (for the remote switch).
Remote switch cable length : Maximum 10m
Remote switch : Minimum applicable load DC12V, 1mA
• 4-20mA / 1-5V / 0-10V / 0-10kΩ
1 Use 4-20mA / 1-5V / 0-10V
Connect the transmission cables to No. 3 and 4 on the terminal
block (TB62).
No. 3 on the terminal block(TB62) : Plus side
No. 4 on the terminal block(TB62) : Minus side (Reference side)
2 Use adjustable resistor (0-10kΩ)
Connect the transmission cables to No. 1 and 2 on the terminal
block (TB62).
Adjust-
able resistor
4-20mA
(0-10kΩ)
0~100Ω
4~5mA
510Ω
7mA
1kΩ
9mA
2kΩ
11mA
3.3kΩ
13mA
4.3kΩ
15mA
5.6kΩ
17mA
7.5kΩ
19~20mA 4.75~5V
10kΩ
OPEN(12kΩ~) –
*The values of the above table show the mid-point of each step range.
tolerance : 0-10kΩ : ±5%
4-20mA : ±0.4mA
1-5V : ±0.1V
0-10V : ±0.2V
Cable length : Maximum 10m
TB142
Step for capacity setting
10-14
TypeA
(COM-IN8)
OFF
[OFF]
OFF
OFF
[ON]
Step1
OFF
Step2
OFF
Step3
OFF
Step4
OFF
Step5
OFF
Step6
OFF
Step7
100%
ON
Auto step
At site
{
4 bit 8 switch
OFF~AUTO step
Step for
1-5V
0-10V
capacity
setting
0~1.25V
0~0.63V
OFF
1.75V
1.88V
Step1 10%
2.25V
3.13V
Step2 20%
2.75V
4.38V
Step3 30%
3.25V
5.63V
Step4 50%
3.75V
6.88V
Step5 70%
4.25V
8.13V
Step6 80%
9.38~10V Step7 100%
Auto step
OFF
TypeB
0%
[OFF]
OFF
0%
10%
[ON]
Step1
10%
20%
Step4
50%
30%
50%
Step7
100%
70%
80%
Auto step
I/F
At site
I/F
10
10
11
11
Step1
12
12
Step4
13
13
Step7
14
14
AUTO step
TB142
TB142
TB62
Remark
0%
Stop
Fixed capacity
(Hz fi xed) mode
Auto step mode
0%
Stop
32
Remark
OFF
Fixed capacity
(Hz fixed)
mode
Auto step mode
Photo. 6-1
TB142