Panasonic PAW-160MAH2L Installation Instructions Manual page 97

Air handling unit kit for panasonic ecoi; panasonic eco g; panasonic paci
Table of Contents

Advertisement

c. On the terminal connector of Section C, located on the upper mounting board inside the
AHU Kit enclosure (see diagram below), connect the digital inputs (DI) as follows:
● Heating start to COM and DI1
● Cooling start to COM and DI2
● Fan mode (free cooling) start to COM and DI3
● All DI contacts open = Stop
3. In order to activate the 0–10 V demand control mode for the external BMS, remove the jum-
per (JP1) between terminals "M2-5" and "M2-6 (FREE)" on the AHU kit's terminal connector
of section F. Make sure that all other jumpers remain intact.
4. For advanced version only:
On the AHU kit's terminal connector of section F, disconnect the white wire from terminal
"M2-1" and the red wire from terminal "M2-2".
For medium version: Proceed with step 5.
5. In 0–10 V demand control mode, in order to achieve the default relation of voltage versus ca-
pacity as shown in step 7, adapt the wiring on the AHU Kit's terminal connector of section F
as follows (see also "5.4 Terminal board layout").
For advanced version: Remove the jumpers from M2-1, M2-2 to M2-3 and M2-4 and connect
the positive pole ("+") to "M2-3" and the negative pole ("–") to "M2-4".
For medium version: Connect the positive pole ("+") to "M2-3" and the negative pole ("–") to
"M2-4".
6. Close the AHU Kit enclosure again (see "4.1 Installation of AHU Kit" – step 5).
7. Via the signal wiring from the external BMS, select the 0–10 V demand control functionality
as follows:
Input
0
1.0
Voltage* (V)
Demand (% of
No cut
40
1
nominal current)
Indoor unit
Stop
1
start / stop
1 No cut/Stop: AHU system / indoor unit is completely switched off.
2 No Limit: No restrictions applied by BMS to AHU system / indoor unit performance (equivalent to "full-load operation" of AHU system / indoor unit).
Note:
The control system is based on the rule that the last command within a sequence always
takes precedence over the previous commands. In order to avoid unexpected control behavi-
our in a system where both 0-10 V demand control signals and digital input signals are being
used, it is very important to ensure that the DI signals are applied BEFORE applying the
demand control signals.
1.5
2.0
2.5
3.0
3.5
4.0
4.5
45
50
55
60
65
70
75
5.0
5.5
6.0
6.5
7.0
7.5
80
85
90
95
100
105
Start
Control
8.0
8.5
9.0
9.5
No limit / Full
110
115
120
capacity
2
95

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents