Important information Limitation of liability To the maximum extent permitted by applicable law, in no event will UTCFS be liable for any lost profits or business opportunities, loss of use, business interruption, loss of data, or any other indirect, special, incidental, or consequential damages under any theory of liability, whether based in contract, tort, negligence, product liability, or otherwise.
Product range The compact repeater series includes the panels shown below. Table 1: Compact repeater panels Model Description ZP2-ER-C Addressable fire and evacation alarm repeater panel with fire routing and fire protection controls (compact) ZP2-FR-C Addressable fire alarm repeater panel (compact)
Installation and commissioning This section provides detailed installation, connection, and commissioning information for your control panel. Caution: This product must be installed and maintained by qualified personnel adhering to the CEN/TS 54-14 standard (or the corresponding national standard) and any other applicable regulations. Electrical safety WARNING: Electrocution hazard.
Cabinet assembly The cabinet assembly is shown below. Remove the cover and the interface to access the PCB. Figure 1: Cabinet assembly ZP2 Series Compact Repeater Installation Manual...
Figure 3: Cabinet (back view) 1. DIN rail hook 2. Din rail locking clip Cabinet installation Where to install the control panel Install the control panel in a location that is free from construction dust and debris, and immune to extreme temperature ranges and humidity. Leave enough floor and wall space to allow the control panel to be installed and serviced without any obstructions.
Page 10
Fixing the cabinet to a wall Fix the cabinet to a wall using three M4 × 30 screws and three Ø 6 mm wall plugs, as shown in Figure 4 below. Figure 4: Mounting hole locations To fix the cabinet to a wall: 1.
Page 11
Fixing the cabinet to a DIN rail The cabinet can also be installed onto a top hat DIN rail (type EN 50022) using the mounting hooks and locking clips provided (see Figure 3 on page 5). To fix the cabinet to a DIN rail: 1.
Page 12
Adding the menu inserts Add the control panel interface menus as shown below. Figure 6: Adding the menu inserts The inserts are numbered 1, 2, 3, and 4, and are inserted at the location indicated (with the printed area facing the front of the control panel). For evacuation panels, remember to add descriptions for any output groups assigned to the programmable buttons to insert 3.
Recommended cables Recommended cables for optimal system performance are shown in the table below. Table 2: Recommended cables Cable Cable requirements Maximum cable length Power cables 2 × 1.5 mm Fire network cable Twisted-pair, CAT5 1.2 km 28 to 16 AWG (0.08 - 1.5 mm²) Ethernet cable Unshielded CAT5 30 m [1]...
Connecting inputs Connect input switches to IN1 and IN2, as shown in Figure 8 below. For input supervision (open and short circuit), install a 15 kΩ resistor. Figure 8: Connecting inputs If an input is not used, the 15 kΩ end-of-line resistor must be installed across the unused terminals to avoid an open circuit fault on the input.
Connecting the external power supply Connect the external power supply to VIN1, as shown in Figure 10 below. Note: You can connect an optional secondary external power supply to VIN2. In the event of a failure in the primary power supply, the panel will automatically switch to the secondary power supply.
Connecting remote expansion equipment Connect remote expansion equipment as shown in Figure 12 below. Use the power connector to supply power to remote equipment, if required. Figure 12: Connecting remote expansion equipment Connecting an external printer Connect an external EPSON LX300 printer to RS-232. Note: This option requires the 2010-2-232-KIT (not supplied) to be installed onto the RS-232 connector (see Figure 2 on page 4).
Commissioning After the compact repeater is installed and configured, the panel must be commissioned. Check the following: • That the fire system is designed in accordance with all required regulations and standards • That the maximum alarm current in your installation does not exceed the maximum current specifications of the power supply •...
Maintenance To ensure correct functioning of your control panel and fire alarm system, and compliance with all European regulations, the following maintenance checks should be followed. Caution: Ensure that fire routing (where configured) has been disabled or that the fire brigade has been notified of any planned fire alarm tests. Quarterly maintenance Contact your installation or maintenance contractor to carry out a quarterly inspection of the fire alarm system.
Technical specifications Power supply specifications Supply voltage (VIN1, VIN2) Nominal 24 VDC Minimum 20 VDC Maximum 30 VDC Typical current consumption (with no 190 mA at 24 VDC devices connected) LCD specifications Display type 240 x 128 dot graphic LCD (monochromatic) LCD dimensions (L x W) 83 x 44 mm (active area) Backlight type...
Page 20
Configurable inputs Configurable options For configuraton options, see your fire panel installation manual. Relay outputs Number of relay outputs Relay output specification Potential free, NO/NC/C Maximum output current 2 A / 30 VDC Remote equipment outputs Output voltage [1] Supply voltage (VIN1, VIN2) − 1.5 V (for example, 22.5 V at 24 V) Minimum Supply voltage (VIN1, VIN2) −...
Regulatory information European standards for electrical safety and electromagnetic compatibility These control panels have been designed in accordance with the following European standards for electromagnetic compatibility: • EN 50130-4 • EN 61000-6-3 • EN 61000-3-2 • EN 61000-3-3 ZP2 Series Compact Repeater Installation Manual...
Page 24
ZP2 Series Compact Repeater Installation Manual...
Need help?
Do you have a question about the ZP2-ER-C and is the answer not in the manual?
Questions and answers