dormakaba ED900 Installation Instructions – Double egress door
B.3.1 Troubleshooting chart, information messages.
Red
No.
Display
Description
LED
Communication error, double
door system
•
No communication
6
ln 61
Off
between the two operators.
Current measuring circuit
•
System could not
successfully perform
7
ln 72
Off
internal current measuring
test , performed once
every 24 hours.
Braking circuit test
•
System could not
successfully perform
8
ln 73
Off
internal braking circuit
test , performed once
every 24 hours.
DCW® communication
•
At least one registered
9
ln 91
Off
DCW device is missing.
B.4
Troubleshooting chart, "E" codes
B.4.1 Troubleshooting chart, "E" codes.
•
No.
Display
Red LED
Locking device error
•
Flashing
1
E 02
2 x
Flashing
2
E 03
DCW® program switch is missing.
3 x
Safety sensor test error
•
Flashing
3
E 04
4 x
EEPROM error
•
Flashing
4
E 12
12 x
•
ED900
Troubleshooting information messages
Reference ED900 double door installation manual.
1. Check communication cable connection at the two operators.
•
Cable connects to the horizontal RJ 45 connector next to the user
interface. Check communication cable.
1. The initial current measuring test my not always be successfully
completed due to system tolerances and environmental conditions.
2. The test may also fail, as an example, if someone uses the door while the
test is in progress.
1. The initial braking circuit test my not always be successfully completed
due to system tolerances and environmental conditions.
2. The test also may fail, as an example, if someone uses the door manually
while the test is in progress.
3. If the cyclical test fails ten times in a row, error message ln 73 will be
displayed.
1. Reconnect the corresponding DCW® device.
2. If this is not possible, reactivate the drive. Reactivation can be done by:
•
Switching program switch to Close (off).
•
Pressing both 4 button keypad left
than 3s.
Description
Operator is attempting to open
or close a locking device with
feedback, or a DCW® locking
device. An error has occurred
during this process.
Test of moving safety sensors
was unsuccessful.
Internal memory check could
not be completed.
Drive unit works in door closer
mode.
08125330
Troubleshooting error codes
1. Probable causes are a defective locking device or wiring defect.
•
Check the locking device and feedback system.
1. Check the DCW® program switch and its connections.
1. Factory setting level of "safety sensor test" parameter ST is 0,
test off (Appendix A, Parameter detail).
2. When ST is configured to installed safety sensors, a test signal is
sent to the sensors before each door opening or closing cycle.
Operator waits for a response within a certain time window.
3. Check whether parameter ST has been configured to the
installed safety sensors and their active-high or active-low signal
level.
4. Check for activation of the test at the safety sensors.
1. Using dormakaba handheld, reload current firmware to
reinitialize system.
2. If the error is still present, the control unit must be replaced.
Appendix B
and right
buttons greater
02-2020
111