Air sampling smoke detection system
TITANUS SuperSens
Quick Guide for Commissioning
1
Installation
§ Connect power (24V)
§ Connect outputs for info- (AL1), pre- (AL2) and mainalarm (AL3) as well as "fault"
(switchover relay contacts)
§ Connect reset input
§ Connect ext. input "night" (alt.Sens.) (if required)
§ Connect pipe system or test pipe
2
Set Up
Set DIP switches on pcb "basis E603.1" according to tables below:
Air flow monitoring
switch
Delay time
S2
A(1)
B(2)
ON
OFF
Short
ON
OFF
Middle
ON
ON
Long
OFF
OFF
very long
Alarm
switch
Delay time
S2
E(5)
F(6)
OFF
ON
Short
ON
OFF
Middle
OFF
ON
Long
ON
ON
very long
Fault
switch
S2
J(10)
OFF
Fault not latching
ON
Fault latching until reset
Atmospheric pressure compensation
R58
MP1 (+)
MP2 (-)
Switch
S2
C(3)
ON
30 s
2 min. (standard)
OFF
15 min.
OFF
1 h
ON
Switch
S2
G(7)
0 s
ON
10 s (standard)
OFF
30 s
ON
60 s
OFF
(standard)
see correction table for atm.pressure
Fire & Security Products
range
D(4)
OFF
small
I
ON
middle
II
OFF
large
III
ON
very large
IV
sensitivity
H(8)
ON
0,2 %/m
I
ON
0,1 %/m
II
OFF
0,05 %/m
III
OFF
0,025 %/m
IV
or
2,50 V (standard)
Siemens Building Technologies Group
(standard)
(standard)