6
Operation and indicator elements, mode of opera-
tion (PMI)
6.1
Operating panel
6.1.1
General
Building Technologies
Fire Safety & Security Products
The system operating panel is also called Person Machine Interface - PMI.
Overview operating functions
Related to Alarm
Related to disable system parts
Acknowledge
Reset
Sounder/Resound
sounders
Silence buzzer
Cancel alarm delay
Mode manned / un-
manned
cancel alarm delay
Operating access
Level 1
Operating functions always possible
Level 2
Operating functions accessible via access code or key switch
The default access code is 4233
–
Level 3
For user programming only, with additional access code
Level 4
Used to upload the panel software with additional equipment. The panel
needs to be open by removing the four allen screws.
Inscription stripes
Label the individual zone texts in the Word template (available via hotline).
Each zone LED must have a clear individual zone text, which indicates the geo-
graphical location of the corresponding detectors and / or manual call points.
Inserting inscription stripes
Operation and indicator elements, mode of operation (PMI)
Disable / Enable zones 1 to xx
Disable / Enable alarm horn
Disable / Enable fire controls
Disable / Enable remote alarm
Disable / Enable remote fault
automatic time-out after 3 min
set individual access code, preferably 6 digits
disable access code if a key switch is used
Related to system test
Mode detector test / Cancel
Mode walk test / Cancel
Test alarm horn for 30 sec.
Simulation of zone alarm
Simulation of zone fault
Lamp test
Service function
A6V10265083_a_en_--
21