Heating Limit; Mode Of Operation Of Eco Function 1; Mode Of Operation Of Eco Function 2; Pump Overrun - Siemens RVD240 Basic Documentation

District heating and domestic hot water controller
Table of Contents

Advertisement

Example
Example
Siemens Building Technologies
HVAC Products
• The composite outside temperature (T
is attenuated compared to the actual outside temperature, it represents the effects of
short-time outside temperature variations on the room temperature as they often oc-
cur during intermediate seasons (spring time and autumn)
The thermal inertia of the house or building in the case of outside temperature varia-
tions is taken into account by including the composite outside temperature in the auto-
matic ECO function.

12.6.3 Heating limit

The automatic ECO function necessitates a heating limit. An ECO temperature can be set
separately for each heating circuit in the range –10 K...+10 K (operating line 61). From
this setting value and the room temperature setpoint, the heating limit will be calculated.
The switching differential of 1 K for switching on / off is entered as a fixed value.

12.6.4 Mode of operation of ECO function 1

ECO function 1 operates as an automatic summer / winter function. The heating will be
switched off (mixing valve closed and heating circuit pump off) when the attenuated
outside temperature exceeds the heating limit.
The heating will be switched on again when all 3 outside temperatures have dropped
below the heating limit by the amount of the switching differential.
The heating limit is determined as follows:
Heating limit = T
+ T
RwN
ECO
A nominal room temperature setpoint w
–5 K result in a heating limit of +15 °C.

12.6.5 Mode of operation of ECO function 2

ECO function 2 operates as an automatic 24-hour heating limit. The heating will be
switched off (mixing valve closed and heating circuit pump off) when the actual or the
composite outside temperature exceeds the heating limit.
The heating will be switched on again when all 3 outside temperatures have dropped
below the heating limit by the amount of the switching differential.
The heating limit is determined as follows:
Heating limit = T
+ T
Rw akt
ture).
In contrast to ECO function 1, function 2 also considers when reduced heating is used.
A current room temperature setpoint T
of –5 K result in a heating limit of +13 °C.
The heating limit has a minimum limitation; it cannot be lower than 2 °C.
12.7

Pump overrun

Pump overrun for the heating circuit pump can be set in the range 0...40 minutes (op-
erating line 72). Setting 0 deactivates pump overrun.
12.8

Maximum limitation of the room temperature

The room temperature for each heating circuit can be separately limited to a maximum
value. For that purpose, a room sensor is required (sensor or room unit).
The limit value is generated from the nominal room temperature setpoint plus the value
entered on operating line 73.
Basic documentation RVD240
12 Function block Space heating
). Since the composite outside temperature
AM
(nominal room temperature setpoint plus ECO temperature).
of +20 °C and an ECO temperature T
N
(current room temperature setpoint plus ECO tempera-
ECO
of +18 °C and an ECO temperature of T
Rw akt
of
ECO
ECO
47/126
CE1P2384en
27.05.2004

Advertisement

Table of Contents
loading

Table of Contents