Summary Of Wirings And Settings; Operation Principle; Time Scheme - ABB +Q950 User Manual

Prevention of unexpected start-up option for multidrives
Table of Contents

Advertisement

16 Option description
user's manual (3AXD50000015612 [English]) or FSO-21 safety functions module user's
manual (3AXD50000015614 [English]).
The design principles of the option +Q950 comply with EN ISO 13850. The STO function
complies with EN/IEC 61800-5-2. For a complete list of related standards and European
directives, see section Related standards and directives.

Summary of wirings and settings

The wirings and settings of the POUS function are:
The inverter units are equipped with the FSO safety functions modules (option +Q973
or +Q972). ABB installs the modules at the factory.
The user must wire a dual-channel POUS switch to the FSO module. See section Wiring.
The user can wire a POUS indication lamp to the FSO module (optional).
The digital input of the FSO module to which the POUS switch is connected, is selected
as the input for the POUS request. This is an FSO module parameter that ABB sets at
the factory. The user must check the setting at the start-up.
The digital output of the FSO module to which the POUS indication lamp is connected,
is selected as the output for the POUS completed signal. This is an FSO module
parameter that ABB sets at the factory. The user must check the setting at the start-up.
For a detailed description of wirings, see sections Operation principle diagram and Wiring.
For a detailed description of parameter settings, see section Parameter settings.

Operation principle

Operation principle

Time scheme

Time scheme
This time scheme diagram illustrates the operation of the POUS function. This safety function
uses the POUS function of the FSO module. For more information, see the FSO module
This time scheme diagram illustrates the operation of the POUS function. This safety
user's manual.
function uses the POUS function of the FSO module. For more information, see the FSO
module user's manual.
Motor speed
1
A
POUS indication delay (see parameter POUS.13): An additional security delay. The POUS
completed indication (parameter POUS.22) becomes active after this delay.
Step
Description
1
The user stops the motor.
A
2
3
Option description and instructions 15
4
5
Time
POUS switch
(POUS request)
STO status
(POUS status)
POUS
indication lamp