Fault Finding; Fault Finding Chart Main Menu - Ideal Boilers LOGIC MAX HEAT H 18 Installation & Servicing

Hide thumbs Also See for LOGIC MAX HEAT H 18:
Table of Contents

Advertisement

4.1 FAULT FINDING CHART MAIN MENU

In order to assist fault finding the boiler has a 7 segment display. The key to the display codes is as follows:
'F2' or 'Fn' or 'Ln'
'F9' or 'L9' or 'F8' or 'L8'
NO DISPLAY
RESTART PROCEDURE - To restart boiler, press the "RESTART" button.
Installation and Servicing
SECTION 4 - FAULT FINDING
'L1'
'L2'
'LC'
'L6'
'L7'
'FA'
'Fd'
'F3'
'L4' or 'F4'
'L5' or 'F5'
'F6'
'F7'
'FU'
NO CH
NO HW
GO TO SECTION 4.2 -
FLOW TEMPERATURE OVERHEAT LOCKOUT
or NO WATER FLOW LOCKOUT
GO TO SECTION 4.3 -
IGNITION LOCKOUT
5 RESTARTS WITHIN 15 MINS -
TURN POWER OFF AND ON
GO TO SECTION 4.4 -
FALSE FLAME LOCKOUT
<5ºC RISE ON 3 SUCCESSIVE OCCASIONS.
CHECK THERMISTORS ARE CLIPPED ONTO PIPES
Note: burner will be switched off for 2 mins between
attempts. Function inactive if temperature is >40ºC.
GO TO SECTION 4.5 -
FLOW / RETURN REVERSED
GO TO SECTION 4.6 -
NO WATER FLOW
GO TO SECTION 4.7 -
FLAME LOSS
GO TO SECTION 4.8 -
FAN FAULT
GO TO SECTION 4.9 -
CONTROL/NO FLOW THERMISTOR FAULT
GO TO SECTION 4.10 -
RETURN THERMISTOR FAULT
GO TO SECTION 4.11 -
OUTSIDE SENSOR FAULT
LOW MAINS VOLTAGE -
CONTACT ELECTRICITY PROVIDER
PCB UNCONFIGURED/FAULTY OR GAS VALVE
SHORT CIRCUIT. SEE SECTION 3.18. IF
FAULT PERSISTS REPLACE PCB
DIFF GREATER THAN 50ºC. CHECK ISOLATION
VALVES ARE OPEN, CHECK PUMP, CHECK RAD
VALVES OPEN, CHECK SYSTEM BLOCKAGES.
GO TO SECTION 4.12
GO TO SECTION 4.14
GO TO SECTION 4.13
55

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LOGIC MAX HEAT H 18 and is the answer not in the manual?

Questions and answers

David Pegg
February 12, 2025

what is the best working temperature for boiler to be set at

1 comments:
Mr. Anderson
February 12, 2025

The Ideal Boilers LOGIC MAX HEAT H 18 controls central heating radiator temperature up to a maximum of 80°C, adjustable via the central heating temperature knob. The recommended working temperature depends on the heating needs, but it typically ranges between 30°C (minimum) and 80°C (maximum).

This answer is automatically generated

Table of Contents

Save PDF