3.18 PCB REPLACEMENT

Note. Fit the earth strap provided with the PCB to your wrist and
secure to a suitable earth on the boiler chassis.
1. Refer to Section 3.8.
2. Ensure the control knobs are in the 12 o clock position.
3. Carefully release the six retaining clips and remove control
box cover.
4. Unplug all lead connections to the PCB.
5. Remove the 2 screws, if applicable.
6. Spring out the four side retaining clips and pull the PCB
upwards to clear the corner retaining posts.
7. Take the new PCB.
8. Re-connect all plug connections.
9. Reassemble in reverse order.
10. a. Turn power on, display shows uP.
Rotate both dials fully
anti-clockwise.
b.
Press RESTART, display shows oF
c.
Turn power off
d.
Turn power on, display shows F9
e.
Using central heating knob, rotate clockwise or
anticlockwise to show "H" for Heat, then press
RESTART button.
f.
Using central heating knob, rotate clockwise or
anticlockwise to show "n" for Natural Gas, then press
the RESTART button.
g.
Using central heating knob rotate clockwise or
anticlockwise to show boiler size, select correct 12, 15,
18, 24 or 30, then press RESTART button.
h.
Display shows "H", "n", Boiler size, internal number.
j.
Press restart. New PCB is now programmed.
11. Check operation of the boiler.
Refer to Sections 2.26 & 2.27.

3.19 WATER FLOW SWITCH HEAD REPLACEMENT

1. Refer to Section 3.8.
2. Drain the Boiler. Refer to Section 3.20,
item no. 2.
3. Pull off the electrical connection.
4. Turn the retaining collar anti-clockwise and
pull the head from the housing.
5. Fit the new water flow switch head,
ensuring the electrical lead connections
wires point to the left as shown.
6. Re-assemble in reverse order.
7. Re-fill the boiler.
8. Check the operation of the boiler.
Refer to Sections 2.26 & 2.27.
52
SECTION 3 - SERVICING
5
6
5
4
3
4
IMPORTANT.IT IS CRITICAL FOR SAFE
OPERATION THAT THE CORRECT BOILER SIZE
AND FUEL TYPE IS ENTERED INTO THE BOILER.
3
4
5
Installation and Servicing

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LOGIC MAX HEAT H 18 and is the answer not in the manual?

Questions and answers

David Pegg
February 12, 2025

what is the best working temperature for boiler to be set at

1 comments:
Mr. Anderson
February 12, 2025

The Ideal Boilers LOGIC MAX HEAT H 18 controls central heating radiator temperature up to a maximum of 80°C, adjustable via the central heating temperature knob. The recommended working temperature depends on the heating needs, but it typically ranges between 30°C (minimum) and 80°C (maximum).

This answer is automatically generated

Table of Contents

Save PDF