70 • • • • Chapter Six - Advanced Options
Adding a Register Group
Click this button to add a new register group. The Select Register Group Type
dialog box appears:
Enter the Register Group name. The name may be up to 20 alphanumeric characters
and cannot include embedded spaces or special characters, such as: + * / /, ? () " '.
Select the register type from the Select Register Type pull-down list. The Modbus
Register Types shown are determined by the function codes selected previously. The
four types of register groups that support some of the Modbus function codes are R0,
R1, R3, R4. The table below describes the types, registers, supported codes, and
uses.
Type
Type of Register
Code
R0
Coils
R0
Coils
R0
Coils
R1
Contacts or discrete
inputs
R3
Actual value or input
register
R4
Setpoint or holding
register
R4
Setpoint or holding
register
R4
Setpoint or holding
register
You will need the device's Modbus RTU protocol specification for the correct codes
to add or delete.
Click OK to accept your new register group – the Register Group dialog box is
displayed for you to finish defining the characteristics of the new register group.
Supported
Function Codes
Use
01
Reading coil status
05
Setting/forcing/
executing coils
15
Setting/forcing
multiple coils
02
Reading
contact/discrete
inputs
04
Reading actual value
or input registers
03
Reading setpoint or
holding registers
06
Presetting single
setpoint register
16
Presetting multiple
registers
DDE Server User's Guide