Trouble-Shooting Chart

Error Condition
Many device time-out errors.
Client application times out while
setting up DDE link or receives
negative acknowledgment.
#NAME on Excel spreadsheet (client
application)
#N/A on Excel spreadsheet (client
application)
Printing I/O traffic – output is
compressed and illegible.
Printing I/O traffic –whole I/O traffic
buffer does not print.

Error Messages

DDE Server User's Guide
The following table lists a variety of common problems, possible causes and
recommended solutions.
Possible Cause
Protocol Timer Tick set
too low.
Communication Time-out
value set too low.
Valid Data Time-out set
too low.
Item name is incorrect.
Data is currently
unavailable.
Server is too involved with
processing traffic to print
correctly.
Server printing limitations
were exceeded.
This section provides descriptions of the error messages which may be generated by
the PMCS DDE Server. These messages are logged in the WWLogger.
An additional list of error messages specific to the Ethernet-based host is presented
after the main list.
Activation of <item name> item failed, item not found in register's item list.
Activation of item failed when client requested a link to this item. Please
contact Customer Service. This error message does not appear in normal
circumstances — it appears only if the item list is corrupt or if the toolkit
gives an out-of-sequence ProtActivateItem() call.
Could not find register group with name CPML3710WFCReg, so DDE execute
failed.
This is a device-type configuration problem. Please check that you have the
correct GE32MODB.CFG file.
Could not find register group with name CPML3720WFCReg, so DDE execute
failed.
This is a device-type configuration problem. Please check that you have the
correct GE32MODB.CFG file.
Solution
Increase the PTT from 30 to a higher value (multiples
of 10 only, one step at a time; i.e., 40, 50, 60...).
Check that the Communication Time-out value is set
correctly (default is 2000 milliseconds.)
Increase Valid Data Time-out value. Should be around
5000 milliseconds (5 sec) for most networks.
Check for precise spelling and correct mnemonic.
Make sure device is not deactivated.
Server may be down, suspended, or stopped, or port
may be suspended.
Data request may not yet have been processed.
Suspend Protocol, then print.
Suspend Protocol, then save I/O traffic to a file and
print the file from the Windows Notepad accessory or a
word processor.
Chapter Five - Troubleshooting • • • • 59