Technical Instructions
WARNING
!
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use infor-
mation can result in death, serious personal injury,
property damage, or damage to the equipment.
Keep this Manual for future reference.
WARNING
!
FAILURE TO COMPLY WITH PROPER INSTALLATION AND
MAINTENANCE INSTRUCTIONS COULD CONTRIBUTE TO THE
VALVE FAILURE.
This Hot Water Master Tempering Valves cannot be used for
tempering water temperature at fixtures. Severe bodily injury
(i.e., scalding or chilling) and/or death may result depending
upon system water pressure changes and/or supply water
temperature changes. ASSE standard 1016, 1069 or 1070 listed
devices should be used at fixtures to prevent possible injury.
These Hot Water Tempering Valves are designed to be
installed at or near the boiler or water heater. They are not
designed to compensate for system pressure fluctuations and
should not be used where ASSE standard 1016, 1069 or 1070
devices are required. These valves should never be used to
provide "anti-scald" or "anti-chill" service.
The components of the system must be of materials with a
construction capable of withstanding the high limit output tem-
peratures of the water heating source.
WARNING
!
Need for Periodic Inspection and Yearly Maintenance:
Periodic inspection and yearly maintenance by a licensed con-
tractor is required. Corrosive water conditions and/or unauthor-
ized adjustments or repair could render the valve ineffective for
service intended. Regular checking and cleaning of the valve's
internal components and check stops helps assure maximum
life and proper product function. Frequency of cleaning and
inspection depends upon local water conditions.
!
WARNING
You are required to consult the local building and plumb-
ing codes prior to installation. If the information in this
manual is not consistent with local building or plumbing
codes, the local codes should be followed. Inquire with
governing authorities for additional local requirements.
www.mmcontrol.com/powershome.php
HydroGuard
Description
The HydroGuard
mixing valve designed for use in hot water distribution systems, in
compliance with ASSE 1017.
Specifications
Maximum Operating Pressure ...................... 125 psi (861 kPa)
Maximum Hot Water Temperature ............... 200°F (93°C)
Minimum Hot Water Supply Temp. .............. 5°F (3°C) Above Set-Point*
Hot Water Inlet Temperature Range ............ 120 -180°F (49 - 82°C)
Cold Water Inlet Temperature Range .......... 40 - 80°F (4 - 27°C)
Temp. Adjustment Ranges ** Standard: ....... 90 - 160°F (32 - 71°C)
Listing ........................................ ASSE 1017
Certified .................................... CSA B125
* With Equal Pressure
** Low limit cannot be less than the cold water temperature.
For best operation, hot water should be at least 5°F (3°C) above
desired set point.
800-876-0036
XP Master Tempering Valves
®
Series LFSH1430
Advanced Thermal Actuation
n
XP LFSH1430 series is a temperature actuated
®
n
Low: .................. 60 - 90°F (16 - 32°C)
847-356-0566
IS-P-SH1430

Advertisement

loading
Need help?

Need help?

Do you have a question about the HydroGuard XP Master LFSH1432 and is the answer not in the manual?

Questions and answers

Summary of Contents for Powers HydroGuard XP Master LFSH1432

  • Page 1 Distributed By: M&M Control Service, Inc. www.mmcontrol.com/powershome.php 800-876-0036 847-356-0566 IS-P-SH1430 HydroGuard XP Master Tempering Valves ® Series LFSH1430 Technical Instructions WARNING Read this Manual BEFORE using this equipment. Failure to read and follow all safety and use infor- mation can result in death, serious personal injury, property damage, or damage to the equipment.
  • Page 2 5. When the HydroGuard supplies tempered water to self-closing and/ practices. Flush all piping thoroughly before installation. Installation or solenoid valves, provide a shock absorber (Powers Part No. 460- and field adjustment are the responsibility of the installer. 353) on the discharge line.
  • Page 3 Distributed By: M&M Control Service, Inc. www.mmcontrol.com/powershome.php 800-876-0036 847-356-0566 Parts List - LFSH1432, LFSH1434 Index Description LFSH1432 LFSH1434 Checkstop Rebuild Kit LF390 800 LF390 801 Plunger Kit 390 802 390 803 Adjusting Screw 390 688 390 688 O-Ring 390 805 390 806 Actuator - Standard Temperature 390 807...
  • Page 4 Seller’s equipment unless done by the Seller’s authorized personnel, or by written authority from the Seller. The Seller makes no guarantee with respect to material not manufactured by it. A Watts Water Technologies Company                           IS-P-SH1430 1336 EDP# 6512307 © 2013 Powers...