NorthStar LITE Applications Manual page 12

Advertisement

Secure the battery on the shelf if it is needed and possible.
3
4
NOTE: When batteries are mounted on a shelf no stacking is
allowed.
5
Connect the
cables
according to
item 9-12
above.
6
Start-up
Set circuit
breaker in
the ON
position.
4.4.1 Allowed installation directions of the battery
4.4.2 ADD switch
The ADD switch is used to control the address in the BMS.
It is not recommended to use more than 10 batteries in
parallel.
Circuit breaker
1
2
3
4
Address
0
0
0
0
0
1
0
0
0
1
0
1
0
0
2
1
1
0
0
3
0
0
1
0
4
1
0
1
0
5
0
1
1
0
6
1
1
1
0
7
0
0
0
1
8
1
0
0
1
9
0
1
0
1
10
1
1
0
1
11
0
0
1
1
12
1
0
1
1
13
0
1
1
1
14
1
1
1
1
15
4.5
Led Indicators and Alarms
The Battery Unit is equipped with six (6) LED indicators
positioned on the front panel which indicate the status of
the system, as described by the table below. See section 2.4
Determining State-of-Charge, for introduction to the
capacity indicators.
Normal/Alarm/Protection/
Battery Unit Mode
Failure
Shutdown/Sleep
Normal
Protection
Standby
Alarm
Failure
Normal
Protection
Charge
Alarm
Failure
Normal
Protection
Discharge
Alarm
Failure
Flash mode
ON
Flash 1
0.25 s
Flash 2
0.5 s
Flash 3
0.5 s
4.5.1 Faults
If the battery malfunctions the red ALM light will be flashing,
see above.
 Check that the battery is connected in a correct
manner.
 Press the reset button to see if the problem is solved
 If it is not resolved, contact the manufacturer.
ALM
RUN
Capacity
O
O
O
O
O
OFF
OFF
ALL OFF
OFF
Flash
Flash
Capacity display
2
1
Flash
3
ON
OFF
ALL OFF
OFF
Flash
Flash
Capacity display
2
2
Flash
3
ON
OFF
ALL OFF
OFF
Flash
ON
Capacity display
2
Flash
3
ON
OFF
ALL OFF
OFF
3.75 s
0.5 s
1.5
s
O
12