Configuration
4.11 Access to the Web server
● Enable identifier for processing status
If the option is enabled, every attempt to send returns a status with information about the
processing status of the sent message.
The status is written to the "PLC tag for processing status". If there are problems
delivering messages, you can determine the status via the Web server of the CPU by
displaying the value of the PLC tag there.
For the significance of the status output in hexadecimal, refer to the section Processing
status of e-mails (Page 96).
● PLC tag for processing status
PLC tag of the type DWORD for the processing status
● Include value
If you enable the option, the CP sends a value for the placeholder $$ from the memory
area of the CPU in the message. To do this enter "$$" as a placeholder for the value to
be sent in the message text.
Select a PLC tag whose value will be integrated in the message. The value is entered in
the message text instead of the placeholder $$.
$$ can be a placeholder for data point types with a simple data type up to a size of 32
bits.
● PLC tag for value
PLC tag in which the value to be sent is written.
4.11
Access to the Web server
Access to the Web server of the CPU
The Web server of the S7-1200 station is located in the CPU. Via the CP, you have access
to the Web server of the CPU.
From a PC you can access the Web server of the station via TCSB if the PC is connected to
the telecontrol server via LAN.
For the requirements, refer to the manual /3/ (Page 110).
You will find information on the Web server in the manual /1/ (Page 109).