Installing and connecting the device
3.3 Connecting the IOT2000 Extension Modules
3.3.2
Connecting the power supply for digital output
Note
The device should only be connected to a 9...36 V DC power supply which meets the
requirements of safe extra low voltage (SELV) according to IEC/EN/DIN EN/UL 60950-1.
The power supply must meet the requirement NEC Class 2 or LPS according to IEC/EN/DIN
EN/UL 60950-1.
Note
The power supply must be adapted to the input data of the device, see chapter "IOT2000
Input/Output Module (Page 27)". If there are voltage peaks on power supply lines, use a
protective device in the form of a varistor (MOV) UMOV = U-rated x 1.2 (BLITZDUCTOR
BVT AVD 24 (918 422) or compatible).
Requirement
● A two-core cable with a cable cross-section of 0.75 mm
● A slotted screwdriver with a 3mm blade.
Procedure
1. Switch off the power supply.
2. Connect the lines to the connecting
terminal as shown.
20
to 2.5 mm
.
2
2
IOT2000 Extension Modules
Operating Instructions, 2018/05, A5E39456816-AB