button on the CO
room sensor once, the red LED flashes.
2
Then press the button for 7 seconds until the blue LED on
the CO
room sensor lights up and the status LED flashes
2
alternately red and green. When the CO
been successfully paired, the green LED on the device and
on the CO
room sensor will flash 10 times as confirma-
2
tion, and the device briefly accelerates to the high level.
The CO
room sensor is now ready for use. Pairing an
2
additional CO
room sensor is carried out in the same
2
way as pairing CO
room sensor number 1.
2
Unpairing remote control(s) and CO
on the device
Remove the cover from the device. Press the push button
on the receiver PCB in the device for 15 seconds until the
LED turns orange. Release the push button. After release,
the LED on the receiver PCB flashes alternately red, green,
red. Any connections with the remote control(s) / CO
room sensor(s) are now deleted and the factory settings
are loaded. The LED on the receiver PCB remains green
for 3 minutes, during which time the device is in learning
mode and can be linked to components.
12
room sensor has
2
room sensor(s)
2
2
Reset CO
room sensor
2
A CO
room sensor can be reset to factory settings by
2
pressing the control button for 11 seconds until the LED is
simultaneously red and green (orange). Release the push
button. The CO
room sensor is reset and restarts.
2
6. Service and maintenance
The following parts of the Orcon ventilation system must be
cleaned regularly:
• Housing - at least every 2 years;
• Fan - at least every 2 years;
• Humidity sensor - at least every 2 years;
• Remote control and CO
2
(see maintenance in the user part);
• Valves and grilles - at least every 2 years;
• Ducts - at least every 4 years.
Maintenance of device
The MVS-15RH must be disconnected from the power supply
before maintenance is carried out.
room sensor(s)
Need help?
Do you have a question about the MVS-15RH and is the answer not in the manual?
Questions and answers
datasheets for the MVS-15RH mechanical ventilation system: Noise Level: The unit operates at a noise level of approximately 30 dB(A)
The datasheets for the Orcon MVS-15RH mechanical ventilation system include the following specifications:
- Power Supply: 230 V, 50 Hz
- Max. Power Consumption: 4 W
- Motor Type: Efficient EC motor
- Temperature Class: T40
- Ambient Temperature Range: 0-40 °C
- Humidity Range: 0-90% RH (non-condensing)
- Weight: 4.4 kg
- Dimensions:
- Height: 389 mm (467 mm with connections)
- Width: 449 mm
- Depth: 303 mm
- Protection Class: IP30
- Control Options: Remote control and/or CO2 room sensor
- Communication Frequency: 868.3 MHz (RF)
- Error Indications:
- Flashing red 1x: Motor not running
- Flashing red 2x: No value from humidity sensor
- Flashing red 3x: RF communication failure
- Functional Range of CO2 Sensor: 400 - 2000 ppm
These details provide a technical overview of the Orcon MVS-15RH system.