Communicating with the PLC
6.2 MODBUS communication
Parameter
Function
r2024[0]
USS / MODBUS error statistics
...
r2031[0]
r2018[0...7]
CO: PZD from USS / MODBUS on
RS485
P2019[0...7]
CI: PZD to USS / MODBUS on RS485
Mapping table
The SINAMICS V20 inverter supports two sets of registers (40001 ... 40062, 40100 ...
40522) as the table below shows. "R", "W", "R/W" in the column Access stand for read, write,
read/write.
Register No.
Inverter
MODBUS
0
40001
1
40002
2
40003
3
40004
4
40005
5
40006
6
40007
7
40008
8
40009
9
40010
10
40011
11
40012
12
40013
13
40014
14
40015
15
40016
16
40017
17
40018
18
40019
19
40020
20
40021
21
40022
22
40023
23
40024
24
40025
25
40026
26
40027
27
40028
28
40029
29
40030
112
Description
Acce
ss
WDOG TIME
R/W
WDOG ACTION
R/W
FREQ REF
R/W
RUN ENABLE
R/W
CMD FWD REV
R/W
CMD START
R/W
FAULT ACK
R/W
PID SETP REF
R/W
ENABLE PID
R/W
CURRENT LMT
R/W
ACCEL TIME
R/W
DECEL TIME
R/W
(Reserved)
DIGITAL OUT 1
R/W
DIGITAL OUT 2
R/W
REF FREQ
R/W
PID UP LMT
R/W
PID LO LMT
R/W
P GAIN
R/W
I GAIN
R/W
D GAIN
R/W
FEEDBK GAIN
R/W
LOW PASS
R/W
FREQ OUTPUT
R
SPEED
R
CURRENT
R
TORQUE
R
ACTUAL PWR
R
TOTAL KWH
R
DC BUS VOLTS
R
Setting
The state of the telegram information on RS485 is reported
regardless of the protocol set in P2023.
Displays process data received via USS / MODBUS on
RS485.
Displays process data transmitted via USS / MODBUS on
RS485.
Unit
Scaling
Range or On/Off
factor
text
ms
1
0 - 65535
-
1
-
%
100
0.00 - 100.00
-
1
0 - 1
-
1
0 - 1
-
1
0 - 1
-
1
0 - 1
%
100
-200.0 - 200.0
-
1
0 - 1
%
10
10.0 - 400.0
s
100
0.00 - 650.0
s
100
0.00 - 650.0
-
1
HIGH
-
1
HIGH
Hz
100
1.00 - 599.00
%
100
-200.0 - 200.0
%
100
-200.0 - 200.0
-
1000
0.000 - 65.000
s
1
0 - 60
-
1
0 - 60
%
100
0.00 - 500.00
-
100
0.00 - 60.00
Hz
100
-327.68 - 327.67
RPM 1
-16250 - 16250
A
100
0 - 163.83
Nm
100
-325.00 - 325.00
kW
100
0 - 327.67
kWh
1
0 - 32767
V
1
0 - 32767
Read
-
-
HSW
STW:3
STW:11
STW:0
STW:7
P2240
r0055.8
P0640
P1120
P1121
LOW
r0747.0
LOW
r0747.1
P2000
P2291
P2292
P2280
P2285
P2274
P2269
P2265
r0024
r0022
r0027
r0031
r0032
r0039
r0026
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
Write
-
-
HSW
STW:3
STW:11
STW:0
STW:7
P2240
(BICO) P2200
P0640
P1120
P1121
(BICO) P0731
(BICO) P0732
P2000
P2291
P2292
P2280
P2285
P2274
P2269
P2265
r0024
r0022
r0027
r0031
r0032
r0039
r0026