Chapter 4
SSR Series Modules
SSR-IAC-5, 120 VAC
The SSR-IAC-5 input module senses 90–140 VAC/DC from a field source
and converts it into a TTL logic signal. When a signal in this voltage range
is detected at its input, the SSR generates a logic low signal on the
corresponding DIO line of the E Series DAQ device. Otherwise, the SSR
returns a logic high signal. Figure 4-1 shows the SSR-IAC circuit diagram.
You can insert and use the SSR-IAC-5 in any of the eight SSR sockets
inside the SC-2311.
SSR-IAC-5A, 240 VAC
The SSR-IAC-5A input module senses 180–280 VAC/DC from a field
source and converts it into a TTL logic signal. When a signal in this voltage
range is detected at its input, the SSR generates a logic low signal on the
corresponding DIO line of the E Series DAQ device. Otherwise, the SSR
returns a logic high signal. Figure 4-1 shows the SSR-IAC circuit diagram.
You can insert and use the SSR-IAC-5A in any of the eight SSR sockets
inside the SC-2311.
SC-2311 User Manual
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Rx
1
VAC
2
+V cc
Input
Voltage
3
Hysterisis Circuit
Current
Regulating
Output
4
Ground
5
Figure 4-1. SSR-IAC AC Input Diagram
4-2
ni.com