r0631[0...2]
CO: Stator iron temperature / Stat.iron temp
Access level: 4
Unit: [°C]
Description:
Displays iron temperature of motor mass model.
r0632[0...2]
CO: Stator winding temperature / Stat.wind.temp
Access level: 4
Unit: [°C]
Description:
Displays stator winding temperature of motor mass model.
r0633[0...2]
CO: Rotor winding temperature / Rot. wind.temp
Access level: 4
Unit: [°C]
Description:
Displays rotor winding temperature of motor mass model.
p0640[0...2]
Motor overload factor [%] / Motor ovl fact [%]
Access level: 2
Quick comm. YES
Can be changed: C, U, T
Min
10.0 [%]
Description:
Defines motor overload current limit in [%] relative to P0305 (rated motor current).
Dependency:
Limited to maximum inverter current or to 400 % of rated motor current (P0305), whichever is the lower.
p0640
Note:
Changes to P640 will be effective only after the next off state.
See function diagram for current limitation.
p0700[0...2]
Selection of command source / Command source sel
CU240E
Access level: 1
CU240S
Quick comm. YES
Can be changed: C, T
Min
0
Description:
Selects digital command source.
Values:
0:
1:
2:
4:
5:
Dependency:
Changing this parameter sets (to default) all settings on item selected. These are the following parameters:
P0701, ... (function of DI), P0731, P0732, P0733, P0800, P0801, P0840, P0842, P0844, P0845, P0848, P0849,
P0852, P1020, P1021, P1022, P1023, P1035, P1036, P1055, P1056, P1074, P1110, P1113, P1124, P1140,
P1141, P1142, P1230, P1477, P1501, P2103, P2104, P2106, P2200, P2220, P2221, P2222, P2223, P2226,
P2228, P2235, P2236
Caution:
Be aware, by changing of parameter P0700 all BI parameters are reset to the default value.
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
⋅
min
(r0209,
4
p0305)
=
max
p0305
Factory default setting
BOP (keypad)
Terminal
USS on RS232
USS on RS485
P-Group: Motor
P-Group: Motor
P-Group: Motor
P-Group: Motor
Active: YES
Max
400.0 [%]
⋅
100
P-Group: Commands
Active: NO
Max
5
Parameters
List of Parameters
Data type: Floating Point
Data set: DDS
Data type: Floating Point
Data set: DDS
Data type: Floating Point
Data set: DDS
Data type: Floating Point
Data set: DDS
Factory setting
200.0 [%]
Data type: Unsigned16
Data set: CDS
Factory setting
2
1-63