When a warning message is shown on LCD display, the inverter will continue working but will be accompanied by flash red LED indicator. You may be advised to contact Growatt in some situation, please provide the following information.
Page 4
Display On LCD Record Code Detailed content Warning e.g. LCD Shows “Warning 100” Malfunction with the fan Fail to read EEPROM Firmware version unmatched Fail to write EEPROM Error (Inverter Fault) e.g. LCD shows “Error 101” Communication error, COM board(Slave CPU) doesn't receive from...
Note: a. Growatt 10-20kUE three-phase inverter has two types of fan structures. b. Growatt 10kUE, 12kUE has two fans while 18KUE, 20KUE has three fans on the top of inverter. Fan type 1 cleaning procedure: The left and top of shell plane is as entirety seamlessly.
Page 6
Fig.2.1.2 UE series inverter Fig.2.1.3 A View Fig.2.1.4 B View 3) Remove the handles on both sides of UE inverter as Fig.2.1.4 show. 4) Remove the shell plane of the bottom and right side. Use appropriate screwdrivers counterclockwise rotate the screws marked in Fig.2.1.5. Fig.2.1.5 5) Unlock and remove the plug connectors of cooling fans.
Page 7
Fig.2.1.6 6) Remove the shell plane of the top and left side, as Fig.2.1.6 1 2 4 5 show. It’s easy to clean the grills on shell plane using water or some tools. 7) Clean the grills on shell planes. 8) Remove and clean the cooling fans.
Page 8
female terminals). Disconnect the AC terminal. 2) Remove the inverter from mounting bracket, and place inverter horizontally on clean and dry place. 3) Screw off the screws to open the fans cover with suitable tool, then fans will be seen, as Fig.2.1.8.
Fan replacement is required if it fails to work. The procedure is similar to fan cleaning procedure; the difference is that broken fan should be exchanging before assembling the inverter in reverse order. Please contact Growatt service to get new one if there are some broken fans in inverter. Warning 103 Fail to read EEPROM.
Page 10
2. Please read the internal firmware version and model value by knock or via ShineBus, and register them as well. Model value External firmware version Fig.2.3.2 Property interface Fig.2.3.3 Internal FW Ver. on LCD Model value Firmware version Fig.2.3.4 State information on ShineBus 3. Provide above information to Growatt service. - 8 -...
1. Restart the inverter, check if the error still exists. 2. If the error still exists, please refer Annex 2 to replace control board and COM board. 3. If the error still exists, please contact Growatt service to replace an inverter. Error 117...
PV Isolation Low PV input insulation impedance is too low. 1. Please confirm whether the output of inverter is connected according to user manual. 2. Please provide the model value shown as Fig.2.3.2 or Fig.2.3.3 to Growatt service. - 10 -...
Page 13
7. Disconnect PV terminals and measure the impedance between PV1+ and Earth, PV2+ and Earth, PV- and Earth by multi-meter; check whether all the impedances are beyond 1 Mega ohm, if not, please contact Growatt service. Note: Inverter shell is also grounded.
Earth PV1-/PV2- PV2+ PV1+ Fig.4.1.4 DC side in the inverter PV Voltage High PV voltage is over 1000V. 1. Turn off AC breaker, measure the string voltage between PV+ to PV- by multi-meter according to the mark on DC terminal shown as Fig.4.2.1 and check whether it is within DC voltage range. If it is higher than the Max allowed DC voltage 1000V, you need to reduce the quantity of PV modules.
2. If the error always appears, please update the firmware of control board to version 0D36 or above, and COM board to version 0C29 or above. 3. If the error still exits after updating, please contact Growatt service to replace an inverter. - 13 -...
AC wiring condition (including length and diameter of cables etc.) and record whether assemble an isolated transformer on the output, and then contact Growatt service. Meanwhile you can check as following steps: Note: In this document, L1, L2, L3 means three phase live wire and N means neutral wire.
Page 17
Live wires Neutral Inside AC terminal Fig.4.5.2 Live wires Neutral Inside AC terminal Fig.4.5.3 6) Assemble the inverter in reverse order. 4. Turn on AC breaker, measure the real grid voltage (L1, L2, L3 to N) by multi-meter. 5. Check whether the grid voltage is complied with the local grid standards; check whether the grid voltage is stable with multi-meter.
Page 18
Fig.4.5.4 If the AC terminal belongs to type 3 as Fig.4.3.1 show, please remove the shell of AC terminal by screwdriver and measure the corresponding phase voltage (R, S, T 3 phase) outside inverter as Fig.4.5.5. Fig.4.5.5 6. Turn on DC switch; compare the measured grid voltage with the AC voltage displayed on LCD. If the tolerance is more than 3V, please calibrate AC voltage of the inverter as following steps: R/S/T Fig.4.5.6 Output information interface...
Page 19
Fig.4.5.7 Item List Parameter Input Value e.g. 10.V AC R R phase AC voltage 230.0 14.V AC S S phase AC voltage 230.0 18.V AC T T phase AC voltage 230.0 Table 4.5.1 Select “14.V AC S” or “18.V AC T” in Item List dropdown list and repeat above processes to finish S phase or T phase AC voltage calibration.
115.0 310.0 Table 4.5.1 9. If all conditions are OK and this fault still exists, please contact Growatt service. AC F Outrange Grid frequency is out of range; Or the inverter’s frequency limits is incorrect. If there are several inverters in parallel, and the inverter shows “AC V Outrange” after the inverter feed to grid working for a while, perhaps the grid impedance is too high, please record the AC wiring condition (including length and diameter of cables etc.) and record...
Page 21
Fig.4.6.1 Power information interface 2. Check the grid frequency limits by ShineBus as following steps: 1) Select layout “4 Parameter”, select option “Read” as following figure. Fig.4.6.2 2) Select 15, 16, 19 and 20 option in “Set ID” drop-down list. And click button “Operate” to read the frequency limits one by one.
4. If all conditions are OK and this fault still exists, please contact Growatt service. ANNEX 1. How to connect AC terminal (Disconnect in reverse order) Note: There are three types of AC connector for Growatt UE series inverters. Please follow the instructions corresponding to the parts we offer you. A. AC connector 1: Assembly procedure: 1) Connect the cables into their respective channels shown as Fig.5.1.1, ‘1’...
Page 23
Fig.5.1.3 B. AC connector 2: Assembly procedure: Unscrew the AC connector by hand and slotted screwdriver into four components as Fig.5.1.4: Fig.5.1.4 Connect 5 cables into their respective channels on the AC terminal shown as Fig.5.1.5, for the mark beside every socket, ‘N’ represents Neutral, ‘1, 2, 3’ represent 3 live channels and ‘E’ is ground, tighten all screws (1.0Nm (9 lbf.
Page 24
Fig.5.1.7 Fig.5.1.8 Connect it to the inverter as Fig.5.1.8. C. AC connector 3: Assembly procedure: 1) The AC side terminals of the inverter are like Fig.5.1.9, it is clear to confirm that ‘L1, L2, L3’ represents three live line output, ‘N’ represents neutral line and is grounding line.
Fig.5.1.11 2. How to replace control board and COM board Replacing procedure: 1) Before replacement, please register some important information such as total energy E_all the inverter has already generated to grid. Fig.5.2.1 E_all information on LCD 2) Disconnect DC breaker and AC breaker to power off the inverter. 3) Remove the cover of RS232 interface with a cross screwdriver.
Page 26
Fig.5.2.3 Two nuts on RS232 port 5) Remove the front cover, and disconnect the connectors shown as Fig.5.2.4. Note: If here has a Connectors white connector, disconnect it too. Fig.5.2.4 Connectors on control board and COM board 6) Unscrew the eight screws connecting the control board and COM board with the metal panel. - 24 -...
Page 27
The inverter’s model name is made up of PFU1MxSx four sections, the last two sections should be preset in accordance with the power level and country or grid standards. The meaning of Mx and Sx are shown in Table 5.2.1-5.2.2. Product Growatt 10000UE Growatt 12000UE Growatt 18000UE - 25 -...
Page 28
Growatt 20000UE Table 5.2.1 Mx stands for the power level of the inverter Country/Grid Standard VDE0126 (Netherlands) Barbados Australia (AS4777) Italy (CEI 0-21) Spain (RD1663) Greece Germany (N4105) UK_G59 Ireland EN50438(Denmark, Cyprus) Thailand Hungary Belgium BDEW Table 5.2.2 Sx stands for the adopted standards or countries ...
Page 29
Fig.5.2.8 S/N is serial number Fig.5.2.9 Item Meaning Note Registered total energy Value e.g.20000.0 “E_all” Password Setting password Correction Set State Set process OK is successful for setting COM port address in PC Found in Device Manager “Auto Inv Add” can be Inv Add Internal address of inverter selected if only one inverter...
CONTACT INFORMATION If you have any questions about our product, our hotline will be happy to assisit you, please contact Growatt service with information below. Company GROWATT NEW ENERGY TECHNOLOGY CO.,LTD Website www.growatt.com Email service@ginverter.com Building A, Jiayu Industrial Zone, #28 Guangming Road, Address Longteng Community, Shiyan, Baoan District, Shenzhen, P.R.