  • Page 1 Installation & Operation Manual...
  • Page 2 Index 1 Notes on this manual 1.1 Validity 1.2 Applicable personnel 1.3 Symbols in this document 2 Safety 2.1 Product description and features 2.2 Qualification of skilled person 2.3 Safety instruction 3 Product overview 3.1 Appearance overview 3.2 Dimensions 3.3 Storage environment 4 Unpacking inspection 5.1 Basic installation requirements 5 Installation...
  • Page 3 7 Debugging 8 Working mode 8.1 Normal mode 8.2 Failure mode 8.3 Shutdown mode 9 OLED display and touch 9.1 Boot display buttons 9.2 OLED display wake up 9.3 Function setting 10 Communication and 10.1 COM port monitoring 10.2 USB-A 11 Maintenance and Cleaning 11.1 Checking heat dissipation 11.2 Cleaning the inverter...
  • Page 4 13 Troubleshooting 13.1 Error message 13.2 Syetem error 14 Manufacturer warranty 15 Decommissioning 15.1 Dismantling the inverter 15.2 Packing the inverter 15.3 Storing the inverter 15.4 Disposing of the inverter 16 EU declaration of conformity 17 Specification 17.1 Specification 17.2 Torque 17.3 Annex 18 EU declaration of conformity 19 Contect us...
  • Page 5 If the procedure or practice is not properly implemented or followed, it may cause damage or destruction of part or all of the Growatt device and/or other equipment connected to the Growatt device, or cause personal injury.
  • Page 6 NOTICE is used to address practices not related to personal injury. NOTICE Information that you must read and know to ensure optimal operation of the system. Information 1.3.2 Markings on this product Symbol Explanation Danger: Electricity! Danger:Flame! Danger:Hot surface! Operation after 5 minutes Point of connection for grounding protection Direct Current (DC) Alternating Current (AC)
  • Page 7 1.3.3 Glossary Abbreviation for "Alternating Current” Abbreviation for "Direct Current” Energy Energy is measured in Wh (watt hours), kWh (kilowatt hours) or MWh (megawatt hours). The energy is the power calculated over time. For example, your inverter operates at a constant power of 4600 W for half an hour and then at a constant power of 2300 W for another half an hour, it has fed 3450Wh of energy into the power distribution grid within that hour.
  • Page 8 Growatt MOD 3-10K TL3-XH series inverter can be connected to 2 strings , has 2 maximum power tracking point trackers, so suitable for connection 2 set of arrays of different panels.
  • Page 9 Simple installation Ø Integrated with energy storage and backup functions Ø Integrated with phase-level export limitation function Ø Integrated with AC power supply function Ø Integrated with energy storage one-key detection function Ø Integrated with AC power supply function to realize the 24h self-consumption Ø...
  • Page 10 The inverter need to take 20 minutes to discharge for safety. Persons with limited physical or mental abilities may only work Ø with the Growatt inverter following proper instruction and under constant supervision. Must keep the Growatt inverter away from children.
  • Page 11 2.3.3 Operation Warnings Ensure all connectors are sealed and secure during operation. Ø Although designed to meet all safety requirements, some parts Ø and surfaces of inverter are still hot during operation. To reduce the risk of injury, do not touch the heat sink at the back of the PV- inverter or nearby surfaces while inverter is operating.
  • Page 12 Product overview 3 3.1 Appearance overview B C D Fig 3.1 The appearance instructions are as follows: Name Name Name Front panel DC switch USB port Touch button PV terminal Vent valve OLED screen Battery terminal AC terminal LED indicator COM port The label description on the inverter: Symbol...
  • Page 13 3.2 Dimensions Fig 3.2 Size and weight: Model Height (H) Width (W) Depth (D) Weight MOD 3-6KTL3-XH 387mm 425mm 147mm 13kg MOD 7-10KTL3-XH 387mm 425mm 178mm 14kg 3.3 Storage Environment If you want to store the inverter in a warehouse, you must choose a suitable location for the inverter.
  • Page 14 Unpacking inspection 4 Before opening the inverter package,please check whether the outer package is damaged.After unpacking,please check whether the appearance of the inverter is damaged or lack of accessories.If there is damage or missing parts,please contact the dealer. Fig 4.1 Description Qty.
  • Page 15 5 Installation 5.1 Basic installation requirements The wall on which the inverter is mounted must be sturdy and can withstand the Ø weight of the inverter for a long time (refer to the specifications in Chapter 17 for the weight of the inverter); The installation location must match the size of the inverter;...
  • Page 16 ≥500mm ≥300mm ≥300mm ≥500mm Fig 5.2 Installation dimensions for one inverter Min.30cm Min.30cm Min.30cm Min.30cm Min.30cm Min.30cm Min.30cm Min.30cm Min.30cm Fig 5.3 Installation dimensions for multiple inverters Ø Do not install the inverter on the TV antenna, other antennas or antenna cables; Ø...
  • Page 17 Fig 5.4 Installation Environment Ø Make sure that the inverter is installed in a suitable place and is not allowed to be installed in a closed box; Fig 5.5 Closed box Ø In order to reduce the inverter load and extend the life of the inverter due to direct sunlight, we recommend installing a awning.
  • Page 18 5.2 Install the wall mount 5.2.1 Install the wall mount To prevent electric shock or other damage, be sure to check the wall for power or other piping before opening the hole in the wall. DANGER Fig 5.7 Specifications of wall mount Secure the wall mount as shown, do not let the screws flush with the wall, instead expose 2 to 4 mm.
  • Page 19 Fig 5.9 Schematic diagram of inverter wall mounting...
  • Page 20 Inverter wiring 6 6.1 Security There may be a high voltage in the conductive part of the inverter, which may cause electric shock.Therefore, when installing the inverter,make sure that the AC and DC sides of the inverter are powered off. DANGER Static electricity may damage the electronic components of the inverter.Anti-static measures should be taken during the...
  • Page 21 Inverter model Switch specification MOD 3000TL3-XH 10A(230/400V) MOD 4000TL3-XH 10A(230/400V) MOD 5000TL3-XH 15A(230/400V) MOD 6000TL3-XH 15A(230/400V) MOD 7000TL3-XH 15A(230/400V) MOD 8000TL3-XH 20A(230/400V) MOD 9000TL3-XH 20A(230/400V) MOD 10KTL3-XH/XH BE 20A(230/400V) Residual current protection device (RCMU) Because the inverter itself has a high-precision residual current detection device,it is not recommended to install a leakage protection switch in the system.If for some special reason, it must be installed between the inverter output and the grid.Please install a type A leakage protection switch no less than 300mA.When multiple leakage protection...
  • Page 22 2. Lock the AC cable to the corresponding AC terminal. TheInverterSide TheInverterSide Fig 6.3 Wiring diagram of AC terminal 3. Lock the protective cover on the inverter frame, and finally tighten the protective cover hole. Fig 6.4 AC quick connection diagram Suggested line length: Model Wire ross-sectional area(Cu)
  • Page 23 Please ensure that the following conditions are met, otherwise it may cause a fire hazard or damage the inverter. In this case, the company does not carry out quality assurance and assumes any responsibility. The maximum open circuit voltage of each string of photovoltaic Ø...
  • Page 24 Before connecting the PV panel, please make sure that the DC input Ø polarity is correct, that is, the positive pole of the photovoltaic module is connected to the DC input terminal marked "+" of the inverter, and the negative pole is connected to the DC input terminal marked "-". The maximum DC input current and voltage of the inverter shall not Ø...
  • Page 25 6.4.2 Connecting the Bidirectional DC/DC Box Danger to life due to lethal voltages! Before connecting the Bidirectional DC/DC Box, ensure that the Box do not connect any power supply. NEVER connect or disconnect the BAT connectors under load. Forbidden to reverse the positive and negative poles of the DANGER Bidirectional DC/DC Box and the inverter.
  • Page 26 3.Connect the client to the inverter plug until both are tightly locked on the inverter. Click! Click! Fig 6.11 Remove the signal connector 1.Press down the fastener and pull it out of the inverter. The Inverer Side Fig 6.12 6.6 Grounding the inverter The inverter must be connected to the AC grounding conductor of the power distribution grid via the ground terminal (PE) .
  • Page 27 The wiring of meter, please refer to the manual of smart meter in Ø Information details. This series inverter has integrated export limitation functionality. To use this function, you can connect the Growatt smart meter. For the detailed information, please contact with Growatt. LOAD RS485 Fig 6.14...
  • Page 28 Base Current (Ib) Power consumption ≤2W Frequency 50/ 60Hz(±10%) AC voltage withstand 4KV for 1 minute Impulse voltage withstand 6KV-1.2uS waveform Overcurrent withstand 20Imax for 0.5s Pulse output 1 1000imp/kWh (default) Pulse output 2 400imp/kWh Display Max. Reading LCD with white backlit 999999kWh Environment Operating temperature -25℃to +55℃...
  • Page 29 6.8 Inverter demand response modes (DRMS) This series inverter has the function of demand response modes, We use 16-Pin socket as inverter DRMS connection. DRMS application description Applicable to AS/NZS4777.2:2015 or Commission Regulation Ø (EU) 2016/631. Information DRM0, DRM5, DRM6, DRM7, DRM8 are available. Ø...
  • Page 30 6.8.3 Using the Power Control Interface for EU Fig 6.16 Inverter – RRCR Connection 6.8.3.1 The following table describes the connector pin assignment and function: DRM Socket Pin NO. Description Connect to RRCR Relay contact 1 input K1 – Relay 1 output Relay contact 2 input K2 –...
  • Page 31 6.9 GFCI(Standard) 6.9.1 Ground Fault Circuit Interrupt(GFCI) This inverter includes an integrated residual current device .If the leakage current is over 300mA and last for more than 300ms,the inverter will report 201 fault and the OLED will display Residual I High. The inverter has the function of detecting residual current and protecting the inverter against residual current.
  • Page 32 Backup Mode Setting. Note: 1.The max. power output at the off grid is 10kW when the battery power is enough. 2.The backup function is permitted to be commissioned only by professionals. The backup function requires a backup box provided by Growatt.
  • Page 33 7 Debugging 1.Turn on the DC switch on the inverter.As long as the input DC voltage is greater than 140V,the inverter display will show the following information:No AC connection error,the inverter LED will turn red. If other information is displayed,please refer to Chapter 13.If you encounter any problems during the debugging process and cannot solve it,please contact customer service.
  • Page 34 Touch mark Return to the previous display Triple touch interface The current data returns to the Long press for 5s default value 9.1.2 Set Country/Area Information Press Growatt Country/Area Set OK PV Inverter VDE0126 Single touch Country/Area Press Germany Multiple single...
  • Page 35 9.2 General setting 9.2.1 Set inverter display language Double Language Language Double touch touch Set OK English English Single touch Double touch Language Double touch General German Advanced Single touch Double touch Language Double touch Spanish Set Parameter Multiple single touch Language Double touch...
  • Page 36 9.2.4 Set inverter time Double touch Double touch Double touch Double touch Time Setting Time Setting Time Setting Time Setting Set OK 20:05:00 NN:NN:00 NN:05:00 20:05:00 Single Single Single Single touch Double touch touch touch touch Time Setting Time Setting Time Setting Date Setting 21:05:00...
  • Page 37 9.3.1Export limitation setting The -XH series inverters can work in anti-backflow mode through external power meter or CT,the user can set the percentage of power allowed to flow backward through the OLED, Single touch to switch display or make the number +1.Double touch to confirm the setting, as described below: Double touch Double touch...
  • Page 38 Double touch Double touch General Reset Factory Set OK Advanced Double touch Multiple single Double touch Single touch touch Double touch Password Country/Aera VDE0126 Double touch 9.3.3 Backup mode setting (Off-grid models only) Double touch Double touch Backup Box Backup Box Set OK Disable Disable...
  • Page 39 9.3.4 Grid Charge setting General Double touch Disable Double touch Grid Charge Set OK Advanced Enable Double touch Single touch Double touch Disable Double touch Password Strorage Setting Set OK Enable Double touch Multiple single touch Country/Area VDE0126 9.3.5 Power derating for voltage variation (Volt-Watt mode) The inverter power output will vary in response to the AC grid voltage.
  • Page 40 Communication and Monitoring 10 10.1 COM port This series of inverters provide four RS485 ports. You can monitor one or more inverters via RS485. The other RS485 port is used to connect a smart meter (Export limitation and self-consumption monitoring). Description Function Dry contact: the power of any...
  • Page 41 11 Maintenance and Cleaning 11.1 Checking Heat Dissipation If the inverter regularly reduces its output power due to high temperature, please improve the heat dissipation condition. Maybe you need to clean the heat sink. 11.2 Cleaning the Inverter If the inverter is dirty, turn-off the AC breaker and DC switch ,waiting the inverter shut down ,then clean the enclosure lid, the display, and the LEDs using only a wet cloth.
  • Page 42 When a malfunction occurs, an error message will be displayed on the OLED screen and the LED indicator red will light up. Faults include system faults and inverter faults. In some cases, you may be advised to contact Growatt, please provide the following information.
  • Page 43 Warning Description Suggest message 1.Unplug the U disk. U disk over-current 2.Re-access U disk after shutdown. Warning 207 protection 3.If the error message still exists, contact manufacturer. 1.After shutdown,Check fuse. Warning 208 DC Fuse Open 2.If error message still exists, contact manufacturer.
  • Page 44 Warning Description Suggest message 1.Check if the meter is on. Warning 401 Meter abnormal 2.Check the machine and the meter connection is normal. Optimizer and inverter 1.Check if the optimizer is on. Warning 402 communication is 2.Check whether the connection between the abnormal optimizer and the inverter is normal.
  • Page 45 Warning Description Suggest message 1.Check the environment temperature of battery is Battery temperature Warning 506 in the range of specification or not. outrange 2.If error message still exists,contact manufacturer. BMS failure and 1.Depend on BMS error code. Warning 507 neither charge and 2.If error message still exists,contact manufacturer.
  • Page 46 Warning Description Suggest message Off-grid box 1.Restart inverter. Warning 608 abnormal alarm 2.If error message still exists,contact manufacturer. The off-grid box fan 1.Check the fan wiring after powering it down. Warning 700 is faulty 2.If error message still exists,contact manufacturer. The generator 1.Check the generator and wiring after shutdown.
  • Page 47 Error code Description Suggest 1.After shutdown,Check the SP-CT connection. Error 306 CT LN Reversed 2.If error message still exists,contact manufacturer. Communication 1.Check communication wire. Error 307 fault,M3 didn't 2.If error message still exists,contact manufacturer. receive SP-CT data Communication 1.Restart pairing. Error 308 fault;Pairing time 2.If error message still exists,contact manufacturer.
  • Page 48 Error code Description Suggest 1.Restart inverter. Error 413 IGBT drive fault 2.If error message still exists,contact manufacturer. 1.Restart inverter. Error 414 EEPROM fault 2.If error message still exists, contact manufacturer. Internal power 1.Restart inverter. Error 415 test fail(PV Power 2.If error message still exists,contact manufacturer. low) Over current 1.Restart inverter.
  • Page 49 Error code Description Suggest Battery terminals 1.Check battery terminals. Error 505 reversed 2.If error message still exists,contact manufacturer. Battery terminal 1.Check battery terminal. Error 506 open (only for 2.If error message still exists,contact manufacturer. lithium battery) 1.Check whether output load over Lithium battery rate Lithium battery Error 507 power;...
  • Page 50 Error code Description Suggest Off-grid box grid- 1.Restart the off-grid box. Error 701 side relay failure 2.If error message still exists,contact manufacturer. Off-grid box 1.Restart the off-grid box. Error 702 generator access 2.If error message still exists,contact manufacturer. relay fault Off-grid boxes are 1.Restart the off-grid box.
  • Page 51 14 Manufacturer warranty Please refer to the warranty card. 15 Decommissioning 15.1 Dismantling the Inverter 1. Disconnect the inverter as described in section8. 2. Remove all connection cables from the inverter. Danger of burn injuries due to hot enclosure parts! Wait 20 minutes before disassembling until the housing has cooled down.
  • Page 52 • 2014/30/EU Electromagnetic Compatibility Directive (EMC) • 2011/65/EU RoHS Directive and its amendment (EU)2015/863 Shenzhen Growatt New Energy Co. Ltd confirms that the Growatt inverters and accessories described in this document are in compliance with the above mentioned EU directives. The entire EU Declaration of Conformity can be found at www.ginverter.com...
  • Page 53 17 Specification 17.1 Parameter Model 3000TL3-XH 4000TL3-XH 5000TL3-XH 6000TL3-XH Specifications Input data(DC) Max. recommended PV 6000W 8000W 10000W 12000W power(for module STC) Max. DC voltage 1100V Start voltage 160V Nominal voltage 600V MPP voltage range 140-1000V No. of MPP trackers No.
  • Page 54 Model 3000TL3-XH 4000TL3-XH 5000TL3-XH 6000TL3-XH Specifications THDi <3% AC grid connection type 3W+N+PE Efficiency Max. efficiency 98.30% Euro-eta 97.50% Output data(Backup) Nominal output power Max. apparent power 3kVA 4kVA 5kVA 6kVA Nominal AC output 230V/400V voltage Nominal AC output 50Hz frequency Max.
  • Page 55 Model 3000TL3-XH 4000TL3-XH 5000TL3-XH 6000TL3-XH Specifications General data Dimensions (W / H / D) in 425*387*147mm Weight 13kg Operating temperature -25°C ... +60°C range (>45°CDerating) Noise emission (typical) ≤29dB(A) Altitude 3000m Internal consumption at <5.5W night Topology Transformerless Cooling Natural heat dissipation Electronics protection IP66 degree...
  • Page 56 Model Specifications 7000TL3-XH 8000TL3-XH 9000TL3-XH 10KTL3-XH 10KTL3-XH BE Input data(DC) Max. recommended PV 14000W 16000W 18000W 20000W 20000W power(for module STC) Max. DC voltage 1100V Start voltage 160V Nominal voltage 600V MPP voltage range 140-1000V No. of MPP trackers No. of PV strings per MPP trackers Max.
  • Page 57 Model 10KTL3-XH BE 7000TL3-XH 8000TL3-XH 9000TL3-XH 10KTL3-XH Specifications Power factor >0.99 (@nominal power) THDi <3% AC grid connection 3W+N+PE type Efficiency Max. efficiency 98.60% Euro-eta 98.10% Output data(Backup) Nominal output power 10kW 10kW Max. apparent power 7kVA 8kVA 9kVA 10kVA 10kVA Nominal AC output 230V/400V...
  • Page 58 Model 10KTL3-XH BE Specifications 7000TL3-XH 8000TL3-XH 9000TL3-XH 10KTL3-XH AFCI protection General data Dimensions (W / H / D) 425*387*178mm in mm Weight 14kg Operating temperature -25°C ... +60°C range (>45°CDerating) Noise emission ≤29dB(A) (typical) Altitude 3000m Internal consumption <5.5W at night Topology Transformerless Cooling...
  • Page 59 MOD 7-10KTL3-XH C10/11, IEC 62116/61727, IEC 60068/61683 19 Contect us If you have technical questions about our products, please contact the Growatt New Energy Service Hotline. We need the following information to provide you with the necessary help: Inverter type Ø...
  • Page 60 Growatt New Energy Download Manual Shenzhen Growatt New Energy Co., Ltd 4-13/F, Building A, Sino-German(Europe) Industrial Park, Hangcheng Ave, Bao’an District, Shenzhen, China +86 755 2747 1942 service@ginverter.com www.ginverter.com GR-UM-246-A-03...