Table of Contents

Advertisement

TSA 160 NT
EN Wiring diagram
Valid for variants:
TSA 160 NT F
TSA 160NT F-IS
TSA 160NT Invers
TSA 160 NT Z
TSA 160 NT Z-Invers
135239-03

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TSA 160 NT Series and is the answer not in the manual?

Questions and answers

Summary of Contents for GEZE TSA 160 NT Series

  • Page 1 TSA 160 NT EN Wiring diagram Valid for variants: TSA 160 NT F TSA 160NT F-IS TSA 160NT Invers TSA 160 NT Z TSA 160 NT Z-Invers 135239-03...
  • Page 2: Table Of Contents

    TSA 160 NT Contents Symbols and illustrations ..............................4 Validity .....................................4 Product liability ..................................4 Notes ....................................5 Important safety instructions ..................................5 Installation information....................................5 Safety-conscious working .....................................5 Inspection of installed system ..................................6 Commissioning and service..................................6 Disposal of the door system ..................................6 Abbreviations ................................6 Electrical data ................................7 Control ..................................8 Safety sensor open and close ..........................9...
  • Page 3 TSA 160 NT Electric strike ................................28 12.1 24V DC electric strike supplied on drive side ............................28 12.2 Customer-supplied 12 V AC electric strike ............................29 12.3 Bar message ........................................29 Mode of operation ............................... 30 13.1 Internal programme switch ..................................30 13.2 Mechanical programme switch (MPS, external programme switch) ..................
  • Page 4: Symbols And Illustrations

    TSA 160 NT Symbols and illustrations Warning notices Warning notices are used in these instructions to warn you of property damage and personal injury. Always read and observe these warning notices. Observe all the measures that are marked with the warning symbol and warning word. Warning symbol Warning word Meaning Danger for individuals.
  • Page 5: Notes

    Keep these instructions. à Only specialists who are authorised by GEZE are permitted to carry out installation, commissioning and maintenance. à If unauthorised changes made to the system, GEZE cannot be made liable in any way whatsoever for any resulting damages.
  • Page 6: Inspection Of Installed System

    Abbreviations TSA 160 NT Inspection of installed system Measures for checking safety and prevention of crushing, impact, shearing or drawing-in spots. Check the function of the presence sensors and movement detectors. Check the protective earth connection to all metal parts that can be touched. Commissioning and service The values of parameter setting are only saved when the Service menu is closed.
  • Page 7: Electrical Data

    TSA 160 NT Electrical data Electrical data Mains voltage 230 V AC –15 %, +10 % 50 Hz Frequency Protection rating Capacity rating 300 W Mains connection Fixed connection (installation cable) Primary fuse 1.6 A (1-leaf drive) T4A (2-leaf drive) Control voltage for external components 24 V DC ±10% Output current control voltage 24 V...
  • Page 8: Control

    Control TSA 160 NT Control RS485-ASF...
  • Page 9: Safety Sensor Open And Close

    TSA 160 NT Safety sensor open and close Safety sensor open and close In the case of 2-leaf systems connect the safety sensors of the active leaf with the active leaf control and those of the passive leaf with the passive leaf control. Install the sensor for monitoring closing on the door leaf, opposite hinge side.
  • Page 10 Safety sensor open and close TSA 160 NT 5. 1 . 1 Monitoring closing and opening Setting the parameter contact type: à DPS: (“normally closed contact”) (factory setting). à ST220: Set the “Input signals”, “SI1 – terminal SIS”, “SI1 contact type” to “normally closed contact”...
  • Page 11 TSA 160 NT Safety sensor open and close 5. 1 .2 Monitoring opening Setting the contact type parameter: à DPS: (“normally closed contact”) (factory setting). à ST220: Set the “Input signals”, “SI3 – terminal SIO”, “SI3 contact type” to “normally closed contact”...
  • Page 12: Safety Sensor Gc 342

    GC 342 opposite hinge side Door transmission cable Settings GC 342 à See installation instructions GC 342. à GEZE recommends using the optional remote control to change the sensor parameters. Settings DCU5 Setting the contact type parameter: à DPS: (normally closed contact) (factory setting).
  • Page 13 TSA 160 NT Safety sensor open and close 5.2.2 Monitoring opening 60 mA Test GC 342 hinge side Door transmission cable Settings DCU5 Setting the contact type parameter: à DPS: (normally closed contact) (factory setting). à ST220: Set the “Input signals”, “SI3 – terminal SIO”, “SI3 contact type” to “normally closed contact” (factory setting). à...
  • Page 14: Safety Sensor Gc 334

    Safety sensor open and close TSA 160 NT Safety sensor GC 334 à GC 334 module, mat. no. 126410 Follow the installation instructions. Set testing: à DPS: (testing with GND). à ST220: Set “Output signals”, “Testing SI” to “Testing with GND”. à S1, S2: Set parameter 11 to 02 “Testing with GND”.
  • Page 15 TSA 160 NT Safety sensor open and close 5.3.2 Monitoring opening Setting the contact type parameter: à DPS: (“normally closed contact”) (factory setting). à ST220: Set the “Input signals”, “SI3 – terminal 13 SIO 60mA SIO” and “SI3 contact type” to “normally closed contact”...
  • Page 16: Safety Sensor Gc 335

    Safety sensor open and close TSA 160 NT 5.3.4 GC 334 connection over interface GC 334 The GC 334 interface is used to connect a customer's existing cable transition. 13 SIO 60mA 10 TST 11 SIS GC 334 module Opposite hinge side Hinge side GC 334 hinge side Interface GC 334...
  • Page 17 TSA 160 NT Safety sensor open and close 5.4. 1 Monitoring closing and opening Setting the contact type parameter: à DPS: (“normally closed contact”) and (“normally closed contact”) (factory setting). à ST220: Set the “Input signals”, “SI1 – terminal SIS”, “SI1 contact type” to “normally closed contact” and “SI3 –...
  • Page 18: Mechanical Contact

    Mechanical contact TSA 160 NT 5.4.2 Monitoring opening Setting the contact type parameter: à DPS: (“normally closed contact”) (factory setting). à ST220: Set the “Input signals”, “SI3 – terminal 60mA SIO” and “SI3 contact type” to “normally closed contact” (factory setting). à...
  • Page 19: Key Switch

    TSA 160 NT Contact sensor inside 6. 1 Key switch à Setting the contact type parameter: à DPS: (factory setting). à ST220: Set the “Signals”, “Input signals”, “KB”, “KB contact type” to “normally opened contact” 20 KB (factory setting). à S1, S2: Set parameter 12 to 01 ”normally opened contact“.
  • Page 20: Radar Movement Detector Gc 304 R

    Contact sensor outside TSA 160 NT Radar movement detector GC 304 R à The GC 304 R is a direction-sensitive radar movement GC 304 R detector. - UB à Upon activation, the output of the GC 304 R is closed 80 mA + UB (24V applied to the KI input).
  • Page 21: Radar Movement Detector Gc 304 R

    TSA 160 NT Radio activation Radar movement detector GC 304 R à The GC 304 R is a direction-sensitive radar movement GC 304 R detector. - UB à Upon activation, the output of the GC 304 R is closed 80 mA + UB (24V applied to the KI input).
  • Page 22: Push And Go

    Push And Go TSA 160 NT Push And Go WARNING Danger of injury due to crushing and shearing! During an activated Push And Go function door handles can form crushing and shearing points. à The Push And Go function allows activation of the drive without contact sensors being used. à...
  • Page 23: Emergency Lock

    TSA 160 NT Configurable inputs 11.3 Emergency lock WARNING Danger of injury due to crushing and shearing! The safety sensors and obstruction are not evaluated. The door closes with the set force. If the door closes unexpected, move out of the danger zone. The emergency lock is not permitted with lipped doors and on emergency exits.
  • Page 24: Control Reset

    Configurable inputs TSA 160 NT 11.5.2 Switch function hold-open time (OHZ) In the case of 2-leaf drives, the settings on the active leaf control determine the hold-open time. Setting the parameters: à DPS: (switch function OHZ NO) for: 1st switch contact = open door / 2nd switch contact = close door If the SIO is triggered before the hold-open time or the 2nd switch contact is activated, the hold-open time runs out and is not cancelled by the 2nd switch contact.
  • Page 25: Operating Mode Switchover Off

    TSA 160 NT Configurable inputs 11.8 Operating mode switchover Off à The configurable inputs can be used to change between the operating mode Off as required (depending on the parameter setting). This can, for example, be advisable if the mode of operation is switched by a timer via the available programme switching inputs (AU, DO).
  • Page 26: Closing Position Monitoring, Closing Position Blanking Sis, Push And Go

    Configurable inputs TSA 160 NT 11. 1 0 Closing position monitoring, closing position blanking SIS, Push And Go A closing position limit switch has to be used for closing position monitoring, for blanking the safety sensor close (SIS), for the Push And Go function as well as for the opening delay function. The closing position limit switch can be a supplementary cam switch that is mounted in the drive or a Reed switch that is mounted at the door.
  • Page 27: Wc Control

    TSA 160 NT Configurable inputs 11. 1 1 WC control Only use the fail-safe electric strikes. à In the event of a power failure the door is freely passable. à The “OCCUPIED” changeover switch switches between the AUTOMATIC and NIGHT modes of operation. à...
  • Page 28: Electric Strike

    à Activation of the electric strike is limited to 5 s plus the activation delay time by parameters In case of an TSA 160 NT Invers use only emergency exit electric strikes, holding magnet or GEZE motor lock GEZE IQ Lock EL.
  • Page 29: Customer-Supplied 12 V Ac Electric Strike

    à Fail-safe electric strikes for TSA 160 NT: TOEB à IQ eStrike A5300--B, mat. no. 144631 Mount a free-wheeling diode 1N4007 (1), mat. no. 115293 (no free swing diode is required for GEZE electric strike). Free swing diode Wire jumper 12.2 Customer-supplied 12 V AC electric strike Contact load output TOE with 12 V AC: max.
  • Page 30: Mode Of Operation

    Mode of operation TSA 160 NT Mode of operation à To operate the display programme switch DPS see chapter 24.1, “Display programme switch (DPS)”. à To operate the service terminal ST220 see chapter 23.2, “Operation of ST220”. 13. 1 Internal programme switch à...
  • Page 31: Mechanical Programme Switch (Mps-D, External Programme Switch)

    TSA 160 NT Mode of operation 13.3 Mechanical programme switch (MPS-D, external programme switch) à MPS-D, AS500, mat. no. 118417 PS-GF à MPS-D-ST, with key, AS500, mat. no. 118418 à Operating modes: NA, AU, DO à Accessories: à Surface-mounted cap, single, AS500, mat.
  • Page 32: Display Programme Switch (Dps) With Off

    Mode of operation TSA 160 NT 13.5 Display programme switch (DPS) with OFF à AS500, DPS with OFF, UP, alpine white, mat. no. 151524 RS485 à Operating modes: OFF, NA, LS, AU, DO, 1-leaf/2-leaf opening Follow the installation instructions. 42 RS485-A à...
  • Page 33: 14 2-Leaf Drives

    TSA 160 NT 2-leaf drives 2-leaf drives 14. 1 TSA 160 NT IS-TS: Active leaf automated, passive leaf with TS 160 à Programme switch, mat. no. 72526 Setting the parameters: à DPS: for 1-leaf drive (hold-open time KB) in such a way that the passive leaf only closes when the active leaf is in closing position.
  • Page 34: Smoke Switch Control Unit

    Smoke switch control unit TSA 160 NT Smoke switch control unit à For 2-leaf drives the mains cut-off printed circuit board from the TSA 160-F accessories is installed in the pas- sive leaf drive. Please note the installation and operating instructions of the smoke switch control unit. Setting the parameters: à...
  • Page 35: Motor, Solenoid Valve

    TSA 160 NT Motor, solenoid valve Motor, solenoid valve à TSA 160 NT EN3-6 à Hydraulic unit, mat. no. 019603 à Motor capacitor, mat. no. 058821 140 °C à 1~ motor, 220-230 V, 1.10 A, 50 Hz cos phi 0.98, 0.125 kW, S2-6 Min., GN/YE WSK 140 °C, C 8 µF, 400 V DB, IP44, EN60034 Solenoid valve...
  • Page 36: Mains Connection

    Mains connection TSA 160 NT Mains connection 18. 1 TSA 160 NT 1-leaf à Drive nominal power 300 W Mains fuse (on site) *) T4AH Main switch (provided by customer) **) Door drive unit Fuse terminal strip, fuse 5×20 mm, T4AH/250 V AC Earthing base plate Earthing drive hood Ferrite sleeve *) The customer must use an on-site automatic cut-out as the line-side disconnecting device, the dimensioning...
  • Page 37: Two Automated Door Leaves Tsa 160 Nt

    TSA 160 NT Mains connection 18.3 Two automated door leaves TSA 160 NT à Drive nominal power 2 x 300 W T4AH Mains fuse (on site) *) Ferrite sleeve Main switch (provided by customer) **) Earthing base plate passive leaf drive Earthing drive hood Fuse terminal strip, fuse 5×20 mm, T4AH/250 V AC Intermediate cover kit...
  • Page 38: Tsa 160 Nt Invers At Rwa-Control Panel

    TSA 160 NT Invers at RWA-control panel TSA 160 NT TSA 160 NT Invers at RWA-control panel à Accessory ZR-Invers, mat. no. 090769 à With 2-leaf drives the power disconnection circuit board from the accessory ZR-Invers is mounted in the pas- sive leaf drive. Follow the mounting and operating instructions of the SHEV control panel. Setting the parameters: à...
  • Page 39: Control

    TSA 160 NT Control Control à DCU5 control, mat. no. 118444 à Terminal bag, mat. no. 124448 à S1, S2: Button for configuring/setting parameters à LED1 through LED5: LEDs to display the operation mode, faults, parameters and parameter values RS485 S1 - LED 1 (OG) LED 2 (OG)
  • Page 40: Commissioning And Service

    Commissioning and service TSA 160 NT Commissioning and service Commissioning and service can be carried out with the display programme switch DPS, the service terminal ST220 or using the push buttons S1 and S2. à Parameter setting using the buttons S1 and S2 of the control see chapter 24.2, “Service buttons S1 and S2”. à...
  • Page 41 TSA 160 NT Commissioning and service Switch the mains supply voltage off. Re-establish the RS485 connection active leaf control – passive leaf control. Switch the mains supply voltage on again. With TSA 160NT F: Press the reset switch. Separate parameter setting for the controls is no longer necessary. The drive for which parameter setting is to take place (GF or SF) can be selected via the service terminal.
  • Page 42: Finish Commissioning

    Commissioning and service TSA 160 NT 21.2.4 Commissioning via service push buttons S1 and S2. Configuring a brand-new drive For 2-leaf drives, the RS485 connection can be maintained between active leaf and passive leaf control. The parameters are set directly at the respective control via the Service push buttons. Active leaf drive: 1-leaf drive: Set parameter “01”...
  • Page 43 TSA 160 NT Commissioning and service 21.4. 1 Configuring the active leaf control à For parameter setting with the service terminal ST220, the control to be configured can be selected via the Service menu. à For parameter setting with the service push buttons S1 and S2, parameter setting can take place directly at the control to be configured.
  • Page 44: Mode Of Operation

    Mode of operation TSA 160 NT Mode of operation LED 1 to LED 4 are used to display the set operating mode. Mode of operation ○ ○ ○ ○ ● ○ ○ ○ ● ○ Night mode ○ ○ ● ○...
  • Page 45: Connecting Service Terminal St220

    TSA 160 NT Service menu 23.4 Connecting service terminal ST220 The service terminal ST220 is connected to the control component of the DCU5 at connection RS484 (1). RS485-ASF 23.5 Service menu ST220 23.5. 1 Parameter setting 2-leaf drives Carry out parameter setting for the active leaf/passive leaf individually without RS485 connection. à...
  • Page 46 Service menu TSA 160 NT 23.5.3 Mode of operation Designation Setting values Explanation Mode of operation Operating mode setting Night mode Exit only Automatic Hold open Opening type 2-leaf Open Open active and passive leaves at activation 1-leaf Open Only active leaf opens Open door Opening of the door via ST220 (press button...
  • Page 47 TSA 160 NT Service menu 23.5.5 Movement parameters Designation Setting values Explanation Hold-open times 2-leaf (summer) 0 .. 1 .. 10 .. 12 .. 20 .. 25 .. 50 60 s 1-leaf (winter) 0 .. 1 .. 10 .. 12 .. 20 .. 25 .. 50 60 s Mechanical contact 0 ..
  • Page 48 Service menu TSA 160 NT Designation Setting values Explanation Current state Display Z-> inactive K->normally closed contact KB contact type Not used Input KB without function Normally opened contact Normally closed contact Current state Display Z-> inactive K -> normally opened contact A ->...
  • Page 49 TSA 160 NT Service menu Designation Setting values Explanation P-KI activation Additional contact sensor KI P-KA activation Additional contact sensor KA Switch function With 2-leaf assemblies the push button can be connected to the active leaf control or to the passive leaf control.
  • Page 50 Service menu TSA 160 NT Designation Setting values Explanation Closing position GF Closing position contact of the door leaf à For 1-leaf Door à For 1-leaf Door drive with manual passive leaf (door closer): Closing position contact of the active leaf à...
  • Page 51 TSA 160 NT Service menu Output signals Designation Setting values Explanation Testing SI Current state Z-> inactive Display K -> not used F -> no testing No testing Testing SI Testing switched off Testing with 24 V Testing with GND Diagnosis Designation Setting values...
  • Page 52 à If the password has been forgotten, a special flash file with which the pass- word on the control can be reset to 00 has to be requested from GEZE. à The password cannot be deleted by installing a new software version.
  • Page 53: Display Programme Switch Dps And Service Push Buttons S1, S2

    TSA 160 NT Display programme switch DPS and Service push buttons S1, S2 Display programme switch DPS and Service push buttons S1, S2 24. 1 Display programme switch (DPS) The DPS can be used for commissioning and servicing, mat. no. 151524: à...
  • Page 54 Display programme switch DPS and Service push buttons S1, S2 TSA 160 NT System messages à If one or more faults are pending, these are displayed consecutively alternatively with the current mode of operation in encoded form with service LEDs 1 to 4. à...
  • Page 55: Dps Service Menu And Service Buttons S1/S2 With Leds

    TSA 160 NT Display programme switch DPS and Service push buttons S1, S2 24.3 DPS service menu and service buttons S1/S2 with LEDs à Changing to the Service mode is possible in the NA, LS, AU and DO operating modes. à...
  • Page 56 Display programme switch DPS and Service push buttons S1, S2 TSA 160 NT no. DPS Service-LEDs Parameter Value ST220 display Explanation NO Switchover to OFF (nor- mally opened contact) Switchover Summer NO Switchover Winter Sabotage Closing position GF NO P-KI activation P-KA activation Switch function Switch function OHZ NO...
  • Page 57 TSA 160 NT Display programme switch DPS and Service push buttons S1, S2 no. DPS Service-LEDs Parameter Value ST220 display Explanation ** ○ ● ○ ● Electric strike type No electric strike Fail-secure Fail-safe Motor lock Working close pressure Static close pressure Motor close pressure ** ○...
  • Page 58: Value Table For Service Leds And Display Programme Switch

    Display programme switch DPS and Service push buttons S1, S2 TSA 160 NT no. DPS Service-LEDs Parameter Value ST220 display Explanation Permanently open contact type Not used Only available at ST220 Normally opened contact and with GEZEconnects Normally closed contact ○...
  • Page 59: Fault Messages

    TSA 160 NT Fault messages Fault messages 25. 1 Fault display On the DPS à Currently queued fault messages are displayed on the display programme switch in cycles (10 s). In addition, they are also entered in the fault memories. e® à...
  • Page 60: Fault Messages Keypad Programme Switch

    Fault messages TSA 160 NT Display of passive leaf faults on the active leaf (DPS, service LEDs, ST220/GEZEconnects) DPS Service-LEDs Fault message ST220 Fault description SF - Faulty solenoid valve SF - Faulty solenoid valve The faults are displayed SF - Motortriac SF - Motortriac defective at the active leaf SF - Motor relay...
  • Page 61 TSA 160 NT Fault messages...
  • Page 62 Fault messages TSA 160 NT...
  • Page 63 TSA 160 NT Fault messages...
  • Page 64 E-Mail: danmark.se@geze.com Tel. +49 (0) 7152 203 594 www.geze.at www.geze.hu www.geze.dk E-Mail: leonberg.de@geze.com Baltic States Iberia Singapore GEZE GmbH Baltic States office GEZE Iberia S.R.L. GEZE (Asia Pacific) Pte, Ltd. GEZE GmbH E-Mail: office-latvia@geze.com E-Mail: info@geze.es E-Mail: gezesea@geze.com.sg Niederlassung Süd-Ost www.geze.com www.geze.es...

Table of Contents

Save PDF