An-10 Terminal 53 Low Voltage; An-11 Terminal 53 High Voltage; An-14 Terminal 53 Low Ref./Feedb. Value; An-15 Terminal 53 High Ref./Feedb. Value - GE AF-600 FP Operating Instructions Manual

Fan and pump drive (460v/575v 150hp and above)
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip

AN-10 Terminal 53 Low Voltage

Range:
0.07 V*
[0.00 - par. AN-11 V]

AN-11 Terminal 53 High Voltage

Range:
10.00 V*
[par. AN-10 - 10.00 V]

AN-14 Terminal 53 Low Ref./Feedb. Value

Range:
0.000 N/A*
[-999999.999 - 999999.999 N/A]

AN-15 Terminal 53 High Ref./Feedb. Value

Range:
50.000 N/A* [-999999.999 - 999999.999 N/A]
1.
par. AN-01 Live Zero Timeout Function
2.
par. O-04 Control Word Timeout Function
The output frequency of the frequency converter can be:
[1] frozen at the present value
[2] overruled to stop
[3] overruled to jog speed
[4] overruled to max. speed
[5] overruled to stop with subsequent trip
Function:
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
feedback value set in par. AN-14 Terminal 53 Low Ref./Feedb. Value.
Function:
Enter the high voltage value. This analog input scaling value should correspond to the high reference/
feedback value set in par. AN-15 Terminal 53 High Ref./Feedb. Value.
Function:
Enter the analog input scaling value that corresponds to the low voltage/low current set in par.
AN-10 Terminal 53 Low Voltage and par. AN-12 Terminal 53 Low Current.
Function:
Enter the analog input scaling value that corresponds to the high voltage/high current value set in par.
AN-11 Terminal 53 High Voltage and par. AN-13 Terminal 53 High Current.
AF-600 FP High Power Operating Instructions