2 CALCULATION OF SETTINGS
Table 2–11: PROTECTION SETTINGS GUIDE (Sheet 5 of 7)
NO.
MNEMONIC
SCADA_DTA
1501
FLTLOCK
1502
FLTRESET
OS BLOCKING
1601
MOBZONE
1602
MOBCHARANG
1603
BLOCKWHAT
1604
BLOCKZ1
1605
BLOCKZ2
1606
BLOCKZ3
1607
BLOCKZ4
OS TRIPPING (OUT-OF-STEP TRIPPING MODELS ONLY)
1701
USE_OST
1702
NUMBRCHAR
1703
TRIPIN_OUT
1704
FWDREACH
1705
REVREACH
1706
OUTER
1707
MIDDLE
1708
INNER
1709
TLOS1PU
1710
TLOS1DO
1711
TLOS2PU
1712
TLOS3PU
1713
TLOS4PU
RECLOSER
1801
RECLMODE
RECTYPE
^
1802
^
NUM1P
1803
^
1PDELAY1
1804
^
1PDELAY2
1805
^
1PDELAY3
1806
^
1PDELAY4
1807
1808
NUM3P
1809
3PDELAY1
1810
3PDELAY2
1811
3PDELAY3
1812
3PDELAY4
1813
RESETTIME
1814
DWELLTIME
1815
HOLD
1816
HOLDTIME
† Setting value QUAD applies to Revision B models only.
‡ Setting applicable to Revision B models only.
^ Setting applicable to Single Phase Tripping models only.
GE Power Management
DESCRIPTION
Hold Time
Fault Location Reset Time
Coordinating Zone
MOB Characteristic Angle
Block during OS
Block all Zone 1 Functions
Block all Zone 2 Functions
Block all Zone 3 Functions
Block all Zone 4 Functions
Select OST
Select Number of Characteristics
Trip Entering or Leaving Inner
OST Forward Reach
OST Reverse Reach
Outer Characteristic Angle
Middle Characteristic Angle
Inner Characteristic Angle
Coordinating Timer 1 Pickup
Coordinating Timer 1 Dropout
Coordinating Timer 2 Pickup
Coordinating Timer 3 Pickup
Coordinating Timer 4 Pickup
Select Reclosing Option
Set Reclosing Type
Number of Attempts Following 1P
Trip
1 Pole First Delay
1 Pole Second Delay
1 Pole Third Delay
1 Pole Fourth Delay
Number of Attempts Following 3P
Trip
3 Pole First Delay
3 Pole Second Delay
3 Pole Third Delay
3 Pole Fourth Delay
Reset Time
Contact Dwell Time
Inhibit Hold Select
Inhibit Hold Time
ALPS Advanced Line Protection System
RANGE (5A)
RANGE (1A)
0 to 99.9 sec. step 0.1
0 to 999 minutes step 1
ZONE2, ZONE3, ZONE4
30 to 130 deg. step 1
BLKALL, BLKDIST, BLKPHAS, BLKNONE
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
2, 3
IN, OUT
0.1 to 75.0 ohms
0.5 to 375.0 ohms
step 0.1
step 0.5
0.1 to 75.0 ohms
0.1 to 375.0 ohms
step 0.1
step 0.5
40 to 165 deg. step 1
40 to 165 deg. step 1
40 to 165 deg. step 1
1 to 100 msec. step 1
1 to 100 msec. step 1
1 to 100 msec. step 1
1 to 100 msec. step 1
1 to 100 msec. step 1
OFF, NONE, INTERNAL, EXTERNAL, BOTH
1POLE, 3POLE, 1POLE/3POLE
1 to 4 step 1
0.1 to 300 sec. step 0.1
0.1 to 300 sec. step 0.1
0.1 to 300 sec. step 0.1
0.1 to 300 sec. step 0.1
1 to 4 step 1
0.1 to 300 sec. step 0.1
0.1 to 300 sec. step 0.1
0.1 to 300 sec. step 0.1
0.1 to 300 sec. step 0.1
0.1 to 300 sec. step 0.1
0.1 to 2 sec. step 0.1
NO, YES
1 to 1000 sec. step 1
2.5 REFERENCE TABLES
DEFAULT
0 sec.
0 minutes
ZONE3
70 deg.
BLKALL
YES
YES
YES
YES
NO
3
OUT
15.0Ω at 5A
75.0Ω at 1A
5.0Ω at 5A
25.0Ω at 1A
90 deg.
105 deg.
120 deg.
40 msec.
40 msec.
40 msec.
40 msec.
40 msec.
OFF
3POLE
1
0.1 sec.
0.1 sec.
0.1 sec.
0.1 sec.
1
0.1 sec.
0.1 sec.
0.1 sec.
0.1 sec.
1 sec.
0.1 sec.
NO
1 sec.
2-61