Control And Status Word 1 - Siemens SINAMICS G120D Series Operating Instructions Manual

Distributed converter, control units cu240d-2 with encoder evaluation.
Hide thumbs Also See for SINAMICS G120D Series:
Table of Contents

Advertisement

Adapt fieldbus configuration
6.2 PROFIdrive profile for PROFIBUS and PROFINET
Figure 6-3
The telegrams use - with the exception of telegram 999 (free interconnection) - the word-by-
word transfer of send and receive data (r2050/p2051).
If you require an individual telegram for your application (e.g. for transferring double words),
you can adjust one of the predefined telegrams via parameters p0922 and p2079. For
details, please refer to the List Manual, function diagrams 2420 and 2472.
6.2.1.1

Control and status word 1

Control word 1 (STW1)
Bit
0
1
2
94
Interconnection of the receive words
Significance
Telegram 20
All other tele-
grams
0 = OFF1
0 → 1 = ON
0 = OFF2
1 = No OFF2
0 = Quick stop (OFF3)
Explanation
The motor brakes with the ramp-down time
p1121 of the ramp-function generator. The
inverter switches off the motor at standstill.
The inverter goes into the "ready" state. If, in
addition bit 3 = 1, then the inverter switches on
the motor.
Switch off the motor immediately, the motor
then coasts down to a standstill.
The motor can be switched on (ON com-
mand).
Quick stop: The motor brakes with the OFF3
ramp-down time p1135 down to standstill.
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB
Signal inter-
connection
in the in-
verter
p0840[0] =
r2090.0
p0844[0] =
r2090.1
p0848[0] =
r2090.2
Converter with control units CU240D-2