Advanced commissioning
7.3 Setpoints
2. Binary selection:
You set 16 different fixed setpoints. You precisely select one of these 16 fixed setpoints
by a combination of four selection bits.
Figure 7-16
Additional information about binary selection can be found in function diagram 3010 in the
List Manual.
Parameter for setting the fixed setpoints
Parameter
p1001
p1002
...
p1015
p1016
p1020
p1021
p1022
p1023
r1024
r1025.0
134
Simplified function diagram for binary selection of the setpoints
Description
Fixed speed setpoint 1 (factory setting: 0 rpm)
Fixed speed setpoint 2 (factory setting: 0 rpm)
...
Fixed speed setpoint 15 (factory setting: 0 rpm)
Speed fixed setpoint mode (factory setting: 1)
1:
Direct
2:
Binary
Speed fixed setpoint selection bit 0 (factory setting: 0)
Speed fixed setpoint selection bit 1 (factory setting: 0)
Speed fixed setpoint selection bit 2 (factory setting: 0)
Speed fixed setpoint selection bit 3 (factory setting: 0)
Fixed speed setpoint effective
Fixed speed setpoint status
1 signal
Fixed speed setpoint is selected
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB