Instructions for installation, use and
maintenance for current and voltage
transformers
This installation, use and maintenance
guide is valid for current and voltage
transformers operating in indoor
conditions.

1. Service conditions

01 Example of current
transformer label
The transformers should be mounted in dry indoor
conditions where the ambient air is not signifi-
cantly polluted by dust, smoke, corrosive gases,
vapours or salt.
The transformers are designed for standard ambi-
ent temperature between –5°C and +40°C. The al-
titude for use should be lower than 1000 m above
the sea level. The transformers may be used also in
higher or lower ambient temperatures and higher
altitudes when agreed between the manufacturer
and purchaser.

2. Technical details

The technical details for each individual trans-
former are mentioned on the rating plate fastened
on the transformer. Values mentioned on the rat-
ing plate must not be exceeded. Markings used on
the rating plate are as follows:
These instructions are valid for
Current transformer type:
TPU; TPE; TTR; BB; BBO; KOKS; KOFA; IHBF
Voltage transformers types:
TJE; TJCL; TJC; TJCH; TDC; TJP; TJPH; TDP; KGUG; KGUGI
01
Where:
1VLT5116001275
TPU 60.23
or.n. 544234
150-
300//5/5A+CD
50 Hz
1S1-1S2
1S1-1S3
2S1-2S2
2S1-2S3
0.5FS10, 10P10
10 VA
ext
Ck-PE
Icth
24/50/125 kV
Ith
40°C
IEC 61869-2
Idyn
E
2016
3
serial number + barcode
transformer type code
order number
rated transformer ratio + capacitive
divider
rated frequency
terminal marking for core number 1,
first tap
terminal marking for core number 1,
second tap
terminal marking for core number 2
terminal marking for core number 2
accuracy classes
rated output
extension
capacitive voltage divider
specifications (see page 5.)
rated thermal current
highest voltage for equipment /
power-frequency withstand voltage
/ rated lightning-impulse voltage
rated short time thermal current
(thermal time)
ambient temperature
referred standard(s)
rated dynamic current
temperature class
year of production