SIMOCODE pro Introduction Advantages/benefits/configuration with SIMOCODE pro Areas of application Industrial Controls Features Motor management and control devices Overview of functions SIMOCODE pro Check list for selecting a device series System Manual An overview of system components Description of system components Compartment identification Accessories 3UF50 compatibility mode...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Table of contents Introduction ............................. 9 Important notes ......................... 9 Siemens Industry Online Support ................... 12 Siemens Industry Online Support app ..................14 Support Request ........................15 Security information ........................ 16 Current information about operational safety ................. 17 Information about third-party software ..................18 Recycling and disposal ......................
Page 4
8.3.3.17 Identification of the motor feeder and the SIMOCODE pro components......132 Current measuring modules (IM) for the SIMOCODE pro C, SIMOCODE pro S, and SIMOCODE pro V device series ..................133 Current / voltage measuring modules (UM, UM+) for the SIMOCODE pro V High Performance device series ..................
Page 5
Table of contents Compartment identification ........................159 Applications and advantages of compartment identification ..........159 Hardware and software requirements for compartment identification ........162 Operating compartment identification ................... 163 Mounting, wiring, interfaces, compartment identification ............167 Commissioning and service compartment identification ............170 Alarm, fault, and system events for compartment identification ...........
Page 6
Table of contents Commissioning, service, troubleshooting....................255 13.1 General information about commissioning and service ............255 13.2 Commissioning........................257 13.2.1 Commissioning with PROFIBUS ..................257 13.2.1.1 PROFIBUS commissioning steps ..................257 13.2.1.2 Setting the PROFIBUS DP address..................258 13.2.1.3 Diagnostics via LED display on the basic unit and on the operator panel (PROFIBUS) ..259 13.2.1.4 Diagnostics via LED display on the modules DM-F Local or DM-F PROFIsafe ....
Page 7
15.1 Common technical data ......................329 15.2 Technical specifications of the SIMOCODE pro C / pro S / pro V PB / pro V MR basic units ......................332 15.3 Technical specifications of the SIMOCODE pro V PN / pro V PN GP / pro V EIP basic units......................
Page 8
100 kA and 690 V for 1st generation current / voltage measuring module ......364 15.11 Typical reaction times ......................365 15.11.1 Typical reaction times of the SIMOCODE pro C/V device series ........365 15.11.2 Typical response times of SIMOCODE pro S device series ..........366 15.11.3 Typical reaction times of the Modbus RTU device series ............
This manual is applicable to the listed SIMOCODE pro system components. It contains a description of the components applicable at the time of printing the manual. SIEMENS reserves the right to include updated information about launched new components or new versions of components in a Product Information.
Page 10
When reference is made to "SIMOCODE pro", the reference also includes the following device series: SIMOCODE pro C (see Device series (Page 24)) SIMOCODE pro S (see Device series (Page 24)) SIMOCODE pro V PB (PROFIBUS) (see Device series (Page 24))
Page 11
The manufacturer is responsible for ensuring safe functioning of the complete plant or machine. Siemens AG, its subsidiaries, and associated companies (hereinafter referred to as "Siemens") are not in a position to guarantee every characteristic of a complete plant or machine not designed by Siemens.
Siemens Industry Online Support Information and service At Siemens Industry Online Support you can obtain up-to-date information from our global support database quickly and simply. To accompany our products and systems, we offer a wealth of information and services that provide support in every phase of the lifecycle of your machine or plant –...
Page 13
Introduction 1.2 Siemens Industry Online Support mySupport With "mySupport", your personal work area, you get the very best out of your Industry Online Support experience. Everything enables you to find the right information - every time. The following functions are now available: ●...
Siemens Industry Online Support app Siemens Industry Online Support app You can use the Siemens Industry Online Support app to access all the device-specific information available on the Siemens Industry Online Support portal for a particular article number, including operating instructions, manuals, datasheets, FAQs etc.
Using the Support Request form in Online Support you can send your query directly to our Technical Assistance. After describing your query in a few guided steps, you will immediately be provided with possible suggestions for solving the problem. Support Request: Internet (https://support.industry.siemens.com/My/ww/en/requests) SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure...
(or could be) relevant to operation of safety-related systems. By subscribing to the appropriate newsletter in the Industry newsletter system (https://www.industry.siemens.com/newsletter), you will ensure that you are always up-to-date and able to make changes to your system, when necessary.
SIEMENS is providing you with the OSS portions of this product at no additional cost. Insofar as SIEMENS has combined or linked, according to the definition of the applicable license,...
Page 19
The following license terms and conditions may contain liability limitations that apply between you and the relevant licensor. To clarify matters, your attention is drawn to the fact that SIEMENS shall not cede any warranty obligations on behalf of or as an obligation for a third-party licensor.
Page 20
Introduction 1.7 Information about third-party software LICENSE CONDITIONS AND COPYRIGHT NOTICES Commercial Software: tiva ware - 2.1.0 Enclosed you'll find license conditions and copyright notices applicable for Commercial Software tiva ware - 2.1.0. License conditions: // Redistribution and use in source and binary forms, with or without // modification, are permitted provided that the following conditions // are met: // Redistributions of source code must retain the above copyright...
Introduction 1.8 Recycling and disposal Recycling and disposal For environmentally friendly recycling and disposal of your old device, please contact a company certified for the disposal of old electrical and/or electronic devices and dispose of the device in accordance with the regulations in your country. SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Introduction 1.9 What is SIMOCODE pro? What is SIMOCODE pro? SIMOCODE pro (SIRIUS Motor Management and Control Device) is a flexible and modular motor management system for motors with constant speeds in low-voltage applications. It optimizes the link between the control system and the motor feeder, increases plant availability and allows significant savings to be made during installation, commissioning, operation and maintenance.
Device series The following functionally graduated device series are available for SIMOCODE pro: ● Basic units: SIMOCODE pro C - the compact system for PROFIBUS DP communication with a direct-on-line and reversing starter function and/or for controlling a circuit breaker (MCCB).
Page 25
Introduction 1.10 Device series Figure 1-1 SIMOCODE pro device series SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Introduction 1.11 Modules, interfaces, configuration options 1.11 Modules, interfaces, configuration options For each feeder, every system comprises a basic unit and a separate current measuring module. Both modules are connected to each other electronically via the system interface, by means of a connecting cable, and can be installed together as a unit (behind one another) or separately (side-by-side).
Page 27
Depending on functional requirements, the systems can be used simultaneously in a low-voltage switchboard without any problems and without any additional effort. Parameterization of SIMOCODE pro C or SIMOCODE pro S can be transferred without a problem. SIMOCODE pro...
Page 28
Introduction 1.11 Modules, interfaces, configuration options SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Advantages/benefits/configuration with SIMOCODE pro Advantages/benefits ● The quantity of cabling required between the motor feeder and the PLC is reduced significantly by connecting the entire motor feeder to the process control system via the fieldbus (see Figures "SIMOCODE pro, integrated in the main circuit, control circuit and at automation level (PLC)") ●...
Page 30
Advantages/benefits/configuration with SIMOCODE pro 2.1 Advantages/benefits Figure 2-1 SIMOCODE pro C, pro V, integrated in the main circuit, control circuit and at automation level (PLC) SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 31
Advantages/benefits/configuration with SIMOCODE pro 2.1 Advantages/benefits Figure 2-2 SIMOCODE pro S, integrated in the main circuit, control circuit and at automation level (PLC) SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Advantages/benefits/configuration with SIMOCODE pro 2.2 Independent operation Independent operation SIMOCODE pro protects and controls the motor feeder, independently of the automation system. Even if the automation system (PLC) fails, or if communication is disrupted, the motor feeder remains fully protected and controllable. SIMOCODE pro can be used without being connected to the fieldbus.
Advantages/benefits/configuration with SIMOCODE pro 2.3 Simplifying configuration with SIMOCODE pro Simplifying configuration with SIMOCODE pro Conventional configuration without SIMOCODE pro Individual components are used for control, monitoring and signal pre-processing. The component and wiring requirements for this type of configuration are as follows: ●...
Page 34
Advantages/benefits/configuration with SIMOCODE pro 2.3 Simplifying configuration with SIMOCODE pro Configuration with SIMOCODE pro SIMOCODE pro only is used to perform all control, monitoring and signal pre-processing functions. The advantages of this configuration are as follows: ● Additional overload relays, thermistor evaluation devices, current transformers and analog/digital converters are not necessary.
Advantages/benefits/configuration with SIMOCODE pro 2.4 Typical configuration Typical configuration The following figures show typical hardware configurations: Figure 2-5 Typical SIMOCODE pro C hardware configuration Figure 2-6 Typical SIMOCODE pro S hardware configuration SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 36
Advantages/benefits/configuration with SIMOCODE pro 2.4 Typical configuration Figure 2-7 Typical SIMOCODE pro V PN GP hardware configuration Figure 2-8 Typical SIMOCODE pro V PROFIBUS/Modbus RTU hardware configuration SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 37
Advantages/benefits/configuration with SIMOCODE pro 2.4 Typical configuration Figure 2-9 Typical SIMOCODE pro V PN/EtherNet/IP hardware configuration For information about system components, see Chapter Description of system components (Page 81). SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 38
Advantages/benefits/configuration with SIMOCODE pro 2.4 Typical configuration SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Areas of application SIMOCODE pro is often used for automated processes where plant downtimes are very expensive (e.g. steel or cement industry) and where it is important to prevent plant downtimes through detailed operating, service and diagnostics data or to localize the fault very quickly in the event of a fault.
Page 40
Areas of application SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
● Safety-related tripping of motor feeders, e.g. fail-safe tripping in the process industry, locally or via fieldbus (see manual "SIMOCODE pro Safety fail-safe digital modules" (https://support.automation.siemens.com/WW/view/en/50564852)) Recording of measured curves SIMOCODE pro is able to record measured curves and can, for example, illustrate the characteristic curve of the motor current during motor startup.
Page 42
Features Flexible motor control with integrated control functions (instead of extensive hardware interlocks): SIMOCODE pro has many pre-defined, integrated motor control functions, including all necessary connections and interlocks: ● Overload relay ● Direct starter (direct-on-line starter) ● Reversing starter ● Star-delta starter, also with direction reversal ●...
Page 43
PROFIBUS DPV1 is the extension of the DP protocol. It enables acyclic data exchange of parameter, diagnostic, receive and test data. SIMOCODE pro C, pro S and pro V support, among others: ● Baud rates up to 1.5 Mbit / s or 12 Mbit / s ●...
Page 44
● Shared device in combination with DF-FP modules ● Media redundancy (device with two ports) ● System redundancy ● RT communication ● Support for PROFIenergy See Chapter "PROFINET communication" in the manual SIMOCODE pro - Communication (https://support.industry.siemens.com/cs/ww/en/view/109743960). SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 45
("Multipoint System requirements") listed in the specification apply equally for a communication network with SIMOCODE devices. See Chapter "Modbus communication" in the manual SIMOCODE pro - Communication (https://support.industry.siemens.com/cs/ww/en/view/109743960). Communication via EtherNet/IP: EtherNet/IP (EtherNet Industrial Protocol, often simply called EIP) is a real-time Ethernet that is used mainly in automation engineering.
Page 46
Features SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Overview of functions Protection functions Detailed description: See Chapter "Motor protection" in the manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958). Overload protection Current-dependent electronic protection of three-phase and AC motors with adjustable tripping characteristics (class times) according to IEC 60947-4-1 requirements. Unbalance protection Protects motors from excessive temperatures caused by excessive phase unbalance.
Page 48
● Chapter "Dry-running protection for centrifugal pumps by active power monitoring (Page 314)" in the safety and commissioning information for Ex areas ● Chapter "Dry-running protection for centrifugal pumps" in the manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958). SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Monitoring functions Detailed description: See Chapters "Monitoring functions" and "Logic blocks" in the manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958). Current limit monitoring Current limit monitoring is used for process monitoring. This enables incipient anomalies in the system to be detected in good time. If a current limit is exceeded but still below the overload limit, it can, for example, indicate a dirty filter on a pump, or an increasingly sluggish motor bearing.
Page 50
Overview of functions 5.2 Monitoring functions Voltage monitoring High Performance SIMOCODE pro V allows voltage monitoring of a three-phase current network or a single-phase network for undervoltage or further availability: ● Monitoring for undervoltage: Two-level monitoring for freely selectable limits. The response of SIMOCODE pro on reaching a prewarning level or trip level can be freely parameterized.
Page 51
. Further information can be found in Chapter "Limit monitors" in the manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958). 1) For use with current / voltage measuring module 2) Temperature module or multifunction module additionally required 3) Analog module additionally required...
● Operating instructions "Fail-Safe Digital Module DM-F PROFIsafe" (https://support.automation.siemens.com/WW/view/en/49222281). You will find the System Manuals and Operating Instructions at Manuals/operating instructions (https://support.industry.siemens.com/cs/ww/en/ps/16027/man) CAUTION Loss of safety function is possible For the 24 V DC power supply, always use an SELV or PELV power supply unit!
All the necessary protection functions and interlocks are already available and can be flexibly adapted and expanded. For a detailed description of the individual control functions: See Chapter "Motor control" in the manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958). SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
— — ✓ Detailed description: See Chapter "PROFIBUS DP communication" in the manual SIMOCODE pro - Communication (https://support.industry.siemens.com/cs/ww/en/view/109743960). Modbus RTU SIMOCODE pro V Modbus RTU possesses integrated Modbus RTU communication functions. Detailed description: See Chapter "Modbus communication" in the manual SIMOCODE pro - Communication (https://support.industry.siemens.com/cs/ww/en/view/109743960).
Page 55
Performance device have an integrated web server function that permits access to the service and diagnostic data from a PC on which a web browser is installed. Detailed descriptions: See Chapter "PROFINET communication" in the manual SIMOCODE pro - Communication (https://support.industry.siemens.com/cs/ww/en/view/109743960). SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 56
● Deactivation of ports Detailed description: See Chapter "EtherNet/IP communication" in the manual SIMOCODE pro - Communication (https://support.industry.siemens.com/cs/ww/en/view/109743960). Web server In addition to the EtherNet/IP communication functions, SIMOCODE pro V EIP has an integrated web server function that permits access to the service and diagnostic data from a PC on which a web browser is installed.
(calculators) Analog — — — — — multiplexer Pulse width — — — — — modulator 1) from version *E03* Detailed description: See Chapter "Logic blocks" in the manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958). SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Overview of functions 5.8 Operating, service and diagnostics data Operating, service and diagnostics data SIMOCODE pro supplies a large amount of detailed operating, service and diagnostics data. Operating data ● Motor switching state (ON, OFF, LEFT, RIGHT, SLOW, FAST), derived from the current flow in the main circuit: thus, feedback via auxiliary contacts of circuit breakers and contactors is not necessary.
Page 60
Overview of functions 5.8 Operating, service and diagnostics data Service data Among other things, SIMOCODE pro provides the following relevant data for maintenance: ● Number of motor operating hours, also resettable ● Motor stop times, also resettable ● Number of motor starts, also resettable ●...
Check list for selecting a device series The following check list should help you decide upon the optimum device series for your requirements: Function/component SIMOCODE pro V PN GP V PB V MR V PN V EIP Control functions Intelligent overload ✓...
Page 62
Check list for selecting a device series Function/component SIMOCODE pro V PN GP V PB V MR V PN V EIP Power factor (cos phi) — — — ✓ ✓ ✓ ✓ monitoring Monitoring operating ✓ ✓ ✓ ✓ ✓ ✓...
Page 63
Check list for selecting a device series Function/component SIMOCODE pro V PN GP V PB V MR V PN V EIP Digital module; — — ✓ ✓ ✓ ✓ ✓ monostable relay; 110 to 240 V AC/DC inputs Digital module; bistable —...
Page 64
Check list for selecting a device series SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
An overview of system components Modules Selection and ordering data: See also Catalog IC10 (https://www.siemens.com/ic10). For simple product selection, we recommend the TIA Selection Tool (https://www.siemens.com/TIA-Selection-Tool). Note Product version data The product version data (*Exx*) refer to the device series (pro C, pro S, etc.).
Page 66
Number that can be connected to supply pro C pro S V PN pro V pro V pro V pro V voltage Basic units (BU) SIMOCODE pro C — — — — — — — The compact Basic Performance system for PROFIBUS and direct-on-line and reversing starters and/or for controlling a circuit breaker.
Page 67
— — — The variable High Performance system for PROFIBUS, which offers numerous functions in addition to all of the SIMOCODE pro C/S functions. 4 inputs/3 outputs freely parameterizable, input for thermistor, monostable relay outputs, expandable with expansion modules From product version *E16* with...
Page 68
— — — The variable High Performance system for EtherNet/IP that offers numerous functions in addition to all of the SIMOCODE pro C/S functions. 4 inputs/3 outputs freely parameterizable, input for thermistor, monostable relay outputs, expandable with expansion modules From product version *E04* with...
Page 69
An overview of system components Module Control MLFB Diagram Number that can be connected to supply pro C pro S V PN pro V pro V pro V pro V voltage Current measuring module (IM) Current measuring with through-hole or bus connection system.
Page 70
An overview of system components Module Control MLFB Diagram Number that can be connected to supply pro C pro S V PN pro V pro V pro V pro V voltage Current/voltage measuring module (UM) Can only be mounted next to the basic unit, otherwise like current measuring modules.
Page 71
An overview of system components Module Control MLFB Diagram Number that can be connected to supply pro C pro S V PN pro V pro V pro V pro V voltage 2nd generation current/voltage measuring modules (UM+) Can only be mounted below / next to the basic unit, otherwise like current measuring modules.
Page 72
An overview of system components Module Control MLFB Diagram Number that can be connected to supply pro C pro S V PN pro V pro V pro V pro V voltage Digital modules (DM) 2) Up to two digital modules can be used to add additional binary inputs and relay outputs to the basic unit.
Page 73
An overview of system components Module Control MLFB Diagram Number that can be connected to supply pro C pro S V PN pro V pro V pro V pro V voltage DM-F PROFIsafe fail-safe digital module For fail-safe tripping via PROFIBUS/PROFIsafe: 2 relay enabling circuits, wired in parallel 2 relay outputs, common ground, fail-safe tripping 1 input for feedback circuit;...
Page 74
An overview of system components Module Control MLFB Diagram Number that can be connected to supply pro C pro S V PN pro V pro V pro V pro V voltage Multifunction module To expand the number of inputs and outputs •...
Page 75
An overview of system components Note Usage restrictions concerning the operator panel with display • SIMOCODE pro V PB basic unit: The operator panel with display can only be used with SIMOCODE pro V PB basic unit from version *E03*. •...
Page 76
An overview of system components Accessories Selection and ordering data: See also Catalog IC10 (https://www.siemens.com/ic10). Table 7- 2 System components, accessories that can be connected System component, MLFB Diagram for V for pro accessory pro C pro S PN GP...
Page 77
An overview of system components System component, MLFB Diagram for V for pro accessory pro C pro S PN GP V PB pro V MB pro V pro V Length of Length system of open 3UF7931-0CA00-0 interface cable 3UF7932-0CA00-0 0.1 m 3UF7937-0CA00-0 1.0 m 0.5 m...
Page 78
An overview of system components System component, MLFB Diagram for V for pro accessory pro C pro S PN GP V PB pro V MB pro V pro V Labeling strips ✓ ✓ ✓ ✓ ✓ ✓ ✓ for pushbuttons of the 3UF7925-0AA00-0 operator panel 3UF7 20 3UF7925-0AA01-0...
Page 79
An overview of system components System component, MLFB Diagram for V for pro accessory pro C pro S PN GP V PB pro V MB pro V pro V Covers for screwed ✓ ✓ ✓ ✓ ✓ ✓ ✓ connection: between contactor and current measuring 3RT1956-4EA3...
Page 80
An overview of system components Software For parameterization, control, diagnostics and testing: See Manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958). Selection and ordering data: See also Catalog IC10 (https://www.siemens.com/ic10). SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Description of system components Basic units (BU) Types of basic units The basic units are the fundamental components of the SIMOCODE pro system. Basic units are always necessary when using SIMOCODE pro. They contain the processor in which all protection, control and monitoring functions of the SIMOCODE system are executed. Figure 8-1 Basic units The basic units are suitable for DIN rail mounting or with additional push-in lugs for mounting...
Page 82
8.1 Basic units (BU) SIMOCODE pro C basic unit Basic unit pro C is the fundamental component of the SIMOCODE pro C device series and is used in conjunction with a current measuring module and optional operator panels. The following motor control functions are supported: ●...
Page 83
● Soft starter control, possibly combined with reversing starter The SIMOCODE pro V High Performance basic units provide the following expansion options not offered by the SIMOCODE pro C, SIMOCODE pro S and SIMOCODE PRO V PN GP basic units: ●...
Page 84
TEST/RESET button or, for example, by accepting the PROFIBUS address. You will find further information in Chapter "Test/Reset" in the manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958), in Chapters Setting the PROFIBUS DP address (Page 258) and Setting IP parameters and PROFINET device name (Page 261) and in Chapter Backing up and saving parameters (Page 277).
Description of system components 8.2 Operator panel (OP) Operator panel (OP) Function of the operator panel The operator panel controls the motor feeder from the switchgear cabinet. It has an external system interface on the front to allow easier parameterization or diagnostics via a PC / programming device.
Page 86
Description of system components 8.2 Operator panel (OP) Labeling strips: Labeling strips are enclosed for designating buttons 1 to 4 and the yellow LEDs 1 to 3: ● Buttons 1 to 4: 6 pre-assigned labeling strips and 1 individually inscribable labeling strip ●...
Page 87
Description of system components 8.2 Operator panel (OP) "Park position" for memory module: The memory module can be protected from unauthorized use by "parking" it on the rear of the operator panel inside the switchgear cabinet. In this case, the storage clips for the labeling strips cannot be used.
Description of system components 8.3 Operator panel with display Operator panel with display 8.3.1 Description of the operator panel with display Apart from the standard operator panel (OP), an optional operator panel with display (OPD) is also available for the SIMOCODE pro V High Performance device series. This operator panel can additionally display current measured values, operating data, diagnostics data or status information of the motor feeder on the cabinet.
Page 89
Description of system components 8.3 Operator panel with display Note Modification of selected device parameters via the operator panel with display Modification of selected device parameters is possible via the operator panel with display (see Parameters (Page 124)) The following figure shows an operator panel with display: Figure 8-6 Operator panel with display The operator panel with display can be connected directly to basic unit SIMOCODE pro V or...
Page 90
Description of system components 8.3 Operator panel with display Labeling strips: Labeling strips for labeling buttons 1 to 4 (6 pre-assigned and 1 that can be labeled individually) are included: Figure 8-7 Labeling strips for the buttons of the operator panel with display Unused labeling strips can be stored on the back of the operator panel with display: Figure 8-8 Storage clips for labeling strips...
Page 91
Description of system components 8.3 Operator panel with display "Park position" for memory module: The memory module can be "parked" on the front of the operator panel with display beneath the system interface: Figure 8-9 "Park position" for memory module SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Description of system components 8.3 Operator panel with display 8.3.2 Operator controls and display elements of the operator panel with display Displays of the operator panel with display The display shows current measured values, operating data and diagnostics data as well as the status information of the motor feeder in plain text or with the aid of symbols.
Page 93
(see also Chapter Operator panel with display (Page 88) and Chapters "Operator panel LED" and "Operator panel buttons" in the manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958)) Two softkeys. They can have different functions depending on the menu displayed (e.g.
Description of system components 8.3 Operator panel with display 8.3.3 Menu of the operator panel with display 8.3.3.1 Timing charts Navigating the menu of the operator panel with display Main menu, operator panel with display Details: See Displays of the operator panel with display (Page 109). Figure 8-12 Main menu, operator panel with display SIMOCODE pro...
Page 95
Description of system components 8.3 Operator panel with display Main display, operator panel with display Details: See Read and adapt main display (Page 112). 1 Measured values, operator panel with display Details: See Display of measured values in the measured values display (Page 115). Figure 8-13 Measured values, operator panel with display SIMOCODE pro...
Page 96
Description of system components 8.3 Operator panel with display Note Numbering of the displays The numbering is valid with the maximum expansion. 2 Status motor protection/motor control, operator panel with display Details: See Motor protection and motor control status (Page 117). Figure 8-14 Status motor protection/motor control, operator panel with display - PROFIBUS / Modbus RTU...
Page 97
Description of system components 8.3 Operator panel with display Figure 8-15 Status motor protection/motor control, operator panel with display - PROFINET / EtherNet/IP SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 98
Description of system components 8.3 Operator panel with display 3 Statistics/maintenance, operator panel with display Details: See Display of statistical and maintenance-relevant information on the statistics/maintenance display (Page 119). Figure 8-16 Statistics/maintenance, operator panel with display - PROFIBUS / Modbus SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 99
Description of system components 8.3 Operator panel with display Figure 8-17 Statistics/maintenance, operator panel with display - PROFINET / EtherNet/IP SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 100
Description of system components 8.3 Operator panel with display 4 Communication on the fieldbus, operator panel with display Details: See Status display for fieldbus communication (Page 120). Figure 8-18 Communication on PROFIBUS / Modbus, operator panel with display SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 101
Description of system components 8.3 Operator panel with display Figure 8-19 Communication on PROFINET/EtherNet/IP, operator panel with display SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 102
Description of system components 8.3 Operator panel with display 5 Device I/Os, operator panel with display Details: See Displays the current status of all device I/Os (Page 122). Figure 8-20 Device I/Os, operator panel with display SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 103
Description of system components 8.3 Operator panel with display 6 Parameters, operator panel with display SIMOCODE pro V allows selected parameters to be set using the operator panel with display Details: See Parameters (Page 124) Figure 8-21 Parameter settings, operator panel with display Overview of the basic units and operator panels and their product versions, which permit the setting of parameters via the operator panel with display: Operator panel...
Page 104
Description of system components 8.3 Operator panel with display 7 Display settings, operator panel with display Details: See Adapt display settings (Page 126). Figure 8-22 Display settings, operator panel with display SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 105
Description of system components 8.3 Operator panel with display 8 commands, operator panel with display (for pro V PB / pro V MR basic units) Details: See Resetting, testing and parameterizing via commands (Page 129). Figure 8-23 Commands, operator panel with display 9 Messages, operator panel with display Details: See Display of all pending status information (Page 130).
Page 106
Description of system components 8.3 Operator panel with display 10 Warnings, operator panel with display Details: See Display of all pending warnings (Page 130). Figure 8-25 Warnings, operator panel with display 11 Faults, operator panel with display Details: See Display of all pending faults (Page 130). Figure 8-26 Faults, operator panel with display 12 Fault memory, operator panel with display...
Page 107
Description of system components 8.3 Operator panel with display 13 Event memory, operator panel with display (only for OPD as from *E06* and BU2 as from *E07*) Details: See Reading out the device-internal event memory (Page 131). Figure 8-28 Event memory, operator panel with display SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 108
Description of system components 8.3 Operator panel with display 14 Identification, operator panel with display Details: See Identification of the motor feeder and the SIMOCODE pro components (Page 132). Figure 8-29 Identification, operator panel with display SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Description of system components 8.3 Operator panel with display 8.3.3.2 Displays of the operator panel with display You can navigate through the menu using the arrow keys and softkeys. Each menu item may have one or more submenus. The menu structure and display are, in part, directly dependent on the device parameterization (e.
Page 110
Description of system components 8.3 Operator panel with display The parameterization is possible with the following combinations of basic unit/operator panel with display: Operator panel 3UF7210- 3UF7210- 3UF7210- 3UF7210- 1AA00-0 1BA00-0 1AA01-0 1BA01-0 SIMOCODE pro V PN 3UF7011-1A.00-0 E01 E07 SIMOCODE pro V EIP 3UF7013-1A.00-0 E01 E07 SIMOCODE pro V PROFIBUS...
Page 111
Description of system components 8.3 Operator panel with display ● Event memory The "Event Memory" menu item enables access to the SIMOCODE pro device-internal event memory. For detailed information: See "Reading out the device-internal event memory (Page 131)." Note Precondition for event memory display Is only displayed if DM-F present.
Description of system components 8.3 Operator panel with display 8.3.3.3 Read and adapt main display To enable users speedy viewing of the measured values typically shown on their switchboard, various profiles are stored in the operator panel with display that enable user- specific adaptation of the standard measured values displayed in the SIMOCODE pro main display.
Page 113
Description of system components 8.3 Operator panel with display ● Inputs AM 1 / inputs AM2 [mA] Shows the current value at the two inputs of analog module 1 / 2 in mA. ● Max. temp. °C TM 1 / TM2 Shows the maximum temperature of all used sensor measuring circuits of the temperature module 1 / 2 in °C.
Page 114
Description of system components 8.3 Operator panel with display ● Calculator 2 Shows the calculated result that the function block Calculator 2 provides without units in the range 0 ... 65535. Permits display, for example, of a 2-byte or 4-byte value sent directly from the automation system on the display of the switchboard or the display without units of each 2-byte and 4- byte value in SIMOCODE pro.
Description of system components 8.3 Operator panel with display 8.3.3.4 Display of measured values in the measured values display The "Measured Values" menu item displays all current SIMOCODE pro measured values. Depending upon the type of expansion modules used, all or only some of the values listed here will be available.
Page 116
Description of system components 8.3 Operator panel with display ● T1, T2, T3 Shows the individual temperatures of all used sensor measuring circuits of the temperature module 1 in °C (can be switched to °F). ● T1, T2, T3 Shows the individual temperatures of all used sensor measuring circuits of the temperature module 2 in °C (can be switched to °F).
Description of system components 8.3 Operator panel with display 8.3.3.5 Motor protection and motor control status The status display shows all higher-level status information, i.e. all status information relevant to the protection and controlling of the motor. The type of status information depicted is, therefore, in part directly dependent upon the parameterized control function and the hardware configuration of SIMOCODE pro, and may vary.
Page 118
Description of system components 8.3 Operator panel with display Safety ● Safety DM-F Local: Status of enabling circuit, shutdown "Safety," "Safety o.k." (only with an OPD as from product version *E04*, a SIMOCODE pro V MR / PN / EIP basic unit or a SIMOCODE pro V PB basic unit as from product version *E07* and a DM-F Local) ●...
Description of system components 8.3 Operator panel with display 8.3.3.6 Display of statistical and maintenance-relevant information on the statistics/maintenance display The "Statistics/Maintenance" menu item gives an overview of all SIMOCODE pro information that is primarily relevant to maintenance. The states of timers and counters, etc. are displayed, as well as operating hours, stop times and the number of starts.
Description of system components 8.3 Operator panel with display 8.3.3.7 Status display for fieldbus communication The "Communication" menu item displays all important information concerning fieldbus communication. PROFIBUS/Modbus: In addition to the current PROFIBUS/Modbus device address, the baud rate or fieldbus-relevant settings concerning process and diagnostic alarms to the automation system.
Page 121
Description of system components 8.3 Operator panel with display PROFINET: Not only information about IP configuration, device name, MAC address, PROFIsafe address but also settings about the status of communication and the response of SIMOCODE pro if communication failures are displayed. These are the most important menus by way of example: ●...
Description of system components 8.3 Operator panel with display 8.3.3.8 Displays the current status of all device I/Os The "Device I/Os" menu item provides a complete overview of the current status of all inputs and outputs of the basic unit as well as any connected expansion modules. The type of status information displayed is directly dependent upon the SIMOCODE pro hardware configuration.
Page 123
Description of system components 8.3 Operator panel with display Digital module 1 is DM-F PROFIsafe Possible only if digital module 1 is "PROFIsafe", an OPD as from version *E04* and a SIMOCODE pro V PB / PN basic unit (PB as from product version *E07*) is used. ●...
Description of system components 8.3 Operator panel with display 8.3.3.9 Parameters You can set the following parameters using the operator panel with display: Parameters Range Note Overload protection → current settings Possible only if a current measuring module is configured Current setting Is1 0.00 - 9,999.00 A Current setting Is2...
Page 125
Description of system components 8.3 Operator panel with display Parameters Range Note Trip level 0.00 - 40.00 A Warning level 0.00 - 40.00 A 0/4-20 mA monitoring → 0/4-20 mA limits Possible only if analog module 1 and/or 2 is configured Analog module 1 - trip level 0 - 255...
Description of system components 8.3 Operator panel with display Proceed as follows to change a parameter: ● Choose menu item "Parameters" from the main menu ● Then choose the parameter to be changed in the relevant submenu ● Click OK to confirm the selection You can now change the value with the ▲...
Page 127
Description of system components 8.3 Operator panel with display Profiles Enables selection of the display profiles for the main display. If a defined profile is no longer supported by SIMOCODE pro, for example, due to a changed hardware configuration, the start display will be shown instead of the default main display: ●...
Page 128
Description of system components 8.3 Operator panel with display See Section Read and adapt main display (Page 112). NOTICE 1) Temperatures The temperature from temperature module 1 is always shown in this display profile. The temperature from temperature module 2 is not shown in this profile. Voltage display Switch voltage display: Defines whether "phase voltages"...
Description of system components 8.3 Operator panel with display 8.3.3.11 Resetting, testing and parameterizing via commands The "Commands" menu item contains all commands relating to SIMOCODE pro, e.g. for testing the feeder, resetting after tripping and/or transferring parameters into the memory module or into SIMOCODE pro.
Description of system components 8.3 Operator panel with display 8.3.3.12 Displaying all pending messages This menu item provides an overview of all pending status information. A precise description of the pending status information messages can be found in Chapter Alarms, faults, and system events - error handling (Page 291).
Description of system components 8.3 Operator panel with display 8.3.3.16 Reading the device's internal event memory The "Event memory" menu item enables access to the SIMOCODE pro's internal event memory. The two most recent events "DM-F enabling circuit closed" and "DM-F enabling circuit open"...
Description of system components 8.3 Operator panel with display 8.3.3.17 Identification of the motor feeder and the SIMOCODE pro components In the "Identification" menu item, you will find detailed information about the used SIMOCODE pro hardware components, e.g. hardware and firmware versions. This dialog box also enables identification of the motor feeder via a plant identifier stored in SIMOCODE pro, as well as a request for the location designation and display of the device's internal comment.
Description of system components 8.4 Current measuring modules (IM) for the SIMOCODE pro C, SIMOCODE pro S, and SIMOCODE pro V device series Current measuring modules (IM) for the SIMOCODE pro C, SIMOCODE pro S, and SIMOCODE pro V device series Current measuring modules can be used together with all device series.
Page 134
Description of system components 8.4 Current measuring modules (IM) for the SIMOCODE pro C, SIMOCODE pro S, and SIMOCODE pro V device series The current measuring module is connected to the basic unit via a connecting cable, which also supplies the power. Current measuring modules up to 100 A are suitable for standard rail mounting or can be fixed directly to the mounting plate using additional push-in lugs.
Description of system components 8.5 Current / voltage measuring modules (UM, UM+) for the SIMOCODE pro V High Performance device series Current / voltage measuring modules (UM, UM+) for the SIMOCODE pro V High Performance device series Variants Two device generations of the current / voltage measuring modules are available: 1st generation: UM, MLFB ending in 000 (e.g.
Page 136
Description of system components 8.5 Current / voltage measuring modules (UM, UM+) for the SIMOCODE pro V High Performance device series The diagram below shows the various current / voltage measuring modules: Figure 8-31 Variants of current / voltage measuring modules Wiring: The current / voltage measuring modules are connected to the basic unit via a connecting cable, which also supplies the power.
Page 137
). The relevant settings are made via the "Internal ground fault" function block. See Chapter "Ground fault monitoring" in the manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958). The accuracy of measured values has been improved. The following measuring accuracies are possible in the rated ranges: ●...
Page 138
The measured values with the accuracy figures mentioned can be found in data record 94 - Measured values (from byte position 132) and in data record 95 - Statistics data in the manual SIMOCODE pro - Communication (https://support.industry.siemens.com/cs/ww/en/view/109743960). Note Frequency measurement For a correct frequency measurement, the voltage measurement must be connected.
Page 139
The tripping characteristics can be found in Chapter "Overload protection" in the manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958). The trip classes have been extended with trip class 7. Thus, if required, finer coordination of the trip classes can be chosen in the lower range (if, for example, there is a wish to approximate to the characteristic curve of the class 10 current measuring modules).
Page 140
/ voltage measuring modules. • The new measured values stored as float in the data records are not entered (see manual SIMOCODE pro - Communication (https://support.industry.siemens.com/cs/ww/en/view/109743960) → Tables, data records - definitions"). The following restrictions still have to be observed:...
Page 141
Description of system components 8.5 Current / voltage measuring modules (UM, UM+) for the SIMOCODE pro V High Performance device series See also Configuration information for SIMOCODE pro V when using an older basic unit (Page 155) for more information. NOTICE Rated motor current is in the range from 2.4 - 2.99 A and a 1st generation current / voltage measuring module with the 2.4 - 25 A measuring range is used...
Description of system components 8.6 Decoupling module (DCM) for 1st generation current/voltage measuring modules (e.g. 3UF711.1AA000) Decoupling module (DCM) for 1st generation current/voltage measuring modules (e.g. 3UF711.1AA000) Function of the decoupling module When measuring voltage and power with SIMOCODE pro in ungrounded networks, each current / voltage measuring module must have a decoupling module connected upstream in series at the system interface.
Page 143
Description of system components 8.6 Decoupling module (DCM) for 1st generation current/voltage measuring modules (e.g. 3UF711.1AA000) Using the decoupling module in different networks A decoupling module may be required when using a voltage measuring module, especially for the following networks: ●...
Page 144
Description of system components 8.6 Decoupling module (DCM) for 1st generation current/voltage measuring modules (e.g. 3UF711.1AA000) The tables below show decoupling module requirements for different grounding systems and system configurations (star systems, delta systems, and single-phase systems): Star networks: Table 8- 1 Decoupling module requirements for star networks Star configuration Network configuration...
Page 145
Description of system components 8.6 Decoupling module (DCM) for 1st generation current/voltage measuring modules (e.g. 3UF711.1AA000) Delta configurations Table 8- 2 Decoupling module requirements for delta networks Delta network Network configuration Decoupling module Note required? 3-wire, delta, one phase Parameter "Voltage grounded display →...
Description of system components 8.7 Spectrum of the expansion modules Spectrum of the expansion modules Expansion modules are provided as optional additions for the SIMOCODE pro S and pro V device series. The following expansion modules are available: ● Digital modules (DM) (Page 147) ●...
You can set a debouncing time for the digital module inputs if required (see Chapter "Digital module inputs" in the manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958)). Power supply to the inputs: See Chapter Wiring basic units, expansion modules and the decoupling module (Page 195).
LEDs for DM-F device diagnostics: See Chapter Technical data (Page 329) and / or Manual SIMOCODE pro fail-safe digital modules (https://support.automation.siemens.com/WW/view/en/50564852). "TEST/RESET" DM-F button, setting the DM-F DIP switches, DM-F system interfaces: See Manual SIMOCODE pro fail-safe digital modules (https://support.automation.siemens.com/WW/view/en/50564852).
Page 149
Safety-related functions and additional information on fail-safe digital modules can be found in the following documentation: ● Manual SIMOCODE pro fail-safe digital modules (https://support.automation.siemens.com/WW/view/en/50564852) ● Operating Instructions "Fail-safe Digital Module DM-F Local" ● Operating Instructions "Fail-safe Digital Module DM-F PROFIsafe"...
Page 150
Description of system components 8.9 Fail-safe digital module (DM-F) From a non-safety-related perspective, the DM-PROFIsafe module comprises: Table 8- 6 Inputs, outputs and voltage supply to the digital module Fail-safe PROFIsafe (DM-F PROFIsafe) Inputs Power supply Outputs 4 non-safety-related digital 24 V DC 2 non-safety-related monostable inputs...
Description of system components 8.10 Analog module (AM) 8.10 Analog module (AM) By means of the analog module, the SIMOCODE pro V High Performance basic units can be optionally expanded by analog inputs and outputs (0/4 mA to 20 mA). This makes it possible to detect and monitor any process variables that can be mapped onto a 0/4 to 20 mA signal.
Use of this ground-fault module requires a SIMOCODE pro V PB basic unit, with at least product version *E10* (from 09/2013). Detailed information on ground-fault monitoring: See Chapter "Monitoring functions" in the manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958). SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Description of system components 8.12 Temperature module (TM) 8.12 Temperature module (TM) The temperature module offers the option of expanding the SIMOCODE pro V/pro S device series by an analog temperature monitoring system. In addition to the thermistor monitoring system for the basic units, up to 3 analog sensor measuring circuits (in two or three-wire systems) can be connected, the temperatures in the 3 sensor measuring circuits can be measured, and the highest temperature in all sensor measuring circuits can be determined.
Description of system components 8.13 Multifunction module 8.13 Multifunction module The multifunction module is the expansion module of the SIMOCODE pro S device series with the following functions: ● Digital module function with four digital inputs and two monostable relay outputs ●...
Description of system components 8.14 Configuration information for SIMOCODE pro V when using an older basic unit 8.14 Configuration information for SIMOCODE pro V when using an older basic unit Note Restrictions for the SIMOCODE pro V device series The restrictions mentioned here apply to the SIMOCODE pro V High Performance device series with the following product versions: •...
Page 156
Description of system components 8.14 Configuration information for SIMOCODE pro V when using an older basic unit Maximum configuration with expansion modules Table 8- 7 Maximum configuration with expansion modules when using an operator panel/operator panel with display, a 1st generation current/voltage measuring module and a decoupling module for SIMOCODE pro V PB basic units (3UF7010-1A.00-0) with a 24 V DC or 110 V - 240 V AC/DC supply SIMOCODE pro basic unit SIMOCODE pro basic unit...
Page 157
Description of system components 8.14 Configuration information for SIMOCODE pro V when using an older basic unit Table 8- 8 Maximum configuration with expansion modules when using an operator panel/operator panel with display, a 2nd generation current/voltage measuring module and a SIMOCODE pro V-PB basic unit with a product version earlier than E15 / SIMOCODE pro V Modbus basic unit with product version E01 SIMOCODE pro basic unit SIMOCODE pro basic unit...
Description of system components 8.15 Configuration notes for use of a SIMOCODE pro V MR and SIMOCODE pro V EIP basic unit 8.15 Configuration notes for use of a SIMOCODE pro V MR and SIMOCODE pro V EIP basic unit The following expansion modules are not supported: ●...
Compartment identification Applications and advantages of compartment identification The compartment identification described in this chapter is mainly used in application in which SIMOCODE pro is used in a withdrawable motor control center (MCC). In withdrawable motor control centers, all components belonging to the motor feeder are grouped together as one unit in a switchboard-specific enclosure.
Page 160
9.1 Applications and advantages of compartment identification Figure 9-1 Compartment identification CAUTION Basic units SIMOCODE pro C (3UF7000*) and basic units SIMOCODE pro V (3UF7010*) to E08, V3.0 These basic units do not support the initialization module and start with the internal parameters.
Page 161
Compartment identification 9.1 Applications and advantages of compartment identification The advantages of operation with a permanently installed initialization module in the switchboard: ● Device parameters and device addressing are automatically stored in the initialization module in the motor control center and loaded form this initialization module (initialized). ●...
● SIMOCODE pro V PN basic units ● SIMOCODE pro V EIP basic units. NOTICE Basic units SIMOCODE pro C (3UF7000*) and basic units SIMOCODE pro V (3UF7010*) to E08, V3.0 These basic units do not support the initialization module and start with the internal parameters.
Loading parameters from the initialization module into the SIMOCODE pro V basic units with an earlier product version Basic units SIMOCODE pro C (3UF7000*) and SIMOCODE pro V (3UF7010*) to E08, V3.0 do not detect the initialization module and ignore its parameters!
Page 164
Compartment identification 9.3 Operating compartment identification Saving parameters onto the initialization module If an initialization module is connected to a SIMOCODE pro basic unit, all parameters that are saved to the SIMOCODE basic unit, e.g. SIMOCODE ES (TIA Portal), are automatically copied into the initialization module.
Page 165
Compartment identification 9.3 Operating compartment identification Commands "Initialization module write protection on" command All contents of the initialization module are write-protected. This prevents any inadvertent changes to the contents of the initialization module and any parameter changes to the connected SIMOCODE pro basic unit. An inadvertent change of parameters for a motor feeder is prevented.
Page 166
Compartment identification 9.3 Operating compartment identification Messages You can check the states of the initialization module by the following events (in the ""Commissioning → Faults, warnings, event" dialog box of the "SIMOCODE ES (TIA Portal)" software: ● Initialization module write-protected ●...
Compartment identification 9.4 Mounting, wiring, interfaces, compartment identification Mounting, wiring, interfaces, compartment identification Mounting the initialization module in the switchboard Mounting the initialization module with the mounting lugs in the switchboard Figure 9-2 Mounting the initialization module Wiring the initialization module Unlike the other expansion components of the system, the initialization module does not have a connector.
Page 168
CAUTION SIMOCODE pro basic units with an earlier product version SIMOCODE pro C basic units (3UF7000*) and SIMOCODE pro V PB basic units (3UF7010*) up to E08, V3.0 do not support the initialization module and start with the internal parameters.
Page 169
Compartment identification 9.4 Mounting, wiring, interfaces, compartment identification Connecting the Y connecting cable to the basic unit and to the current measuring module or to the current / voltage measuring module ● Connect the connector in the middle of the Y connecting cable (1) on the basic unit ●...
During commissioning and service work, also heed the relevant "Initialization Module" Operating Instructions! You will find the operating instructions for SIMOCODE pro at Manuals/operating instructions (https://support.industry.siemens.com/cs/ww/en/ps/16027/man). Commissioning the initialization module Sequence for initial startup of a new SIMOCODE pro basic unit and a new initialization...
Compartment identification 9.6 Alarm, fault, and system events for compartment identification Alarm, fault, and system events for compartment identification Messages Table 9- 1 Alarm, fault, and system events Message Description Troubleshooting Initialization module write-protected The initialization module is completely Deactivate write protection of the write-protected.
Compartment identification 9.8 Technical data compartment identification Technical data compartment identification Technical data initialization module ● Order number (MLFB): 3UF7 902-0AA00-0 ● Ambient temperature: -25 ... +80 °C ● Rated insulation voltage: 300 V ● Rated operating voltage: 24 V. Technical data Y connecting cable ●...
Page 174
Compartment identification 9.8 Technical data compartment identification SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Accessories Accessories overview The following figure shows selected accessories: Figure 10-1 Accessories USB PC cable For device parameterization, for connecting a PC via its USB interface or serial interface to the system interface of a basic unit. Note PC cable variant For SIMOCODE pro V PN, a serial PC cable 3UF7940-0AA00-0 as from product version *E02* or a USB PC cable USB 3UF7941-0AA00-0 can be used.
Page 176
Note Memory module type • The SIMOCODE pro C and SIMOCODE pro V PB basic units up to product version *E08* only support the 3UF7900* memory module. • The SIMOCODE pro S, SIMOCODE pro V MR and SIMOCODE pro V PB basic units support all memory modules as from product version *E09*.
Page 177
Accessories Door adapter The door adapter is used to facilitate access to the SIMOCODE pro system interface, for example via the front panel, to ensure fast parameterization. System interface cover The system interface cover helps to protect and/or seal the system interfaces against the ingress of dirt.
Page 178
Accessories SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
3UF50 compatibility mode 11.1 Application, Win-SIMOCODE-DP converter Application of 3UF50 compatibility mode 3UF50 compatibility mode is used whenever a SIMOCODE-DP device is to be replaced with a SIMOCODE pro V PB device without modification of the configuration. In 3UF50 compatibility mode, you can operate a SIMOCODE pro V PB basic unit with a 3UF50 configuration.
3UF50 compatibility mode 11.2 Diagram of send and receive data 11.2 Diagram of send and receive data The following table shows the send and receive data in compatibility mode: Table 11- 1 "Receive" configuration Receive Basic type 1, Basic type 1, Basic type 2, Basic type 2, Basic type 3,...
3UF50 compatibility mode 11.3 Diagram of diagnostics data 11.3 Diagram of diagnostics data The following table shows the diagnostics data in the 3UF50 compatibility mode: Table 11- 3 Diagram of the diagnostics data in the 3UF50 compatibility mode Byte. Setup 3UF50 - Byte.
Page 182
3UF50 compatibility mode 11.3 Diagram of diagnostics data Byte. Setup 3UF50 - Byte. Setup 3UF50 - Equivalent in SIMOCODE pro V Device-specific diagnostics Device-specific diagnostics according to DP standard according to DPV1 SIMOCODE DP SIMOCODE DP Warning: I1 response level 12.4 Warning: I1 response level Warning - Warning level I <...
Page 183
3UF50 compatibility mode 11.3 Diagram of diagnostics data Byte. Setup 3UF50 - Byte. Setup 3UF50 - Equivalent in SIMOCODE pro V Device-specific diagnostics Device-specific diagnostics according to DP standard according to DPV1 SIMOCODE DP SIMOCODE DP 12.1 Trip: OPO 15.1 Trip: OPO Fault - Operational Protection Off (OPO)
Page 184
3UF50 compatibility mode 11.3 Diagram of diagnostics data SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.1 Mounting 12.1.1 Mounting basic units, expansion modules, and the decoupling module You can attach these system components as follows: ● Snap-on mounting onto a 35 mm standard mounting rail, without tools ● Snap-on mounting of basic units (no tools required) onto current measuring modules of 45 mm and 55 mm in width (up to 100 A or 115 A (UM+))) with integrated standard mounting rail ●...
Page 186
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.1 Mounting Figure 12-1 Mounting basic unit, expansion modules or the decoupling module, SIMOCODE pro C/V SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 187
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.1 Mounting Figure 12-2 Mounting of basic unit and multifunction module, SIMOCODE pro S SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.1 Mounting 12.1.2 Mounting the bus terminal Sequence for mounting the bus terminal on the SIMOCODE pro S basic unit Proceed as follows: Table 12- 1 Mounting the bus terminal on the SIMOCODE pro S basic unit Step Description Screw the two PROFIBUS cables to the bus terminal as shown...
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.1 Mounting 12.1.3 Mounting of digital modules DM-F Local and DM-F PROFIsafe See Manual SIMOCODE pro fail-safe digital modules (https://support.automation.siemens.com/WW/view/en/50564852), Chapter "Mounting and connection." 12.1.4 Mounting of current measuring modules You can attach these system components as follows: ●...
Page 190
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.1 Mounting Figure 12-4 Mounting the current measuring modules SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.1 Mounting 12.1.5 Mounting the current / voltage measuring modules You can attach these system components as follows: ● Current / voltage measuring modules up to 115 A: Standard mounting rail mounting or screw attachment with mounting lugs (article number: 3RV2928-0B) and screws for mounting on a level surface.
Page 192
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.1 Mounting Figure 12-6 Mounting the current / voltage measuring modules UM with through-hole technology Figure 12-7 Mounting the current / voltage measuring modules UM with bus connection system SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.1 Mounting 12.1.6 Mounting of the operator panel and operator panel with display The operator panels are designed for installation in the front panels of motor control centers, for example, or in control cabinet doors. To install, proceed as follows: Table 12- 2 Sequence for installing the operator panel / operator panel with display...
Page 194
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.1 Mounting Figure 12-9 Mounting the operator panel with display WARNING Tightening torque of the screws To ensure that the panel will function correctly and is sealed to comply with IP54, the tightening torque of the screws provided must not be set too high when mounting and the seal must be properly fitted.
Figure 12-10 Removable terminals for basic units, expansion modules, or the decoupling module, SIMOCODE pro C/V Note The removable terminals are mechanically coded and will only fit in a certain position!
Page 196
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Figure 12-11 Removable terminals for SIMOCODE pro C and pro V basic units Figure 12-12 Removable terminals for basic unit and multifunction module, SIMOCODE pro S SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 197
Table 12- 3 Conductor cross sections, stripped lengths, and tightening torques of the cables for the basic units SIMOCODE pro C and pro V Removable terminals Screwdriver Tightening torque PZ2 / Ø...
Page 198
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Table 12- 4 Conductor cross sections, stripped lengths, and tightening torques of the cables for the basic unit SIMOCODE pro S Removable terminals Screwdriver Tightening torque PZ1 / Ø 4.5 mm TORQUE: 5.2 to 7.0 lb.in 0.6 to 0.8 Nm...
Page 199
The following table show the assignment of the removable terminals of the SIMOCODE pro C/pro V PB basic units: Table 12- 5 Assignment of the removable terminals, SIMOCODE pro C / pro V PB basic units Terminal Assignment Upper terminals...
Page 200
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Assignment of the removable terminals, SIMOCODE pro S basic units The following table shows the assignment of the removable terminals of the SIMOCODE pro S basic unit: Table 12- 6 Assignment of the removable terminals, SIMOCODE pro S basic unit Terminal Assignment...
Page 201
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Pin assignment for SIMOCODE pro V PN GP basic unit The following table shows the pin assignment of the removable terminals: Table 12- 7 Pin assignments of the removable terminals of the basic unit Terminal Assignment Upper terminals...
Page 202
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Pin assignment for SIMOCODE pro V PN / EIP basic units The following table shows the pin assignment of the removable terminals: Table 12- 8 Pin assignments of the removable terminals of the basic unit Terminal Assignment Upper terminals...
Page 203
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Power supply to the inputs of the basic unit There are three possibilities for powering the inputs: a): 24 V DC internal b): 24 V DC external. Input 3 is the reference potential, i.e. three inputs are available. c): 24 V DC external.
Page 204
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Wiring sequence of the removable terminal of the SIMOCODE pro C/V basic units Proceed as follows: Table 12- 9 Wiring of the removable terminals of the SIMOCODE pro C/V basic units...
Page 205
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Wiring sequence of the PROFIBUS cable for SIMOCODE pro S basic units Proceed as follows: Table 12- 10 Wiring of the removable terminals on the basic units Step Description Insulate the PROFIBUS cable as shown below. Screw the SPE cable to the bus terminal as shown below.
Page 206
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Figure 12-15 Wiring sequence of the PROFIBUS cable for SIMOCODE pro S basic units SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 207
Connection examples of SIMOCODE pro C/V/S basic units Figure 12-16 Connection example of SIMOCODE pro C/V basic units SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 208
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Figure 12-17 Connection example SIMOCODE pro S basic unit Note Only three inputs can be used With an external 24 V DC supply, only three inputs can be used (see "Power supply to the inputs of the basic unit" above). Note Baud rates PROFIBUS DP Baud rates up to 1.5 Mbits are possible via bus terminals A/B.
Page 209
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Connection examples for SIMOCODE pro V PN / pro V EIP basic units Figure 12-18 Connection examples for SIMOCODE pro V PN / pro V EIP basic units SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 210
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Terminal assignment of the digital module The following table shows the assignment of the removable terminals: Table 12- 12 Pin assignment of the removable terminals of the digital module Terminal Assignment Upper terminals Common potential for relay outputs 1...
Page 211
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Power supply to the digital module inputs There are two possibilities for powering the inputs: a) Digital module with 24 V DC input supply b) Digital module with 110 to 240 V AC / DC input supply Figure 12-19 Power supply to the digital module inputs Digital module connection example Figure 12-20 Digital module connection example...
Page 212
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Terminal assignment of the multifunction module Table 12- 13 Assignment of the removable terminals, multifunction module Terminal Assignment Upper terminals Digital input IN1 Digital input IN2 Digital input IN3 System shielding Ground for IN1 to IN4 Digital input IN4 Terminal 1, 3UL23 residual current...
Page 213
Figure 12-21 Connection example for multifunction module Safety information on installing the 3UL23 residual current transformer: See Chapter 14.2.5 in the Manual 3UG4/3RR2 Monitoring Relay (https://support.industry.siemens.com/cs/ww/en/view/54397927). NOTICE Routing the connecting cables / using shielded cables To avoid interference injection, which could result in incorrect measurements, route these connecting lines parallel and twisted, if possible, or use shielded cables.
Page 214
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Terminal assignment of the ground-fault module The following table shows the assignment of the removable terminals: Table 12- 14 Terminal assignment of the removable terminals of the ground-fault module Terminal Assignment Upper terminals Input C1 residual current transformer...
Page 215
The output signal of the transformers 3UL22/3UL23 is connected to terminals C1 and C2 of the corresponding ground-fault module. Information on installing the residual current transformer 3UL23: See Manual 3UG4/3RR2 Monitoring Relay (https://support.industry.siemens.com/cs/ww/en/view/54397927), Chapter 13.2.5. NOTICE Routing the connecting cables / using shielded cables To avoid interference injection, which could result in incorrect measurements, route these connecting lines parallel and twisted, if possible, or use shielded cables.
Page 216
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Terminal assignment of the temperature module The following table shows the assignment of the removable terminals: Table 12- 15 Pin assignment of the removable terminals of the temperature module Terminal Assignment Upper terminals Input T3, temperature sensor 1...
Page 217
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Temperature module connection example Figure 12-23 Temperature module connection example SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 218
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Terminal assignment of the analog module The following table shows the assignment of the removable terminals: Table 12- 16 Pin assignment of the removable terminals of the analog module Terminal Assignment Upper terminals Analog input IN1+...
Page 219
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Analog module connection example Figure 12-24 Analog module connection example SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 220
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Terminal assignment of the decoupling module The following table shows the assignment of the removable terminals: Table 12- 17 Pin assignment of the removable terminals of the decoupling module Terminal Assignment Upper terminals —...
12.2.2 Wiring digital modules DM-F Local and DM-F PROFIsafe Safety guidelines See Manual Fail-safe Digital Modules SIMOCODE pro (https://support.automation.siemens.com/WW/view/en/50564852), Chapter "Mounting and connection." WARNING Loss of safety function is possible For the 24 V DC power supply, always use an SELV or PELV power supply unit! Note Surge suppressors are required for inductive loads.
Page 222
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Terminal assignment for digital module DM-F Local The following table shows the pin assignment of the removable terminals: Table 12- 18 Terminal assignment of the removable terminals of the digital module DM-F Local, 24 V DC version and 110 to 240 V UC version.
Page 223
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Terminal assignment for digital module DM-F PROFIsafe Table 12- 19 Terminal assignment of the removable terminals of the digital module DM-F PROFIsafe, 24 V DC version and 110 to 240 V UC version. Terminal Assignment Upper terminals...
Page 224
This ensures safe tripping in the event of a fault. Figure 12-26 Connection example for "DM-F Local with cross-circuit detection, 2 NCs, 2 channels, monitored start" For further connection examples: See Manual Fail-safe Digital Modules SIMOCODE pro (https://support.automation.siemens.com/WW/view/en/50564852). SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 225
Always install the prescribed fuse protection. This ensures safe tripping in the event of a fault. Figure 12-27 Block diagram of DM-F PROFIsafe Connection examples fail-safe digital module DM-F See Manual Fail-safe Digital Modules SIMOCODE pro (https://support.automation.siemens.com/WW/view/en/50564852). SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
● Through-hole connection up to 200 A: The cables of the three phases are passed through the feed-through openings. ● Bus connection system from 20 A to 630 A, also for direct connection to Siemens contactors. The following table shows the various current measuring modules:...
Page 227
Please note the information in the Operating Instructions. You will also find the Operating Instructions for SIMOCODE pro at Operating instructions (https://support.industry.siemens.com/cs/ww/en/ps/16027/man) SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Select the appropriate current / voltage measuring module according to the motor current. ● Through-hole connection up to 200 A: The cables of the three phases are passed through the feed-through openings. ● Bus connection system from 20 A to 630 A, also for direct connection to Siemens contactors. SIMOCODE pro...
Page 229
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting The following table shows the various current / voltage measuring modules: Table 12- 21 Current / voltage measuring modules 1) Current / voltage measuring module UM Version 2) 2nd generation current / voltage measuring module UM+ 3) 2nd generation current / voltage measuring module UM+ for ATEX dry-running protection 1) 3UF7110-1AA00-0;...
Page 230
/ voltage measuring module and correct routing direction! Please note the information in the Operating Instructions. You will also find the Operating Instructions for SIMOCODE pro at Operating instructions (https://support.industry.siemens.com/cs/ww/en/ps/16027/man) SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 231
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Removable terminals The following tables show conductor cross-sections, stripped lengths, tightening torques of conductors and pin assignments of the removable terminals of the current / voltage measuring modules: Table 12- 22 Conductor cross-sections, stripped lengths, tightening torques of conductors of the 2nd generation 45 mm and 55 mm current / voltage measuring modules Removable Screwdriver...
Page 232
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Table 12- 24 Conductor cross-sections, stripped lengths, tightening torques of conductors of the 1st generation current / voltage measuring modules Removable Screwdriver Tightening torque terminals PZ2 / Ø 5 to 6 mm TORQUE: 7 to 10.3 lb.in 0.8 to 1.2 Nm...
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting 12.2.5 Measuring current with an external current transformer (interposing transformer) Functional principle SIMOCODE pro can be operated with external current transformers. The secondary cables of the current transformer are looped through the three feed-through openings of the current measuring module, and short-circuited.
Page 234
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Requirements for an interposing current transformer ● Secondary current: 1 A ● Frequency: 50 Hz/60 Hz ● Transformer rating: Recommended ≥ 2.5 VA, depending on the secondary current and cable length ●...
Page 235
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.2 Wiring, connecting Example 2 ● 3UF1868-3GA00 current transformer: – Primary current: 205 A at nominal load – Secondary current: 0.25 A ● SIMOCODE pro with 3UF7100-1AA00-0 current measuring module, current setting 0.3 to 3 A. This means: –...
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.3 System interfaces 12.3 System interfaces 12.3.1 Information about the system interfaces Information about the system interfaces ● SIMOCODE pro system components are connected to each other via the system interfaces. The system interfaces are provided on the front and bottom of the devices. ●...
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.3 System interfaces WARNING Hazardous voltage Connect the system interfaces only when they are fully de-energized! See also Closing the system interfaces with the system interface cover (Page 247) 12.3.2 System interfaces on basic units, expansion modules, decoupling module, current measuring modules and current / voltage measuring modules Examples of connection of system components to the system interface and system structure Close system interfaces not in use with the system interface cover (see Closing the system...
Page 238
12.3 System interfaces The following figure shows an example for SIMOCODE pro C/V of connecting system components to the system interfaces: Figure 12-32 Example of system interfaces - SIMOCODE pro C/V with system component IM, UM+ SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 239
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.3 System interfaces The following figure shows an example for SIMOCODE pro S of connecting system components to the system interfaces: Figure 12-33 Example of system interface - SIMOCODE pro S The following figure shows an example of a SIMOCODE pro V system installation: Figure 12-34 Example of SIMOCODE pro V installation SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 240
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.3 System interfaces The following figure shows an example of a SIMOCODE pro S system installation: Figure 12-35 Example of SIMOCODE pro S installation SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 241
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.3 System interfaces Sequence for connecting cables to the system interface Proceed as follows: Table 12- 25 Connecting to the system interface Step Description Place the plug in the plug shaft, keeping it is as straight as possible. Ensure the locking mechanisms of the connector slot audibly snap onto the connector enclosure.
Observe the color coding of the connecting cable (see diagram)! 12.3.3 System interfaces on the digital modules DM-F Local and DM-F PROFIsafe See System Manual SIMOCODE pro fail-safe digital modules (https://support.automation.siemens.com/WW/view/en/50564852), Chapter "Mounting and connection." SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.3 System interfaces 12.3.4 System interfaces on the operator panel and the operator panel with display Versions and safety notices The operator panel has two system interfaces: ● Rear side system interface. This is not normally accessible on an integrated operator panel.
Page 244
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.3 System interfaces Sequence for connecting cables to the system interface of the operator panel and the operator panel with display Proceed as follows: Table 12- 26 Connecting system components to the system interface Step Description Place the plug in the plug shaft, keeping it is as straight as possible.
Page 245
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.3 System interfaces Figure 12-37 Sequence for connecting cables to the system interface of the operator panel SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 246
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.3 System interfaces Figure 12-38 Sequence for connecting cables to the system interface of the operator panel with display SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.3 System interfaces 12.3.5 Closing the system interfaces with the system interface cover Examples of closing the system interface with the system interface cover Figure 12-39 Examples of closing the system interface with the system interface cover WARNING System interface on the operator panels (degree of protection IP54): To ensure degree of protection IP 54...
Note The 9-way SUB-D connection is an alternative to the A / B terminals! Sequence for connecting PROFIBUS DP to the SIMOCODE pro C and SIMOCODE pro V basic units Proceed as follows: Table 12- 27 Sequence for connecting PROFIBUS DP to the basic unit...
Ethernet connector Connect using only Industrial Ethernet connectors, e.g. • Siemens IE FC RJ45 PLUG 180 2x2, RJ45 connector (10/100MBIT/S) with robust metal housing and Fast Connect connection method, for IE FC Cable 2x2 180° cable outlet, order number 6GK1901-1BB10-2AA0 or •...
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.3 System interfaces 12.3.8 Modbus RTU connection to the SIMOCODE pro device Connecting Modbus RTU to the SIMOCODE pro V Modbus basic unit Modbus RTU can be connected to the SIMOCODE pro V basic unit both via the connecting terminals as well as via the sub-D connector.
Page 251
SIMATIC Industrial Communication 6ES7972* RS485 connectors can be used to connect Modbus RTU to the sub-D interface thanks to the identical pin assignments to PROFIBUS DP (see RS485 bus connector (https://mall.industry.siemens.com/mall/en/WW/Catalog/Products/9300041?tree=CatalogTre e) in the Industry Mall). NOTICE Using the PROFIBUS DP connector When the PROFIBUS DP connector is used, the bus terminator does not conform to the Modbus specification.
Configuration guidelines on PROFIBUS DP Definition The key data contained in this chapter is valid for Siemens products and cables. PROFIBUS User Organization (PNO) installation guidelines In the case of electric PROFIBUS networks, note also the PROFIBUS DP / FMS installation guidelines defined by the PROFIBUS user organization.
Page 253
Mounting, wiring, connecting, system interfaces, configuration guidelines 12.4 Configuration guidelines Application of bus termination modules The 3UF1900-1K.00 bus termination module is primarily intended for use in MCC motor feeders. It provides correct bus termination, even when MCC plug-in units have been removed.
● PROFINET commissioning Checklist version: 1.01 Order No.: 8.091 Language: German For an overview of the structure and configuration of Industrial Ethernet networks with SIMATIC NET: See also "Industrial Ethernet Networking Manual" system manual (https://support.automation.siemens.com/WW/view/en/27069465) SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
3ZX1012-0UF76-1AA1 Current measuring module 3ZX1012-0UF71-1AA1 Current / voltage measuring module 3ZX1012-0UF71-1BA1 Door adapter 3ZX1012-0UF78-1AA1 Decoupling module 3ZX1012-0UF71-5BA1 Initialization module 3ZX1012-0UF70-2AA1 You will also find the Operating Instructions for SIMOCODE pro at Operating Instructions (https://support.industry.siemens.com/cs/ww/en/ps/16027/man) SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 256
Commissioning, service, troubleshooting 13.1 General information about commissioning and service Prerequisites The following prerequisites must be fulfilled for commissioning and servicing: ● SIMOCODE pro is already installed and wired ● The motor is switched off. Parameterization methods You can parameterize SIMOCODE pro as follows: ●...
Portal) software is installed. For this, connect the PC / PG to the system interface with the PC cable (see the figure below). Notice With SIMOCODE pro C use the system interface on the front and with SIMOCODE pro S use the right-hand system interface. Start SIMOCODE ES.
After the parameters have been transferred to the basic unit, the message confirming successful downloading appears under "Info → General" in the status window. Setting the PROFIsafe address on DM-F PROFIsafe See Chapter "Safety-related tripping" in the manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958). SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
No fault 13.2.1.4 Diagnostics via LED display on the modules DM-F Local or DM-F PROFIsafe See Manual Fail-safe Digital Modules SIMOCODE pro (https://support.automation.siemens.com/WW/view/en/50564852). SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Commissioning, service, troubleshooting 13.2 Commissioning 13.2.2 Commissioning with PROFINET 13.2.2.1 PROFINET commissioning steps Please observe the information in Chapter General information about commissioning and service (Page 255). To commission SIMOCODE pro, proceed as follows: Table 13- 6 Commissioning the basic unit Step Description Switch on the power supply.
A detailed description of these possible approaches can be found in the Chapter "Configuration of further properties of SIMOCODE pro V PN as IO Device" in the manual SIMOCODE pro - Communication (https://support.industry.siemens.com/cs/ww/en/view/109743960). Setting IP parameters and PROFINET device name with SIMOCODE ES (TIA Portal) via PC cable Proceed as follows:...
Page 262
The initial transfer of the device name must take place via the SIMOCODE pro system interface, since the device cannot be reached via PROFINET as address settings are missing. Setting the PROFIsafe address on DM-F PROFIsafe See Chapter "Safety-related tripping" in the manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958). SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Commissioning, service, troubleshooting 13.2 Commissioning 13.2.2.3 Setting the time manually after switch-on or recovery of the supply voltage Setting the time with SIMOCODE ES (TIA Portal) If the internal realtime clock of the devices is not automatically synchronized via NTP, you can make the setting manually with SIMOCODE ES.
Commissioning, service, troubleshooting 13.2 Commissioning 13.2.2.4 Diagnostics via LED display on the basic unit and on the operator panel (PROFINET) The basic unit and the operating panel have LEDs for displaying specific device states: Table 13- 8 Diagnostics via LED display Status Display Description...
Commissioning, service, troubleshooting 13.2 Commissioning 13.2.3 Commissioning with Modbus 13.2.3.1 Commissioning with Modbus RTU Commissioning sequence of the SIMOCODE pro V Modbus basic unit Table 13- 9 Commissioning sequence of the SIMOCODE pro V Modbus basic unit Step Description Switch on the power supply. In a fault-free state, the "Device" LED should light up green.
Page 266
The functional principle of SIMOCODE ES software is described in the online help. A "Getting Started" is available on the internet in a multimedia format to help you become more familiar with the software in the initial fundamental steps: Guided Tour (https://www.industry.siemens.com/topics/global/en/tia-portal/tia-portal- framework/tabcardpages/Pages/guided-tour.aspx) Device addressing As supplied, the default setting for the device address 126.
Page 267
Commissioning, service, troubleshooting 13.2 Commissioning Setting the Modbus RTU address with SIMOCODE ES (TIA Portal) Proceed as follows: Table 13- 11 Setting the Modbus RTU address with SIMOCODE ES (TIA Portal) Step Description Plug the PC cable into the system interface. Start SIMOCODE ES Select "Online →...
Page 268
Commissioning, service, troubleshooting 13.2 Commissioning ● Baud rate: The baud rate of SIMOCODE pro V Modbus can be set in the range from 0.3 - 57.6 kbps. The parameter setting "auto" activates automatic baud rate detection with which the device autonomously determines the setting selected by the controller. Automatic baud rate search encompasses baud rates in the range from 4.8 ...
Page 269
PLC, and the input "PLC/PCS monitoring" is set, "PLC/PCS in Run" is set to "1". You can find the further description of the "Watchdog" function block (PLC/PCS monitoring) in Chapter "Watchdog" (PLC/PCS monitoring) in the manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958). SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Commissioning, service, troubleshooting 13.2 Commissioning 13.2.4 Commissioning with EtherNet/IP 13.2.4.1 EtherNet/IP commissioning steps Please observe the information in Chapter General information about commissioning and service (Page 255). To commission SIMOCODE pro, proceed as follows: Table 13- 12 Commissioning the basic unit Step Description Switch on the power supply.
The selected application corresponds to the description in "Accessible devices" window opens the manual SIMOCODE pro - Application examples Click the "Start search" button • (https://support.industry.siemens.com/cs/ww/en/view/109743959) Select a station • Check the device configuration and adapt it to the actual •...
Page 272
Commissioning, service, troubleshooting 13.2 Commissioning Step Description Click the "Connect..." button. Open the "Ethernet parameters" dialog box in the parameter editor Select "Use BOOTP/DHCP" if the IP parameters are obtained from a DHCP server and assigned to the IO Device. If the DHCP mode is selected, SIMOCODE pro immediately receives an IP address if the DHCP server is available in the same network.
Commissioning, service, troubleshooting 13.2 Commissioning 13.2.4.3 Set the time manually after switch-on or recovery of the supply voltage Setting the timer with SIMOCODE ES If the internal realtime clock of the devices is not automatically synchronized via NTP, you can make the setting manually with SIMOCODE ES. To do so, follow these steps: Set the time manually after switch-on or recovery of the supply voltage Step...
Commissioning, service, troubleshooting 13.2 Commissioning 13.2.4.4 Diagnostics via LED display on the basic unit and on the operator panel with EtherNet/IP The basic unit and the operating panel have LEDs for displaying specific device states: Table 13- 14 Diagnostics via LED display Status Display Description...
Commissioning, service, troubleshooting 13.3 Service 13.3 Service 13.3.1 Preventive maintenance Preventive maintenance - general information Preventive maintenance is an important step towards avoiding faults and unforeseen costs. Industrial plants require regular professional maintenance, for example, to avoid production losses due to plant downtimes. Preventive maintenance ensures that all components are always kept in perfect working order.
Page 276
Commissioning, service, troubleshooting 13.3 Service Figure 13-6 Reading out statistical data SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Commissioning, service, troubleshooting 13.3 Service 13.3.2 Backing up and saving parameters Always save the parameters in the memory module or in a SIMOCODE ES file. This particularly applies if you replace a basic unit, or if you wish to transfer data from one basic unit to another.
Page 278
Commissioning, service, troubleshooting 13.3 Service Saving parameters from the basic unit to a SIMOCODE ES file Proceed as follows: Table 13- 17 Saving parameters to a SIMOCODE ES file Step Description Plug the PC cable into the system interface. Start SIMOCODE ES. Create a new project via "Create new project".
Note Please observe the information contained in the Operating Instructions! You will also find the Operating Instructions for SIMOCODE pro at Operating Instructions (https://support.industry.siemens.com/cs/ww/en/ps/16027/man) Note It is not necessary to detach the wiring from the removable terminals to replace the...
Page 280
Set the DIP switches for the PROFIsafe address according to the configuration in the F-controller (see Chapter "Configuring the DM-F PROFIsafe and integrating it into the fail-safe automation system" in the manual Manual Fail-safe Digital Modules SIMOCODE pro (https://support.automation.siemens.com/WW/view/en/50564852)). Switch on the power supply for the DM-F and the basic unit.
Page 281
Commissioning, service, troubleshooting 13.3 Service Replacing the current measuring module and the current/voltage measuring module WARNING Replacing current measuring modules and current/voltage measuring modules The main power for the feeder and the supply voltage for the basic unit must be switched off before replacing current measuring modules and current/voltage measuring modules.
Page 282
Commissioning, service, troubleshooting 13.3 Service Figure 13-7 Replacing current/voltage measuring modules Replacing a 1st generation current/voltage measuring module (UM) with a 2nd generation current/voltage measuring module (UM+) WARNING Replacing current measuring modules and current/voltage measuring modules The main power for the feeder and the supply voltage for the basic unit must be switched off before replacing current measuring modules and current/voltage measuring modules.
Commissioning, service, troubleshooting 13.3 Service The following table shows which 2nd generation current/voltage measuring module replaces a 1st generation current/voltage measuring module: 1st generation current/voltage measuring module 2nd generation current/voltage measuring module 3UF7110-1AA00-0, I = 0.3 to 3 A → 3UF7110-1AA01-0, I = 0.3 to 4 A 3UF7111-1AA00-0, I...
Page 284
Commissioning, service, troubleshooting 13.3 Service Figure 13-8 Mounting the operator panel adapter (1) Figure 13-9 Mounting the operator panel adapter (2) SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Commissioning, service, troubleshooting 13.3 Service WARNING Tightening torque of the screws To ensure that the panel will function correctly and is sealed to comply with IP54, the tightening torque of the screws provided must not be set too high when mounting and the seal must be properly fitted.
For example, the basic unit SIMOCODE pro V EIP. The current firmware versions can be obtained on request from Support Request (see Support Request (https://support.industry.siemens.com/My/ww/en/requests)). The firmware update can be performed with the SIMOCODE ES software (TIA Portal or with STEP 7).
Using the Support Request form in Online Support you can send your query directly to our Technical Assistance. After describing your query in a few guided steps, you will immediately be provided with possible suggestions for solving the problem. Support Request: Internet (https://support.industry.siemens.com/My/ww/en/requests) SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Commissioning, service, troubleshooting 13.4 Troubleshooting 13.4 Troubleshooting 13.4.1 Error buffer SIMOCODE pro has an error buffer in which the 21 most recent errors / faults and "Power - On" events are recorded with a time stamp. Time stamps are based upon the operating hours of the device (resolution 1 s), i.e.
Page 289
Commissioning, service, troubleshooting 13.4 Troubleshooting Example: Figure 13-10 Example of event logging using the SIMOCODE ES (TIA Portal) SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
The current DIP switch position of the "DM-F Local" and/or the "DM-F PROFIsafe" is displayed under "DIP switch position DM-F during the last event". See also Chapter "Data record 72 - Error buffer" in the manual SIMOCODE pro - Communication (https://support.industry.siemens.com/cs/ww/en/view/109743960). 13.4.2 Event memory...
Commissioning, service, troubleshooting 13.4 Troubleshooting 13.4.3 Alarms, faults, and system events - error handling Table 13- 26 Alarm, fault, and system events Event Description Troubleshooting Acknowledgment / Contactor Error (alphabetical) fault rectification control Analog An open circuit has occurred in Check the measured Reset module 1/2...
Page 292
Commissioning, service, troubleshooting 13.4 Troubleshooting Event Description Troubleshooting Acknowledgment / Contactor Error (alphabetical) fault rectification control Trip level The power factor cos phi has Please check the Tripped cos phi < undershot the trip level. Possible application that is being cause: The motor is being driven by the motor.
Page 293
Commissioning, service, troubleshooting 13.4 Troubleshooting Event Description Troubleshooting Acknowledgment / Contactor Error (alphabetical) fault rectification control Stalled The torque switch has activated Counter command Tripped The positioner may be • positioner before or without the respective "OPEN / blocked. limit switch. CLOSED!"...
Page 294
Commissioning, service, troubleshooting 13.4 Troubleshooting Event Description Troubleshooting Acknowledgment / Contactor Error (alphabetical) fault rectification control DM-FL The DM-F Local is in Complete the configuration "configuration mode"; the configuration (see manual mode "DEVICE" LED on the front of the "Fail-safe Digital Modules DM-F Local is illuminated yellow.
Page 295
Commissioning, service, troubleshooting 13.4 Troubleshooting Event Description Troubleshooting Acknowledgment / Contactor Error (alphabetical) fault rectification control Initialization The initialization module is Deactivate write protection module write- completely or partially write- of the initialization module protected, protected. parameter Reparameterization of changes not SIMOCODE pro is denied allowed because the initialization module...
Page 296
Commissioning, service, troubleshooting 13.4 Troubleshooting Event Description Troubleshooting Acknowledgment / Contactor Error (alphabetical) fault rectification control Module Supply voltage on the DM- Clear the fault; Tripped The terminals are not • supply F Local is too low or not present. reset wired properly voltage is not...
Page 297
Commissioning, service, troubleshooting 13.4 Troubleshooting Event Description Troubleshooting Acknowledgment / Contactor Error (alphabetical) fault rectification control Wrong SIMOCODE pro parameters are Please use the correct password protected by a password. An password for changing the attempt has been made to parameters.
Page 298
Commissioning, service, troubleshooting 13.4 Troubleshooting Event Description Troubleshooting Acknowledgment / Contactor Error (alphabetical) fault rectification control Status - The motor feeder has been The motor can only be cooling down switched off due to overload. switched on again after period active the cooling down period has expired.
Page 299
Commissioning, service, troubleshooting 13.4 Troubleshooting Event Description Troubleshooting Acknowledgment / Contactor Error (alphabetical) fault rectification control Temperature The temperature trip level has Check the temperature Tripped module 1/2 - been overshot. measuring station. trip level exceeded Temperature The temperature warning level Check the temperature module 1/2 - has been exceeded.
Page 300
Commissioning, service, troubleshooting 13.4 Troubleshooting Event Description Troubleshooting Acknowledgment / Contactor Error (alphabetical) fault rectification control Dry-running An error was detected in the 1. Repeat the teach-in protection – measured value acquisition of process. error the active power of the pump 2.
Page 301
1) See also "Error number" in Chapter "Data record 72 - Error buffer" in the manual SIMOCODE pro - Communication (https://support.industry.siemens.com/cs/ww/en/view/109743960). Note 2) Parameter block On devices in the as-delivered condition or after the factory settings have been restored, the...
Page 302
Commissioning, service, troubleshooting 13.4 Troubleshooting SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Safety and commissioning information for Ex areas 14.1 Motor protection functions (overload protection, thermistor protection) 14.1.1 Module integration The motor protection functions (overload protection, thermistor protection) are implemented in the following modules: ● 3UF70 basic units ● 3UF71 current / voltage measuring modules ●...
Safety and commissioning information for Ex areas 14.1 Motor protection functions (overload protection, thermistor protection) 14.1.2 Information and standards Information and standards Motor protection functions (overload protection, thermistor protection) The overload protection and the thermistor motor protection of the SIMOCODE pro system comply with the requirements for overload protection of explosion-proof motors of the following types of protection: ●...
Please observe the SIMOCODE pro Operating Instructions (enclosed with the devices). You can find the Operating Instructions for SIMOCODE pro listed in Chapter General information about commissioning and service (Page 255) or at Operating Instructions (https://support.industry.siemens.com/cs/ww/en/ps/16027/man) in the Industry Online Support. 14.1.3.2...
Page 306
Tripping conditions of the Ex e motor, selected: CLASS 10 when using a 3UF710* current measuring module The latest tripping characteristics for SIMOCODE pro can be found in the Industry Online Support (Tripping characteristics 3UF7 (https://support.industry.siemens.com/cs/search?search=3UF7&type=Characteristic&lc=en- WW)). SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Safety and commissioning information for Ex areas 14.1 Motor protection functions (overload protection, thermistor protection) NOTICE Tripping characteristic The type of tripping characteristic is dependent on the configured measuring module. If a 3UF711*-1AA00-0 1st generation current / voltage measuring module is configured in a parameter assignment, although a 3UF711*-1AA01-0 2nd generation current / voltage measuring module is used, then the tripping characteristic remains that of the 1st generation current / voltage measuring module.
Safety and commissioning information for Ex areas 14.1 Motor protection functions (overload protection, thermistor protection) Depending on the number of sensors, the following tripping and restart temperatures will result based on the TNF (rated response temperature of the sensor): Table 14- 1 Tripping and restart temperatures Tripping temperature Restart temperature...
Safety and commissioning information for Ex areas 14.1 Motor protection functions (overload protection, thermistor protection) 14.1.3.5 Short-circuit protection for type of coordination 2 according to IEC 60947-4-1 Short-circuit protection must be carried out by separately arranged overcurrent protection devices. NOTICE Fuse protection of the contactor for type of coordination 2 When combining with other contactors, observe the respective maximum fuse protection of the contactor for type of coordination 2.
Page 310
Safety and commissioning information for Ex areas 14.1 Motor protection functions (overload protection, thermistor protection) Test phases ● Phase 1: Hardware test / lamp test (0 to 2 s): The hardware (e.g. the thermistor electronics) is tested, all LEDs and displays are activated, including the lamp control.
WARNING Safety information for DM-F Local and DM-F PROFIsafe fail-safe digital modules Pay attention to the safety notes in the Manual Fail-safe Digital Modules SIMOCODE pro (http://support.automation.siemens.com/WW/view/en/50564852). CAUTION Using relay outputs for the protection function For the protection function, only the relay outputs of the 3UF70 basic unit, of a monostable...
You can find the Operating Instructions for SIMOCODE pro listed in Chapter General information about commissioning and service (Page 255) or at Operating Instructions (https://support.industry.siemens.com/cs/ww/en/ps/16027/man) in the Industry Online Support. SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
14.1 Motor protection functions (overload protection, thermistor protection) 14.1.6 Further information You will find further information on the Internet: ● Internet (https://www.siemens.com/simocode) ● Information and Download Center (https://www.siemens.com/sirius/infomaterial) ● Product Information System (ProdIS) (https://support.industry.siemens.com/cs/ww/en/ps) ● Service and support (https://support.industry.siemens.com/My/ww/en/requests) ● ATEX (https://www.siemens.com/sirius/atex) ● Certificates (https://support.industry.siemens.com/cs/ww/en/ps/16027/cert)
Safety and commissioning information for Ex areas 14.2 Dry-running protection for centrifugal pumps by active power monitoring 14.2 Dry-running protection for centrifugal pumps by active power monitoring 14.2.1 Module integration The function "dry-running protection for centrifugal pumps by means of active power monitoring"...
Page 315
Safety and commissioning information for Ex areas 14.2 Dry-running protection for centrifugal pumps by active power monitoring NOTICE Overall ignition protection concept According to the overall ignition protection concept for the centrifugal pump, further independent monitoring devices may be necessary, depending on the requirement level, to avoid ignition sources in the event of expected and/or rare malfunctions.
Page 316
Safety and commissioning information for Ex areas 14.2 Dry-running protection for centrifugal pumps by active power monitoring Marking on the nameplate of the SIMOCODE pro device with meaning with regard to the possible applications of the centrifugal pumps to be protected in hazardous areas: ●...
Page 317
Safety and commissioning information for Ex areas 14.2 Dry-running protection for centrifugal pumps by active power monitoring Explanation of approval for explosion protection within the equipment (centrifugal pump): In practice, very rarely zone 0 (gas/vapor/mist) will be present inside the pump, but possibly zone 2, sometimes also zone 1.
Please observe the SIMOCODE pro Operating Instructions (enclosed with the devices). You can find the Operating Instructions for SIMOCODE pro listed in Chapter General information about commissioning and service (Page 255) or at Operating Instructions (https://support.industry.siemens.com/cs/ww/en/ps/16027/man) in the Industry Online Support. NOTICE...
Safety and commissioning information for Ex areas 14.2 Dry-running protection for centrifugal pumps by active power monitoring 14.2.3.3 Special conditions for commissioning and operation NOTICE Commissioning and operation of the centrifugal pumps to be protected You must commission and operate the centrifugal pumps that are to be protected in accordance with the pump manufacturer's stipulations.
"Dry running wizard". Note Teach-in procedure The teach-in procedure as well as that for direct entry of the parameters is described in the chapter "Dry-running protection for centrifugal pumps" in the manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958). SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 321
For verification purposes, we recommend generating a log file (see Chapter "Dry-running protection of centrifugal pumps" in the manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958)) after setting the parameters (whether done as a teach-in or by means of direct entry using SIMOCODE ES).
Safety and commissioning information for Ex areas 14.2 Dry-running protection for centrifugal pumps by active power monitoring 14.2.3.5 Line protection NOTICE Cable / conductor cross sections Avoid impermissible maximum cable surface temperatures by correctly dimensioning the cross sections! Choose a sufficient cable cross section, especially for heavy-starting motors CLASS 20 to CLASS 40 (see Chapter Short-circuit protection with fuses for motor feeders for short-circuit currents up to 100 kA and 690 V for 1st generation current / voltage measuring module (Page 364))!
Page 323
Safety and commissioning information for Ex areas 14.2 Dry-running protection for centrifugal pumps by active power monitoring The following table shows the test phases performed when the "TEST / RESET" button is pressed for the required length of time: Test Status Without main current With main current...
Page 324
TRIP V,TRIP – If necessary, carry out a teach-in to determine the trip level (see Chapter "Dry-running protection for centrifugal pumps" in the manual Parameterizing SIMOCODE pro (https://support.industry.siemens.com/cs/ww/en/view/109743958)). – Set the start-up bridging time t to 0 s. BRIDGE – Start the centrifugal pump filled with operating medium; the pressure-side shut-off valve must be closed.
WARNING Safety information for DM-F Local and DM-F PROFIsafe fail-safe digital modules Pay attention to the safety notes in the Manual Fail-safe Digital Modules SIMOCODE pro (http://support.automation.siemens.com/WW/view/en/50564852). CAUTION Using relay outputs for the protection function For the protection function, only the relay outputs of the 3UF70 basic unit, of a monostable...
Safety and commissioning information for Ex areas 14.2 Dry-running protection for centrifugal pumps by active power monitoring 14.2.3.9 Safety values In a system with SIMOCODE pro basic units and current measuring modules, the functionality of the SIMOCODE pro motor protection and control device is suitable for use in safety functions up to safety integrity level SIL1.
(https://support.industry.siemens.com/cs/ww/en/ps/16027/man) in the Industry Online Support. 14.2.7 More information You will find further information on the Internet: ● Internet (https://www.siemens.com/simocode) ● Information and Download Center (https://www.siemens.com/sirius/infomaterial) ● Product Information System (ProdIS) (https://support.industry.siemens.com/My/ww/en/requests) ● Service and Support (https://support.industry.siemens.com/cs/ww/en/ps) ● ATEX (https://www.siemens.com/sirius/atex) ● Certificates (https://support.industry.siemens.com/cs/ww/en/ps/16027/cert)
Page 328
Safety and commissioning information for Ex areas 14.2 Dry-running protection for centrifugal pumps by active power monitoring SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Standards EN 60204-1, EN 1760-1, ISO 13849-1, IEC 61508, IEC/EN 60947-4-1, IEC/EN 60947-5-1, ISO EN 80079-36, ISO EN 80079-37 Test verification documents See Certificates (https://support.industry.siemens.com/cs/ww/en/ps/16027/cert) Permiss. ambient temperature In operation -25 to +60°C For storage and transport -40 to +80°C at installation altitude above MSL ≤...
Page 330
Technical data 15.1 Common technical data Common technical data Shock resistance (sine pulse) acc. to IEC 60068-2-27 General • 15 g / 11 ms • SIMOCODE pro S basic unit and • SIMOCODE pro S multifunction 15 g / 11 ms •...
Page 331
Technical data 15.1 Common technical data Common technical data Protective separation according to All SIMOCODE pro circuits are isolated from each other according to IEC IEC 60947-1 60947-1, i.e. dimensioned with double creepage distance and air clearance. Notice The notes of the test report, No. A0258 "Protective Separation" must be observed.
Technical data 15.2 Technical specifications of the SIMOCODE pro C / pro S / pro V PB / pro V MR basic units 15.2 Technical specifications of the SIMOCODE pro C / pro S / pro V PB / pro V MR basic units...
Page 333
Technical data 15.2 Technical specifications of the SIMOCODE pro C / pro S / pro V PB / pro V MR basic units Technical specifications of the SIMOCODE pro C / pro S / pro V PB / pro V MR basic units...
Page 334
Technical data 15.2 Technical specifications of the SIMOCODE pro C / pro S / pro V PB / pro V MR basic units Technical specifications of the SIMOCODE pro C / pro S / pro V PB / pro V MR basic units...
Page 335
Technical data 15.2 Technical specifications of the SIMOCODE pro C / pro S / pro V PB / pro V MR basic units Technical specifications of the SIMOCODE pro C / pro S / pro V PB / pro V MR basic units...
Page 336
Technical data 15.2 Technical specifications of the SIMOCODE pro C / pro S / pro V PB / pro V MR basic units Technical specifications of the SIMOCODE pro C / pro S / pro V PB / pro V MR basic units Connection of SIMOCODE pro S basic unit TORQUE: 5.2 lb.in to 7.0 lb.in...
Technical data 15.3 Technical specifications of the SIMOCODE pro V PN / pro V PN GP / pro V EIP basic units 15.3 Technical specifications of the SIMOCODE pro V PN / pro V PN GP / pro V EIP basic units Technical specifications of the SIMOCODE pro V PN / pro V PN GP / pro V EIP basic units Mounting Snap-mounted onto 35-mm standard mounting rail or screw-mounted...
Page 338
Technical data 15.3 Technical specifications of the SIMOCODE pro V PN / pro V PN GP / pro V EIP basic units Technical specifications of the SIMOCODE pro V PN / pro V PN GP / pro V EIP basic units PROFINET IO system redundancy PROFIenergy measured values PROFIenergy shutdown...
Page 339
Technical data 15.3 Technical specifications of the SIMOCODE pro V PN / pro V PN GP / pro V EIP basic units Technical specifications of the SIMOCODE pro V PN / pro V PN GP / pro V EIP basic units Rated switching capacity AC-15: •...
Technical data 15.4 Technical data of the current measuring modules and the current / voltage measuring modules 15.4 Technical data of the current measuring modules and the current / voltage measuring modules Technical data of the current measuring modules and the 2nd generation current / voltage measuring modules Mounting Current setting I = 0.3 A -...
Page 341
Technical data 15.4 Technical data of the current measuring modules and the current / voltage measuring modules Technical data of the current measuring modules and the 2nd generation current / voltage measuring modules Temperature drift of current 3UF7110-1AA01-0: 0.02% / K 3UF7113-1AA01-0: 0.01% / K measurement 3UF7111-1AA01-0: 0.01% / K...
Page 342
- 1.5 mm / 2 x AWG 20 to 16 1) You will find more information at SIMOCODE pro (https://www.siemens.com/simocode). 2) Screw connection is possible with an appropriate 3RT19 box terminal. 3) When connecting cable lugs complying with DIN 46235 to cables with a cross section larger than 95 mm , the 3RT19 56-4EA1 terminal cover is required to maintain phase separation.
Page 343
Technical data 15.4 Technical data of the current measuring modules and the current / voltage measuring modules Technical data of the current measuring modules or the 1st generation current / voltage measuring modules Operating range 0.1 x I ≤ I ≤...
Page 344
2) for 3UF7103 or 3UF7104 to 8 kV 3) You will find more information at SIMOCODE pro (https://www.siemens.com/simocode) and in Chapter Short-circuit protection with fuses for motor feeders for short-circuit currents up to 100 kA and 690 V for 1st generation current / voltage measuring module (Page 364) 4) Screw connection is possible with an appropriate 3RT19 box terminal.
Technical data 15.5 Technical data of the decoupling module 15.5 Technical data of the decoupling module Technical data of the decoupling module Mounting Snap-mounted onto 35-mm standard mounting rail or screw-mounted using additional push-in lugs. Display Green "READY" LED • System interfaces The left interface is for connection to a basic unit or an expansion module, the right interface is exclusively for...
Technical data 15.6 Technical data of the expansion modules 15.6 Technical data of the expansion modules 15.6.1 Technical data of the digital modules Technical data of the digital modules Mounting Snap-mounted onto 35-mm standard mounting rail or screw-mounted using additional push-in lugs Display Green "READY"...
Technical data 15.6 Technical data of the expansion modules Technical data of the digital modules Inputs (binary) 4 externally supplied, isolated inputs (24 V DC or 110 V to 240 V AC / DC, depending on the type), connected to common potential for measuring process signals (e.g.
Page 348
Technical data 15.6 Technical data of the expansion modules Technical data of the DM-F Local and DM-F PROFIsafe digital modules Rated insulation voltage U 300 V (at pollution degree 3) Rated impulse withstand 4 kV voltage U Mains buffering time 24 V DC: typically 20 ms at 0.8 x Us •...
Technical data 15.6 Technical data of the expansion modules 15.6.3 Technical data of the DM-F Local digital module Technical data of the DM-F Local digital module LEDs on DM-F LOCAL Color Meaning "READY" System interface not connected / supply voltage too low / device defective Green Device ON/system interface OK Flashing green...
Page 350
Technical data 15.6 Technical data of the expansion modules Technical data of the DM-F Local digital module Flickering yellow Configuration error "6" Cascading input 1, automatic start Yellow Cascading input 1, monitored start Flashing yellow Configuration mode waiting for confirmation Flickering yellow Configuration error "7"...
Technical data 15.6 Technical data of the expansion modules 15.6.4 Technical data of the DM-F-PROFIsafe digital module Technical data of the DM-F PROFIsafe digital module LED display DM- Color Meaning F PROFIsafe "READY" System interface not connected / supply voltage too low / device defective Green Device ON/system interface OK Flashing green...
15.6.5 Safety-related technical data of the digital modules DM-F Local and DM-F PROFIsafe See "Technical Data" in the Manual "SIMOCODE pro Safety" fail-safe digital modules (https://support.automation.siemens.com/WW/view/en/50564852). 15.6.6 Technical data of the analog module Technical data of the analog module Mounting...
Page 353
Technical data 15.6 Technical data of the expansion modules Technical data of the analog module 30 V DC Max. output voltage • ±1 % Accuracy • 500 ohms Max. output load • 25 ms Conversion time • 12 bits Resolution •...
Technical data 15.6 Technical data of the expansion modules 15.6.7 Technical data of the ground-fault module 3UF7500-1AA00-0 Technical data of the ground-fault module 3UF7500-1AA00-0 Mounting Snap-mounted onto 35 mm standard mounting rail or screw-mounted using additional push-in lugs Display Green "READY" LED Continuous light: "Ready for operation"...
Technical data 15.6 Technical data of the expansion modules 15.6.8 Technical data of the ground-fault module 3UF7510-1AA00-0 Technical data of the ground-fault module 3UF7510-1AA00-0 Mounting Snap-mounted onto 35 mm standard mounting rail or screw-mounted using additional push-in lugs Display Green "READY" LED • Continuous light: "Ready for operation"...
Technical data 15.6 Technical data of the expansion modules 1) Technical data residual current transformer 3UL23: See Manual 3UG4/3RR2 Monitoring Relay (https://support.industry.siemens.com/cs/ww/en/view/54397927). 15.6.9 Technical data of the temperature module Technical data of the temperature module Mounting Snap-mounted onto 35-mm standard mounting rail or...
Technical data 15.7 Technical data of the multifunction module 15.7 Technical data of the multifunction module Technical data of the multifunction module Mounting Snap-mounted onto 35-mm standard mounting rail or screw-mounted using additional push-in lugs Cabinet mounting Minimum distance to be maintained from cabinet rear wall for series mounting at side: 0 mm •...
Page 358
Technical data 15.7 Technical data of the multifunction module Technical data of the multifunction module DC-13 2 A / 24 V DC; 0.55 A / 60 V DC; 0.25 A / 125 V DC Ground-fault module function Connectable 3UL23 residual 35 mm to 210 mm current transformer - feed- through diameter...
Page 359
Technical data 15.7 Technical data of the multifunction module Technical data of the multifunction module Connection TORQUE: 5.2 LB.IN to 7.0 LB.IN Tightening torque • 0.6 Nm to 0.8 Nm Connection cross sections • - Solid 2 x0.5 mm to 1.5 mm ;...
Technical data 15.8 Technical data of the operator panels 15.8 Technical data of the operator panels 15.8.1 Technical data of the operator panel Technical data of the operator panel Mounting Installation in a cabinet door or in a front panel, with IP54 system interface cover.
Technical data 15.8 Technical data of the operator panels 15.8.2 Technical data of the operator panel with display Technical data of the operator panel with display Mounting Installation in a cabinet door or in a front panel, with IP54 system interface cover. LED displays Red / green / yellow "DEVICE"...
Page 362
Technical data 15.8 Technical data of the operator panels Note Usage restrictions concerning the operator panel with display • SIMOCODE pro V PB basic unit: The operator panel with display can only be used with SIMOCODE pro V PB basic unit from version *E03*. •...
Technical data 15.9 Technical data of the compartment identification 15.9 Technical data of the compartment identification Technical data of the initialization module Technical data of the initialization module Order No. (MLFB) 3UF7 902-0AA00-0 Ambient temperature -25 to +80 °C Rated voltage 300 V Rated operating voltage 24 V...
You will find selection tables for fuseless and fused motor feeders in the following manuals: ● Configuration Manual Load Feeders – Configuring the SIRIUS Modular System (https://support.automation.siemens.com/WW/view/en/39714188) ● Configuration Manual Configuring SIRIUS Innovations UL - Selection Data for Fuseless and Fused Load Feeders (https://support.automation.siemens.com/WW/view/en/53433538)
Technical data 15.11 Typical reaction times 15.11 Typical reaction times 15.11.1 Typical reaction times of the SIMOCODE pro C/V device series Table 15- 1 Typical reaction times of SIMOCODE pro C device series Component Time inputs Time processing Time outputs...
You wish to switch a relay output of the basic unit via PROFIBUS when the "remote" bit is set: ● SIMOCODE pro C: Reaction time = 30 ms + 30 ms + 10 ms = 70 ms ● SIMOCODE pro V: Reaction time = 5 ms + 5 ms + 10 ms = 20 ms.
Technical data 15.11 Typical reaction times 15.11.3 Typical reaction times of the Modbus RTU device series Component Time: Inputs Time: Processing Time: Outputs Basic unit: Set delay time 5 ms 10 ms Thermistor: 400 ms Modbus RTU: 5 ms 5 ms Current measurement: 300 ms Voltage measurement:...
Technical data in Siemens Industry Online Support Technical data sheet You can also find the technical data of the product at Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/ps/). 1. Enter the full article number of the desired device in the "Product" field, and confirm with the Enter key.
CAx data, dimension drawings 16.1 CAx data You can find the CAx data in the Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/). 1. Enter the full article number of the desired device in the "Product" field, and confirm with the Enter key.
Page 370
CAx data, dimension drawings 16.1 CAx data SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
European Norm EXplosion-proof: Specifies the protection classes for categorizing motors for use in hazardous areas. EtherNet/IP Explosion-proof Ground-fault module Electromotive force Electromagnetic compatibility F-CPU Fail-safe CPU (controller) Fieldbus Message Specification Basic unit SIMOCODE pro S basic unit SIMOCODE pro C basic unit SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 372
List of abbreviations A.1 List of abbreviations Abbreviation Term 1st generation SIMOCODE pro V PB basic unit (for UM) BU2+ 2nd generation SIMOCODE pro V PB basic unit (for UM+) BU2_MR 1st generation SIMOCODE pro V Modbus RTU basic unit (for UM) BU2_MR+ 2nd generation SIMOCODE pro V Modbus RTU basic unit (for UM+) SIMOCODE pro V PN basic unit...
Page 373
List of abbreviations A.1 List of abbreviations Abbreviation Term Feedback closed SELV Safety Extra Low Voltage GF, CF Group fault, control function Safety Integrity Level System function block System function Safe failure fraction Programmable logic controller Thermistor Temperature module Dry-running protection Total one fault delay time (maximum response time when error is present) OFDT Total worst case delay time (maximum response time in error-free state)
Page 374
List of abbreviations A.1 List of abbreviations SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Glossary 0/4 to 20 mA monitoring SIMOCODE pro supports two-phase monitoring of the analog signals of a transducer (standardized 0/4 - 20 mA output signal). The analog signals are fed to the "0/4 to 20 mA monitoring" function block via the analog module. Addressing plug The addressing plug is necessary to enable the hardware-based allocation of the PROFIBUS DP address to a basic unit without a PC / PG.
Page 376
SIMOCODE pro. Versions: ● SIMOCODE pro C basic unit: Basic component of the SIMOCODE pro C device series for PROFIBUS DP. It contains the essential motor control and motor protection functions. ● Basic unit pro S: Basic component of the SIMOCODE pro S device series for PROFIBUS DP.
Page 377
Glossary CLASS Unit for the trip class. Indicates the maximum tripping time in which SIMOCODE must trip at a current that is 7.2 times the value of the current setting I in a cold state (motor protection according to IEC 60947). If Class 10 is set for SIMOCODE pro, for example, it is ensured that the (cold) motor will switch off after 10 seconds if a current occurs that is 7.2 times the current setting.
Page 378
Glossary Control functions Control functions (e.g. direct-on-line starters, reversing starters) are used for controlling load feeders. They are characterized by the following important features: ● Monitoring the switch-on / switch-off process (no current flows in the main circuit without the ON command) ●...
Page 379
Glossary Current limit monitoring Current limit monitoring is used for process monitoring. This enables incipient anomalies in the system to be detected in good time. If a current limit is exceeded but still below the overload limit, it can, for example, indicate a dirty filter on a pump, or an increasingly sluggish motor bearing.
Page 380
Glossary Digital module (DM) Digital modules offer the option of further increasing the types and number of binary inputs and outputs on SIMOCODE pro V as required. Up to two digital modules can be connected to one SIMOCODE pro V basic unit. All types can be combined with each other. SIMOCODE pro V can thus be extended to a maximum of twelve binary inputs and seven binary outputs.
Page 381
Glossary Emergency start Emergency start deletes the thermal memory from SIMOCODE pro each time it is activated. This allows the motor to be immediately restarted after an overload trip. This function can be used to: ● Enable an immediate restart/reset after an overload trip ●...
Page 382
Glossary Expansion modules Expansion modules are intended as optional additions for the basic units. The following expansion modules are available: ● Digital module (DM) ● Analog module (AM) ● Ground-fault module (EM, EM+) ● Temperature module (TM) ● Multifunction module (MM). All expansion modules are equipped with 2 system interfaces (incoming/outgoing) and removable terminals.
Page 383
Glossary Function block Defined group of functions that can be freely parameterized by the user and connected to other function blocks to create a complete feeder-specific logic system. This means conventional wired control circuits containing auxiliary relays, time relays, etc. can be completely replaced.
Page 384
Glossary I&M data Identification and maintenance data. Information stored in a module that helps you to check the plant configuration, to locate hardware modifications in a plant, or to remedy faults in a plant. I&M data can be used to identify modules uniquely on the network.
Page 385
SIMOCODE pro parameterization, e.g. if a unit is exchanged. Note The SIMOCODE pro C and SIMOCODE pro V PB basic units up to product version *E08* only support the 3UF7900-0AA00-0 memory module. The basic units SIMOCODE pro S and SIMOCODE pro V (PB as from product version *E09*) also support the memory module 3UF7910-0AA00-0.
Page 386
Glossary Modbus address table Data with similar properties are combined in one of four address tables: Discrete inputs, coils, input register, holding register Modbus RTU Modbus RTU (Remote Terminal Unit) is a standard protocol for network communication and uses the electrical RS485 connection for serial data transmission between Modbus devices in the network.
Page 387
Glossary Motor stop time monitoring SIMOCODE pro can monitor the stop times of a motor to avoid plant downtimes due to failed motors caused by either running too long (wearing out) or being stopped for too long. Multifunction module Universal module of the SIMOCODE pro S device series with the following functions: ●...
Page 388
Glossary Operating hours monitoring The motor operating hours monitoring function enables the operating hours (service life) of a motor to be recorded so that motor maintenance prompts can be generated in good time as applicable. Operation monitoring SIMOCODE pro can monitor the operating hours and stop times of a motor and restrict the number of startups in a defined time frame in order to avoid plant downtimes due to failed motors caused by running or being stopped for too long.
Page 389
Glossary PC cable The PC cable is used to connect the serial interface of the PC to the system interface of a basic unit for device parameterization. Note PC cable variant For SIMOCODE pro V PN, a serial PC cable 3UF7940-0AA00-0 as from product version *E02* or a USB PC cable 3UF7941-0AA00-0 can be used.
Page 390
Glossary Process Automation (PA) Automation of continuous production processes. For instance, it controls production processes in the chemical industry or in water supply systems. PROFIBUS Process Fieldbus, a European process and fieldbus standard defined in the PROFIBUS standard (EN 50170, Volume 2, PROFIBUS). It specifies the functional, electrical and mechanical characteristics of a bit-serial fieldbus system.
Page 391
Glossary PROFINET PROFINET (Process Field Network) is the open Industrial Ethernet Standard from Profibus & Profinet International (PI) for automation. Within the context of Totally Integrated Automation (TIA), PROFINET is the systematic development of the following systems: ● PROFIBUS DP, the established fieldbus ●...
Page 392
Glossary Protection functions The protection functions ● Overload protection ● Unbalance protection ● Stalled rotor protection ● Thermistor protection ● Dry-running protection operate alongside motor control "at a higher level in the background." They can be active or not, according to the control function selected. Protective Extra Low Voltage (PELV) Protective measure against electric shock (formerly referred to as "protective extra low voltage with safe isolation").
Page 393
The SIL value describes the specified safety function in the event of a fault. SIMATIC Name of products and systems for industrial automation from Siemens AG. SIMATIC PDM You can also configure SIMOCODE pro using the SIMATIC PDM (Process Device Manager) software.
Page 394
Glossary SIMOCODE pro S7 slave The SIMOCODE pro S7 slave is a special slave with the following characteristics: ● It supports the S7 model (diagnostic interrupts, process interrupts) ● It can be parameterized SIMOCODE pro object manager (OM) Part of SIMOCODE ES. When SIMOCODE ES and SIMOCODE pro object manager are installed on a PC/PG, SIMOCODE ES can be called directly from STEP 7 HW Config.
Page 395
Glossary Station A device that can send, receive or amplify data via the bus, e.g. master, slave. Statistical data SIMOCODE pro makes statistical data available, which can be read out, for example, with SIMOCODE ES (TIA Portal) under Commissioning → Service Data / Statistical Data. STEP7 The basic STEP 7 software is the standard tool for the SIMATIC S7, SIMATIC C7, and SIMATIC WinAC automation systems.
Page 396
Glossary Test Position Feedback (TPF) If the motor feeder is in the test position, its main circuit is isolated from the network. However, the control voltage is connected. The "cold run" function test is performed with the feeder in this state. This means the motor feeder is tested without a current in the main circuit.
Page 397
Glossary Voltage monitoring SIMOCODE pro supports two-phase undervoltage monitoring of either a three-phase network or a one-phase network for freely selectable limits, direction of rotation (for AC) or readiness to start. The response of SIMOCODE pro on reaching a prewarning level or trip level can be freely parameterized and delayed.
Page 398
Glossary SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Color coding of the connecting cable, 244 Antivalence, 291 Commands, 110, 165 Commands, operator panel with display, 105 Siemens Industry Online Support, 14 Commissioning, 305, 318 Application description Saving Energy with Commissioning and service compartment SIMATIC S7 and ET200 S, 11...
Page 400
Connection conductors ground-fault module, 354, 355 Communication via PROFINET, 44 Connection conductors multifunction module, 359 Compartment identification, 159 Connection conductors SIMOCODE pro C / pro V basic Conductor cross sections, 197 units, 335 Conductor cross sections, stripped lengths, and Connection conductors temperature module, 356...
Page 401
Index Debouncing time, 147 Display of the operator panel with display, 361 Decoupling module, 135, 142 Display settings, 110 Decoupling module (DCM), 71 Display settings, operator panel with display, 104 Decoupling module connection example, 221 Displays of the operator panel with display, 92, 109 Decoupling module in different power systems, 143 Displays the current status of all device I/Os, 122 Degree of protection (according to IEC 60529), 329...
Page 402
Index Exchanging a 3UF52 operator panel for a 3UF720 operator panel, 283 Hardware fault, 294 Execution ON command, 291 High Performance units, 24 Execution STOP command, 291 Expansion modules, 62, 146 External fault, 57, 294 External ground fault, 294 External ground-fault monitoring, 49 Identification, 111 Identification of the motor feeder and the SIMOCODE pro components, 132...
Page 403
SIMOCODE pro V-PB basic Mounting, 332 units (3UF7010-1Ax00-0) with a 24 V DC or 110 V - Mounting basic unit, expansion modules or the 240 V AC/DC supply, 156 decoupling module, SIMOCODE pro C/V, 186 SIMOCODE pro System Manual, 05/2019, A5E40507475002A/RS-AD/004...
Page 404
No start permitted, 295 Phase sequence detection, 51 Non-volatile elements, 58 Phase unbalance, 297 Pin assignment for SIMOCODE pro C / pro V PB basic units, 199 Pin assignment for SIMOCODE pro V PN / EIP basic units, 202 OPC UA, 55...
Page 405
Removable terminals for basic units, expansion Prewarning overload, 300 modules, or the decoupling module, Product data sheet, 369 SIMOCODE pro C/V, 195 Product Information System (ProdIS), 313, 327 Repair, 312, 326 PROFIBUS DP, 54 Replacing a 1st generation current/voltage measuring...
Page 406
100 kA and 690 V, 364 Support Request, 15, 18, 287 Signal conditioning, 58 System interface SIMOCODE pro C, 10, 24, 66 Connection of cables, 244 SIMOCODE pro C basic unit, 82 Connection of system components, 244...
Page 407
Technical data of the Y connecting cable, 173, 363 Trip level P < undershot, 292 Technical specifications of the SIMOCODE pro C / Trip level P > overshot, 292 pro S / pro V PB / pro V MR basic units, 332 Trip level U <...
Page 408
Wiring sequence of the PROFIBUS cable for SIMOCODE pro S basic units, 205 Wiring sequence of the removable terminal of the SIMOCODE pro C/V basic units, 204 Wiring the initialization module, 167 Wiring the removable terminals of the basic unit, 207...