Using a motor reactor and dv/dt filter to limit the voltage gradient and transients
IGBT converter switching frequencies result in high voltage gradients (dv/dt) at the converter
output. If long motor cables are used, this leads to an additional current load on the
converter due to capacitive charge/discharge currents. The high voltage gradients, and the
resulting transients at the motor terminals, cause the motors' electrical winding load to
increase as compared with direct on-line operation. In conjunction with the connected cable
capacitances, the motor reactors with their adapted inductances reduce the capacitive
charge/discharge currents in the motor cables and, as a function of these motor cables, limit
the voltage gradient (dv/dt) and the transients Û
Figure 2-1
Motor reactors
Operating Instructions, 03/2012, A5E00409660A
6
5
4
3
2
1
0
100
200
300
0
m
Û /U
LL
N
Using a motor reactor and dv/dt filter to limit the voltage gradient and transients
at the motor terminals.
LL
6
5
4
3
2
1
0
100
200
300
0
m
Û /U
Û /U
LL
N
LL
N
General
9