Altitude And Temperature De-Rating; Motor Cable Length - Toshiba T300MV2 Instruction Manual

Medium voltage adjustable speed motor drive
Table of Contents

Advertisement

Altitude and Temperature De-rating

Altitude Derate Chart
Altitude
3,300'
4,000'
4,500'
5,000'
Temperature Derate Chart
Ambient Temperature
40 C
45 C
50 C

Motor Cable Length

Below are cable length guidelines for use with most standard industrial motors.
Suggested Maximum Output Cable Distances
AC Motor Voltage
2300
2300/4000
4000V or 2300/4000
6600V
CAUTION
(1) Older motors, or motors with marginal insulation systems, may require filters to help reduce the stress on
the insulation system. Consult Toshiba application engineering.
(2) Exceeding the peak voltage and allowable voltage rise time of the motor insulation system will reduce
motor life expectancy. To insure good insulation life, consult with the motor supplier to determine motor
insulation ratings and allowable maximum output lead distance. Long lead lengths between the motor and
drive may require that filters be added to the drive output.
IF08CZ10 April, 2019
% Amp Output Derate
0.0%
2.0%
3.3%
4.7%
% Amp Output Derate
0.0%
7.5%
15.0%
Drive Output Voltage
2400V
2400V
4160V
6600V
- 14 -
Max lead length
without filter
0-1000 ft
0-1000 ft
0-1000 ft
0-1000 ft