Grounding; Prevention Of Cable Removal - Mitsubishi Electric MELIPC MI5000 Series User Manual

Startup
Hide thumbs Also See for MELIPC MI5000 Series:
Table of Contents

Advertisement

Grounding

• Provide independent grounding when possible. Grounding work is to be to a class D grounding (3rd class grounding).
• Use the thickest cable (maximum of 2). Bring the grounding point close as close to the product as possible in order to
reduce to the minimum the length of the ground cable.
• If independent grounding cannot be provided, employ shared grounding with all grounding wires the same length.
(1)
Equipment
MELIPC
Ground
resistance of
100Ω or less

Prevention of cable removal

Take measures to prevent removal of USB and DisplayPort cables connected to this product.
1.
Pass a fixing band through the fixing band attachment structure (1) on the underside of the product.
2.
Pass a cable through the attached fixing band (2).
3.
Pass cables through the fixing bands (3).
(2)
Equipment
MELIPC
Ground
resistance of
100Ω or less
(1)
(2)
(3)
(3)
Equipment
MELIPC
APPX
167
Appendix 10 Wiring
A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melipc mi5122-vw

Table of Contents