Fairland Rapid IPHCR15 Installation And User Manual

Fairland Rapid IPHCR15 Installation And User Manual

Hide thumbs Also See for Rapid IPHCR15:

Advertisement

EN-CZ
INSTALLATION & USER MANUAL
Thank you for choosing Rapid by Fairland Inverter-Plus heat pump.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Rapid IPHCR15 and is the answer not in the manual?

Questions and answers

Summary of Contents for Fairland Rapid IPHCR15

  • Page 1 EN-CZ INSTALLATION & USER MANUAL Thank you for choosing Rapid by Fairland Inverter-Plus heat pump.
  • Page 3: Table Of Contents

    Summary For users ………………………………………………………………..………………. P.1-P.9 1. General information: ..........................- 3 - 1.1. Contents: .............................. - 3 - 1.2. Operating conditions and range:....................... - 3 - 1.3. Advantages of different modes: ......................- 3 - 1.4. Kind reminder: ............................. - 4 - 2.
  • Page 4: For Users

    For users Warning: a. Please read the following tips before installation, use and maintenance. b. Installation, removal and maintenance must be carried out by Professional personional in accordance with the instructions. c. Gas leakage test must be done before and after installation. 1.
  • Page 5 For users e. Installation must be stopped if any gas leakage, and the unit must be returned to professional maintenance center. 3. Transportation & Storage a. Sealing is not allowed during transportation b. Transporting goods at a constant speed is needed to avoid sudden acceleration or sudden braking, so as to reduce the collision of goods.
  • Page 6: General Information

    For users 1. General information: 1.1. Contents: After unpacking, please check if you have all the following components. 1.2. Operating conditions and range: ITEMS RANGE Operating range Air temp -7℃~43℃ heating 18℃-35℃ Temp. setting cooling 12℃-30℃ The heat pump will have ideal performance in the operation range Air 15 ℃~...
  • Page 7: Kind Reminder

    For users 1.4. Kind reminder: This heat pump has Power-off memory function. When the power is recovered, the heat pump will restart automatically. 1.4.1. The heat pump can only be used to heat the pool water. It can NEVER be used to heat other flammable or turbid liquid.
  • Page 8 For users 1.4.6. If any abnormal circumstances occurred, e.g.: abnormal noises, smells, smokes and leakage of electricity, switch off the main power immediately and contact your local dealer. Don’t try to repair the heat pump by yourselves. 1.4.7. The main power switch should be out of the reach of Children. 1.4.8.
  • Page 9: Operations

    For users 2. Operations 2.1. Notice before using ① For longer service life, please ensure water pump is on before heat pump is on, and water pump is off after heat pump is off. ② Ensure no water leakage on piping system, then unlock screen and press power on heat pump.
  • Page 10 For users ② Screen unlock: a. Press for 3 seconds to unlock screen and it will be lit up. b. Only after screen is unlocked, any other buttons can be functioned. Water inlet temperature Smart/Silence Water outlet mode temperature Auto Heating Cooling Compressor...
  • Page 11: Daily Maintenance And Winterizing

    For users 4. Smart/Silence mode selection: Smart mode as default will be activated when heat pump is on, and screen shows ① Press to enter Silence mode, and screen shows ② (Suggestion: select Smart mode for initial heating) 5. Defrosting a.
  • Page 12: Technical Specification

    For users 3. Technical specification Model IPHCR15 IPHCR20 IPHCR26 IPHCR33 IPHCR40 IPHCR45 IPHCR55 IPHCR70 IPHCR70T IPHCR100T Advised pool volume 15~30 20~40 25~45 30~55 35~65 40~75 50~95 65~120 65~120 90~160 Working air temp (℃) -7~43 Performance Condition: Air 26°C, Water 26°C, Humidity 80% Heating capacity (kW) 10.5 13.0...
  • Page 13: Transportation

    1. Transportation 1.1. When storing or moving the heat pump, the heat pump should be at the upright position. 1.2. When moving the heat pump, do not lift the water union since the titanium heat exchanger inside the heat pump will be damaged. 2.
  • Page 14: Installation Instruction

    between the pool and the heat pump. 2.2. Installation instruction 2.2.1. Location and size The heat pump should be installed in a place with good ventilation * MINIMUM DISTANCE Filter Water processor Water switch...
  • Page 15 UNIT=MM IPHCR15 IPHCR20 IPHCR26 IPHCR33 IPHCR40 IPHCR45 IPHCR55 IPHCR70 1084 IPHCR70T 1084 IPHCR100T 1154 ※ Above data is subject to modification without notice. 2.2.2. Heat pump installation. The frame must be fixed by bolts (M10) to concrete foundation or brackets. The ①...
  • Page 16 1. Connecting your power wire Please use cross screwdriver to take off ① the 2 screws at the bottom of the right side panel. Take off the lower half of the panel. Unscrew the 3 screws on the cover of ②...
  • Page 17: Trial After Installation

    Must be hard wired, no plug allowed For your safe use in winter, it’s strongly recommended to equip heating priority function.  For the detailed wiring diagram, please refer to Appendix 1.  3.Options for protecting devices and cable specification MODEL IPHCR15 IPHCR20...
  • Page 18: Maintenance And Winterizing

    2.4. Maintenance and winterizing 2.4.1 Maintenance The maintenance should be carried out once per year by qualified professional technician. ① Cut off power supply of the heat pump before cleaning, examination and repairing . Do not touch the electronic components until the LED indication lights on PCB turn off.
  • Page 19: Appendix 1: Heating Priority Wiring Diagram (Optional)

    DISPLAY NOT FAILURE DESCRIPTION No water protection Power supply excesses operation range Excessive temp difference between inlet and outlet water(Insufficient water flow protection) Ambient temperature too high or too low protection Anti-freezing reminder DISPLAY FAILURE DESCRIPTION High pressure protection Low pressure protection 3 phase sequence protection (three phase only) Water outlet temp too high or too low protection High exhaust temp protection...
  • Page 20: Appendix 2: Heating Priority Wiring Diagram (Optional)

    APPENDIX 2: HEATING PRIORITY WIRING DIAGRAM (OPTIONAL)
  • Page 21: Appendix 3: Heating Priority Wiring Diagram (Optional)

    APPENDIX 3: HEATING PRIORITY WIRING DIAGRAM (OPTIONAL)
  • Page 22 Parallel connection with filtration clock A: Water pump timer...
  • Page 23 B: Water pump wiring of Heat Pump Note: The installer should connect A parallel with B (as above picture). To start the water pump, condition A or B is connected. To stop the water pump, both A and B should be disconnected. EN-CZ...