5.9

PE conductor resistance (MI 3100 SE only)

In TN system instrument measures the resistance of the protection conductor from the power
transformer to the measurement site.
In TT system the resistance of protection conductor from mains outlet to earth electrode and
back to the power transformer via soil and the transformers earthing system is measured.
See chapter 4.2 Function selection for instructions
on key functionality.
Test parameters for PE conductor resistance measurement
Test
Selection of PE conductor resistance sub-function [Rpe,Rpe(rcd)]
Maximum resistance [OFF, 0.1  ÷ 20.0 ].
Lim
Circuits for measurement of PE conductor resistance
Figure 5.39: Connection of plug commander and 3-wire test lead
Figure 5.38: PE conductor resistance
55
Measurements