Installation
5
Inputs / outputs
40 | 124
Building Technologies
Fire safety
Mode
Initiate extra PSU
fault
Dialer (RT Fire
Device) Fault
Initiate fire brigade is
called
Acknowledge
command
Configured as 'output'
Configuration as 'output' allows the activation of external devices (e.g. relays) with
24 V voltage.
The line is not monitored.
Technical:
Max. current of each output: 0.1 A
Total max. current of four outputs (if configured) including AUX power output:
0.2 A.
The IO1 is configured as output by default if the country selection is 'NL: With
FTO3601 H1 (EVAC field)'.
Functionality
Activates external PSU fault as long as the input is
closed.
Activates RT fire device fault as long as the input is
closed.
The 'RT Fire Fault' LED and the 'General Fault' LED are
ON.
Generates an 'Fire brigade is called' event as long as the
input is closed. The 'Fire brigade' LED is ON.
Acknowledge all events as long as the input is closed.
A6V10421795_en--_g