Sounder - Siemens FC361 Series Technical Manual

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

Installation
5

Sounder

5.7 Sounder
38 | 124
Building Technologies
Fire safety
The panel mainboard has two sounder lines. They are monitored from the terminal
to the EOL for open and short circuits.
Application:
Sounder control
Technical:
Current of each sounder line: max. 0.5 A @ DC 24 V
Total available current of both sounder lines: max. 0.5 A @ DC 24 V
Each line must be terminated with an EOL element (Resistor 2.2 kΩ)
EOL
EOL
+
+
2
1
1
2
Sounder
Figure 11: Connection of sounder line
A6V10421795_en--_g
2016-11-18