Page 1
O P E R A T I N G I N S T R U C T I O N S Flexi Soft Gateways...
Page 2
This document is protected by the law of copyright, whereby all rights established therein remain with the com- pany SICK AG. Reproduction of this document or parts of this document is only permissible within the limits of the legal determination of Copyright Law. Alteration or abridgement of the document is not permitted without the explicit written approval of the company SICK AG.
Flexi Soft modular safety controller is integrated and who want to exchange data with a fieldbus (a controller) via a gateway. They are also addressed to people who are placing a Flexi Soft gateway in operation for the first time or maintaining it.
Warning! Pay attention to the safety notes and safety measures on the Flexi Soft gateways! WARNING We also refer you to our homepage on the Internet at Note www.sick.com...
Correct use The Flexi Soft gateways can only be operated with a Flexi Soft system. The firmware ver- sion of the connected FX3-CPUx must be at least V1.11.0, the version of the Flexi Soft Designer configuration software must be at least 1.3.0.
The operating instructions must be made available to the operator of the machine where a Flexi Soft system is used. The machine operator is to be instructed in the use of the device by qualified safety personnel and must be instructed to read the operating instructions.
A Flexi Soft gateway can only be operated on a Flexi Soft system. It does not have a dedi- cated voltage supply. It is possible to use two Flexi Soft gateways per system.
The Ethernet gateways FX0-GENT, FX0-GMOD and FX0-GPNT are available with different firmware versions. To add a gateway to a Flexi Soft system in the Flexi Soft Designer’s hardware configuration window, you must select the appropriate step from the drop down list under the respective gateway.
Data set 1 (max. 50 bytes) contains the operational data. It can be compiled using the Flexi Soft Designer tool. Upon delivery there is a default selection for the content of data set 1 which can be freely modified. For details see Tab. 5 on page 16.
Module status and EFI status as well as input and output values The Flexi Soft gateways can transmit the status and all input and output states of all Flexi Soft modules and EFI devices connected to the Flexi Soft system into the network. Data set 1 containing the input and output values and the EFI information can be customized.
Page 18
(e.g. C4000, S3000). transfer commands to the safety devices. The Flexi Soft gateways allow these EFI devices connected to the FX3-CPU1 or FX3-CPU2 to transmit their data into the network. It is only possible to select the EFI data in byte arrays. 4 byte arrays for each connected EFI Note device are available.
3.3.4 Routing of data from a second network If your Flexi Soft system contains two gateways, it is possible to rout information received by the first gateway from one network (e.g. from a Modbus PLC) into a second network via the second gateway (e.g.
Page 21
Tab. 13: Module status bits of the gateways Example Module 2 (Flexi Soft XTIO) has a stuck-at-high error (24 V) on output 3. The following module status will be transferred into the network (only the first 12 of 60 bytes are shown): Tab.
10 bytes The contents of the output data blocks can be used within the FX3-CPUx logic editor and can also be made available to another network via a second Flexi Soft gateway in the Flexi Soft system. In order to make the data from the network available in the logic editor or as input to Notes another network, you must define a tag name for each bit that shall be used.
Flexi Soft gateway. 4.1.1 Steps for mounting the modules The Flexi Soft system is only suitable for mounting in a control cabinet with at least IP 54 enclosure rating. WARNING While supply voltage is applied, modules must not be plugged to nor be removed from the Flexi Soft system.
Page 25
Fig. 1: Mounting the module onto the DIN mounting rail Make sure that the voltage supply of the Flexi Soft system is switched off. Hang the device onto the DIN mounting rail ( ). Connect the gateways directly onto the right side of the FX3-CPUx module of the Flexi Soft system.
To ensure full electromagnetic compatibility (EMC), the DIN mounting rail must be connected to functional earth (FE). The control cabinet or assembly casing of the Flexi Soft system must comply at least with enclosure rating IP 54. Mounting in accordance with EN 50 274.
Modify the settings if required and click OK. Click OK. The dialog closes. Click on Connect to physical device. The Flexi Soft Designer will search for connected Flexi Soft devices and load the hardware configuration into the hardware configuration dialog. Once all modules have been identified correctly, the Flexi Soft Designer will ask whether the configuration shall be uploaded.
For the configuration of the operational data (data transfer from and to the network), please refer to chapter 7 “Layout and content of the process image” on page 173. More information can be found in the Flexi Soft Designer operating instructions (SICK part no. 8012998).
“Auto Start mode” is active in the configuration of the main module. If the configu- ration is not set to verified, the system stays in Idle mode (CV LED on the FX3-CPUx module flashing) after power-up and needs to be set to Run state using the Flexi Soft Designer.
When in online mode, you can upload a configuration from the connected Flexi Soft system: Click on Upload. The current configuration of the Flexi Soft system will be loaded into the Flexi Soft Designer and can be edited after going offline.
Flexi Soft system over Ethernet TCP/IP. This runs parallel to the Ethernet TCP/IP or other Ethernet protocols. Do not connect to the Flexi Soft system via the RS-232 and the Ethernet interface at the same time! The Flexi Soft system can only communicate with one instance of the Flexi Soft Designer at WARNING one time.
Page 33
On the left side of the dialog you will find the area for the gateway’s IP configuration. If desired, enter a Device name for the Flexi Soft gateway. Enter a valid IP address, for the Flexi Soft gateway, and if required a valid Subnet mask and a valid IP address for a Default gateway.
Page 34
IP address settings of your PC or the IP address set- tings of the gateway to match the other device’s IP setup. Open the Flexi Soft Designer configuration tool installed on the PC and upload the hard- ware configuration including the gateway.
Page 35
Fig. 12: Create new TCP/IP profile dialog after scan has been performed Flexi Soft Designer with version O 1.4.0 performs an UDP scan. This means that all Flexi Notes Soft Ethernet gateways with firmware version O V2.00.0 (FX0-GMOD, FX0-GPNT and FX0-GENT) in the network will be detected, even if they are in a different subnet.
Page 36
TCP/IP profile activated Click OK. All communication to the Flexi Soft system will now happen via TCP/IP. In order to use the profile via the serial interface again, you will have to re-activate it. The port number for the TCP/IP configuration interface is pre-set to port 9000 and can not Note be changed.
Click on the Set device config button to transfer the new settings to the device. Note If the Flexi Soft Designer identifies a Flexi Classic series gateway in the network, this will be displayed in the list as well. These gateways are equipped with an internal web server and can be addressed using the Open web browser button.
Page 38
In that case, the last message overrides data received earlier. The gateway processes the data of a Flexi Soft system and makes it available in different compilations, the data sets. These data sets are available over the TCP/IP interface. For a detailed description of the data sets please refer to section 3.3 “Data transmitted into the...
Page 39
Chapter 5 Flexi Soft Gateways Configuration of the TCP/IP interface — Who establishes the connection If the Flexi Soft gateway shall connect to external applications, perform the following configuration steps: Activate the Connect to radio button. Set IP address to the IP address of the computer the application is running on.
Page 43
In order to configure the Application requests (Polling) mode of the gateway via the Flexi Soft Designer tool, perform the following steps: Open the Flexi Soft Designer and load the hardware configuration including the gateway. Click on the Gateways button above the main window and select the desired gateway or double click the desired gateway in the hardware configuration view to open the gateway configuration dialog.
Page 44
The configuration settings are available via the Flexi Soft Designer configuration tool or via the TCP/IP interface itself. Using one interface does not disable the other: The auto update mode could be enabled via Flexi Soft Designer and disabled via TCP/IP command, for example.
Page 45
In order to configure the Gateway writes to Address/Port (Auto update) mode of the gateway via the Flexi Soft Designer tool, perform the following steps: Open the Flexi Soft Designer and load the hardware configuration including the gateway. Click on the Gateways button above the main window and select the desired gateway or double click the desired gateway in the hardware configuration view to open the gateway configuration dialog.
TCP/IP, issue commands to the gateway and to write data to the gate- way’s output data sets. The TCP/IP socket monitor is a separate program that is installed with the Flexi Soft Designer. You will find the TCP/IP socket monitor in the Windows Start menu under “Programs/SICK/Flexi Soft Designer/Tools/TCPIP socket monitor”.
Page 49
Select the network adapter that is connected to the gateway. The MAC address and the IP address of the selected network adapter are displayed beneath the dropdown list. Enter the Flexi Soft IP address of the gateway and the Port number of the enabled socket.
You will find the EDS files and the device icon for PLC interfacing … in the Internet on the FX0-GENT product page on www.sick.com. in the Flexi Soft Designer program folder on your hard disk (default installation folder is “C:\programs\SICK\FlexiSoft\DeviceDescriptions\...”).
If desired, change the Device name for the Flexi Soft gateway. Enter a valid IP address for the Flexi Soft gateway, and if required a valid Subnet mask and a valid IP address for a Default gateway. Click Connect to go online and download the configuration to the Flexi Soft system.
Flexi Soft Gateways 5.2.3 EtherNet/IP Class 1 communication — Implicit messaging Only Flexi Soft EtherNet/IP gateways with firmware O V2.00.0 support both EtherNet/IP Note implicit messaging and explicit messaging (Class 1 and Class 3). If your gateway has an older firmware version, please refer to section 5.2.6 “Ethernet/IP Class 3 communica- tion —...
Page 58
Vendor Specific objects to a standard interface which the EtherNet/IP PLC uses to communicate with the device. For the Flexi Soft EtherNet/IP gateway, the assembly object corresponds to the Full Data Set Transfer object (72h), which provides access to the input and output data sets (see page 65).
You will find a description of the configuration of a class 1 connection using an OMRON PLC in the brochure “Flexi Soft Ethernet IP: Implicit Messaging with an Omron PLC” (SICK part no. 8015341). This brochure is available for download in PDF format at www.sick.com.
Page 61
Both methods can be mixed. E.g. it is possible to configure the gateway as master for the Flexi Soft to Network direction (option Gateway writes to tag/file activated) while it ope- rates at the same time as slave for the Network to Flexi Soft direction (option PLC writes activated).
Page 62
Within the Gateway configuration dialog, select the transfer method by activating Gate- way writes to tag/file for the Flexi Soft to Network direction and Gateway reads from tag/file for the Network to Flexi Soft direction. Select which data shall be written to/read from the PLC by checking the checkbox for the required data set.
Page 63
The configuration is considered faulty, if the PLC IP address is zero and either Gateway Note writes to tag/file for the Flexi Soft to Network direction and/or Gateway reads from tag/file for the Network to Flexi Soft direction is activated.
Page 64
Within the Gateway configuration dialog, select the transfer method by activating PLC requests for the Flexi Soft to Network direction, PLC writes for the Network to Flexi Soft direction. Select which data shall be requested or written by the PLC by checking the checkboxes for the required data sets.
Page 68
Unsolicited — Write to File Receive Method When it is determined that data received on the Flexi Soft gateway’s FLEXBUS+ inter- face is to be sent to the PLC, the data is immediately written to a file location on the PLC.
Example for the configuration of explicit messaging This section gives an example how to configure explicit messaging using RSLogix. Required gateway settings In the Gateway configuration dialog of the Flexi Soft Designer, the following settings have to be activated: PLC requests...
Operating Instructions Flexi Soft Gateways 5.2.10 Diagnostics and troubleshooting For information how to perform diagnostics on the Flexi Soft system please refer to the operating instructions for the Flexi Soft Designer software (SICK part no. 8012998). Tab. 57: Troubleshooting for Error...
Page 79
Within the Gateway configuration dialog, select the transfer method by checking Gateway writes to tag/file for the Flexi Soft to Network direction and Gateway reads from register for the Network to Flexi Soft direction. Select which data shall be written to/read from the PLC by checking the checkbox for the required data set.
Page 80
The following restrictions apply when the gateway is master and writes the input data sets Note to the PLC: The input data set address (set via Flexi Soft Designer Tool) must be the same as that defined on the PLC. The variable to receive the data on the PLC must be: –...
Page 81
Within the Gateway configuration dialog, select the transfer method by checking PLC requests for the Flexi Soft to Network direction and PLC writes for the Network to Flexi Soft direction. Select which data shall be written/read to/from the PLC by checking the checkbox for the required data set.
See section 5.1.2 “Ethernet TCP/IP socket interface” on page 37. 5.3.6 Diagnostics and troubleshooting For information how to perform diagnostics on the Flexi Soft system please refer to the operating instructions for the Flexi Soft Designer software (SICK part no. 8012998). Tab. 65: Troubleshooting for...
You will find the GSDML file and device icon for PLC interfacing with PROFIBUS support … in the Internet on the FX0-GPNT product page on www.sick.com. in the Flexi Soft Designer program folder on your hard disk (default installation folder is “C:\programs\SICK\FlexiSoft\DeviceDescriptions\...”).
LED of the FX0-GPNT Activate the checkbox. After downloading the configuration, the LED will light up Green permanently, even if no PROFINET communication is established. This feature is only available with firmware O V2.00.0 and Flexi Soft Designer version Note O 1.4.0.
Page 87
Assign a unique plant specific name to the gateway by using either the network configu- ration tool, e.g. SIEMENS SIMATIC Manager or the Flexi Soft Designer tool. Using the plant specific (unique) name, the I/O controller (i.e. PLC) can now assign the IP address to the gateway before system boot.
Usually the IP address will be assigned by the PROFINET IO controller (e.g. PLC). However, the FX0-GPNT allows configuration of the entire Flexi Soft system over Ethernet TCP/IP. In this case, it may be necessary to assign an IP address to the gateway even before the PROFINET IO network has been setup.
Page 89
Flexi Soft Gateways Step 2: Add the gateway to the project In order to have the Flexi Soft system data available in the PLC process image, the gate- way must be added to the hardware configuration first. The procedure associated with this depends on the hardware configuration program of the PLC being used.
Page 91
Assign the device name to the gateway. Select PLC > Ethernet > Assign device name. The Assign device name dialog opens. From the Assign device name dialog, find and select the SICK gateway that you wish to assign the device name to in the list.
PROFINET configuration of the gateway — Which data are transferred Cyclic data The physical Flexi Soft I/O modules are not represented as typical hardware modules in the PROFINET IO hardware catalogue. Instead, the data available from the Flexi Soft sys- tem has been organized into data blocks.
Page 93
There are five (5) output data blocks, 10 bytes each. The content of these data blocks can be used as input in the Flexi Soft logic editor or can be routed via a second gateway into another network. In order to have the desired bits available for routing or in the logic editor, tag names have to be defined for each bit that shall be used.
Page 95
Alarms can be read acyclically through the PROFINET IO alarms infrastructure. Once an error occurs on any Flexi Soft module, the PROFINET IO gateway raises the appropriate diagnostic alarm to the network. This will trigger the fault LED on the PLC, and make the specifics (text and help) of the diagnostic alarm available through the SIMATIC PLC inter- face.
10). If the error remains, replace the gateway. With firmware O V2.00.0 the red/green flashing of the STATUS LED can be disabled in the Flexi Soft Designer. In this case, the STATUS LED is Green permanently, if the configuration is valid.
You will find the ESI file and the device icon for PLC interfacing with EtherCAT support … in the Internet on the FX0-GETC product page on www.sick.com. in the Flexi Soft Designer program folder on your hard disk (default installation folder is “C:\programs\SICK\FlexiSoft\DeviceDescriptions\...”).
5.5.2 Installation of the gateway in the Flexi Soft system This section outlines the basic steps to install the gateway in the Flexi Soft system. More detailed information will be given in the following sections. Add the gateway to a Flexi Soft system Mount the gateway as described in section 4.1.1 “Steps for mounting the modules”...
EtherCAT network configuration tool (e.g. TwinCAT) for the first time, the ESI file of the gateway must be installed into the hardware catalogue of the tool. You will find the ESI file in the Flexi Soft Designer program folder (default folder is “C:\programs\SICK\FlexiSoft\DeviceDescriptions\FX0-GETC_ESI”).
Page 105
I.e. only one of these five input PDOs can be active at any time. There is one input PDO for 10 byte input data (1 data set used in the Flexi Soft Designer), one for 20 byte data (2 data sets used) etc. up to the maximum of 50 byte.
Similar to the input data, the output data are divided into five data sets. Each output data set contains 10 bytes. Notes The contents of the output data sets can be configured in the Flexi Soft Designer confi- guration software. See section 7.3.6 “Output data configuration (Network to Flexi Soft)” on page 180.
5.5.6 Tag name export The Flexi Soft Designer allows you to export the names of the bits used in the input and output data sets. Before exporting you can also edit the start addresses for the used data sets in the PLC. The exported tag names and start addresses can then be imported as variables to the application program in the EtherCAT network configuration tool (e.g.
Page 109
Flexi Soft Gateways How to change the start address for the data sets: Open the Flexi Soft Designer and load the hardware configuration including the EtherCAT gateway. Ensure your project is offline. Click on the Gateways button above the main window and select the FX0-GETC or double click the FX0-GETC in the hardware configuration view to open the gateway configuration dialog.
Follow the instructions in the online help or in the user manual of your EtherCAT network configuration tool for assigning an IP address and a subnet mask. If the EtherCAT master and the Flexi Soft Designer are running on different PCs, then TCP/IP routing must be enabled in the Flexi Soft Designer.
Page 112
Flexi Soft Gateways Input process data (2000h) This object contains the input process data from the Flexi Soft system to an EtherCAT PLC and makes them available for acyclic usage. It corresponds to the EtherCAT input PDO data of the FX0-GETC.
Page 113
The ASCII string is “module xx +” or “module xx -”, where xx stands for the position in the Flexi Soft system of the module that has generated the diagnosis message. Coming diag- nosis messages are marked with a “+”, going diagnosis messages are marked with a “-”.
Operating Instructions Flexi Soft Gateways 5.5.10 Diagnostics and troubleshooting The FX0-GETC provides the following module status bits in the Flexi Soft system for diag- nostic purposes. The module number of the FX0-GETC is 16. Tab. 81: Module status bits Error message...
Page 115
Ethernet gateways Operating Instructions Chapter 5 Flexi Soft Gateways For information how to perform diagnostics on the Flexi Soft system please refer to the operating instructions for the Flexi Soft Designer software (SICK part no. 8012998). Tab. 82: Troubleshooting for Error...
Fieldbus gateways Chapter 6 Operating Instructions Flexi Soft Gateways Fieldbus gateways PROFIBUS DP gateway The following Flexi Soft gateway can be used for PROFIBUS DP: FX0-GPRO. 6.1.1 Interfaces and operation Controls and status indicators Fig. 56: Controls and status indicators FX0-GPRO...
Page 117
The address that can be set via the hardware address switch ranges from 1 … 99. Notes The address that can be set via the Flexi Soft Designer software ranges from 3 … 125. The PROFIBUS master cannot overwrite the address.
On loading configurations that have been prepared using a version of Flexi Soft Designer < 1.3.1 the check box is cleared. In the case of configurations that have been prepared using Flexi Soft Designer 1.3.1 or higher, the check box is selected.
Page 121
“Data transmitted into the network (input data sets)” on page 14. How to set the start address for the data blocks: Open the Flexi Soft Designer and load the hardware configuration including the PROFIBUS DP gateway. Ensure your project is offline.
Click OK to accept the new start address. For further information on how to configure the process image, see chapter 7 “Layout and content of the process image” on page 173 and the Flexi Soft Designer operating instruc- tions (SICK part no. 8012998).
Page 123
Flexi Soft. Step 2: Add the gateway to the project In order to have the Flexi Soft system data available in the PLC process image, the gate- way must be added to the hardware configuration first. The procedure associated with this depends on the hardware configuration program of the PLC being used.
Page 124
(6 bytes) device related diagnostics: status messages or manufacturer specific messages Each Flexi Soft module supports a unique module ID. Based on this ID the gateway deter- mines the manufacturer specific diagnostics number. This way it is possible to retrieve module specific diagnostics texts from the GSD file.
Chapter 6 Flexi Soft Gateways 6.1.4 Diagnostics and troubleshooting For information how to perform diagnostics on the Flexi Soft system please refer to the operating instructions for the Flexi Soft Designer software (SICK part no. 8012998). Tab. 93: Troubleshooting for Error...
Page 131
10 position rotary switch for setting the module address (ones) How to set the baud rate via hardware DIP switches: Set the baud rate using the DIP switches on the device. Then switch the Flexi Soft system off and back on again.
Page 132
The address that can be set via the hardware address switch ranges from 1 … 99. Notes The address that can be set via the Flexi Soft Designer software ranges from 1 … 127. The CANopen master cannot overwrite the address.
You will find the EDS file and device icon for PLC interfacing … in the Internet on the FX0-GCAN product page. in the Flexi Soft Designer program folder on your hard disk (default installation folder is “C:\programs\SICK\FlexiSoft\DeviceDescriptions\...”). 6.2.2 CANopen configuration of the gateway —...
Page 134
Select the EDS file for the FX0-GCAN and click on the Open button. Step 2: Add the gateway to the controller In order to have the Flexi Soft system data available in the PLC process image, the gate- way must be added to the hardware configuration first. The procedure associated with this depends on the hardware configuration program of the PLC being used.
“Data transmitted into the network (input data sets)” on page 14. For further information on how to configure the process image, see chapter 7 “Layout and content of the process image” on page 173 and the Flexi Soft Designer operating instruc- tions (SICK part no. 8012998).
Page 144
281-2FF 381-3FF 481-4FF B1…B32: CAN telegram bytes as mapped into the network input data using the Flexi Soft Designer software (see 7.3 “Customizing the operational data (Flexi Soft to Network)” on page 175). The gateway sends one or more TxPDOs if at least one of the following occurs: At least one input or output byte has changed its value and the transmission type for the TxPDO containing this byte has the value 255.
Page 148
Software version of the device Serial number UDINT Serial number of the device SDO 1027: Module list The module list contains the module type and the module ID of all Flexi Soft modules in the system. Tab. 121: SDO 1027 Subindex Module...
Page 149
0609 0030h, invalid parameter value). SDO 1600…1603: RxPDO mapping parameters This SDO can not be used since the RxPDO mapping is done using the Flexi Soft Designer. See also Tab. 110 and Tab. 112. SDO 1800…1803: TxPDO communication parameters Using SDO 1800 to 1803 the communication parameters for the TxPDOs 1 to 4 are configured.
Page 150
Operating Instructions Flexi Soft Gateways SDO 1A00…1A03: TxPDO mapping parameters This SDO can not be used since the TxPDO mapping is done using the Flexi Soft Designer. See also Tab. 110 and Tab. 111. SDO 3100: Module status bits SDO 3100 contains the module status bits from the Flexi Soft system (see Tab. 105).
Page 151
Flexi Soft Gateways SDO 3300: Module type code array SDO 3300 contains the type codes of the max. 15 modules in the Flexi Soft system in SINT format (8 bytes per module = 120 bytes). See the following table for details.
Always use either node guarding or heartbeat! According to the CIA CANopen specification DS 301 guarding is mandatory. Please activate either node guarding or heartbeat. If no guarding is configured the Flexi Soft system can WARNING not detect an interruption of the CANopen communication, e.g. a broken network cable. In this case the CANopen gateway’s input and output data may be frozen.
Page 154
Heartbeat and node guarding/life guarding can not be used simultaneously. If the configuration is changed from activated life guarding to no life guarding or vice versa a complete power reset of the Flexi Soft system is required to setup the CANopen network communication properly.
Module status bit 8 (bit 0 of byte M4) = 0: input 1-2 dual channel input evaluation: error detected 6.2.14 Diagnostics and troubleshooting For information on how to perform diagnostics on the Flexi Soft system please refer to the operating instructions for the Flexi Soft Designer software (SICK part no. 8012998). Tab. 132: Troubleshooting for Error...
Page 162
DIP 3 DIP 4 on the FX0-GDEV If all DIP switches are set to Off, then the setting for the baud rate in Flexi Soft Designer Notes is used. All other DIP switch settings will set the baud rate to 125 kbit/s.
Page 163
The address that can be set via the Flexi Soft Designer software ranges from 0-63. The DeviceNet master cannot overwrite the address. If the DeviceNet address and the baud rate are set using the Flexi Soft Designer, the settings will become effective immediately after transferring the configuration (i.e.
You will find the EDS file and device icon for PLC interfacing … in the Internet on the FX0-GDEV product page. in the Flexi Soft Designer program folder on your hard disk (default installation folder is “C:\programs\SICK\FlexiSoft\DeviceDescriptions\...”). Download the EDS file and device icon from www.sick.com, on the FX0-GDEV product page.
For information how to define and customize the content and tag names of the input and output data sets please see chapter 7 “Layout and content of the process image” on page 173 and the operating instructions for the Flexi Soft Designer software (SICK part no. 8012998).
Flexi Soft Gateways 6.3.7 Diagnostics and troubleshooting For information on how to perform diagnostics on the Flexi Soft system please refer to the operating instructions for the Flexi Soft Designer software (SICK part no. 8012998). Tab. 147: Troubleshooting for Error...
Layout and content of the process image Routing The process image transmitted by the Flexi Soft gateways into the network consists of the operational data (e.g. logic results, input and output states) and the diagnostics data (e.g. module status, CRCs). These data are organised in 4 data sets.
You will find more detailed information in the Flexi Soft Designer software operating instructions (SICK part no. 8012998). In the delivery status, the data routing configuration of the Flexi Soft gateways is shown in the gateway configuration dialog.
In the default configuration, only the first logic result byte (Logic result 0) is active and available. You can activate more logic result output bits in the logic editor (see the Flexi Soft software operating instructions, SICK part no. 8012998).
(e.g. for extension modules). In the Tag names area of the Flexi Soft to Network configuration dialog, it is not possible to edit tag names, with the exception of the gateway direct outputs (see the following section).
Click on the Flexi Soft to Network or the Network to Flexi Soft tab on the left hand menu to display the routing view for the input or output data you want to monitor.
Need help?
Do you have a question about the Flexi Soft and is the answer not in the manual?
Questions and answers