2. Parameters

2.1. Common parameters

The product doesn't operate if these parameters are not correctly set.
Comm.
Title
No.
CMOd
0003
Command mode selection
Frequency setting mode
FMOd
0004
selection 1
AUE
0032
Eco-standby power setting
Setting of acceleration /
F519
0519
deceleration time unit
Integrating wattmeter display
F749
0749
unit selection
F830
0830
MODBUS continuous address
Number of motor pole pair for
F856
0856
communication
F897
0897
Parameter Writing
Parameter name
Description
0: Terminal
1: Operation panel, Extension panel
2: Embedded Ethernet
3: RS485 communication (connector 1)
4: RS485 communication (connector 2)
5: Communication option
0: -
1: Terminal RR
2: Terminal RX
3: Terminal II
4: Terminal AI4 (option)
5: Terminal AI5 (option)
6-9: -
10: Touch wheel 1 (power off or press OK to save)
11: Touch wheel 2 (press OK to save)
12: Sr0
13,14: -
15: Terminal Up/Down frequency
16: Pulse train
17: High resolution pulse train (option)
18,19: -
20: Embedded Ethernet
21: RS485 communication (connector 1)
22: RS485 communication (connector 2)
23: Communication option
0: -
1: Embedded Ethernet OFF
(Unable to communicate with Ethernet)
0: -
1: 0.01s unit (0 after execution)
2: 0.1s unit (0 after execution)
0: 1.0=1kWh
1: 1.0=10kWh
2: 1.0=100kWh
3: 1.0=1000kWh
4: 1.0=10000kWh
5: 1.0=100000kWh
0: Disabled
1: Enabled
1: 2 pole
2: 4 pole
3: 6 pole
4: 8 pole
5: 10 pole
6: 12 pole
7: 14 pole
8: 16 pole
0: Storage to memory device
1: Storage to memory device except by
communication
7
E6582125
Default
setting
1
1
0
0
(*1)
(*2)
0
2
0