Set Application; Application Point [06] - Siemens SITRANS Series Operating Instructions Manual

Pressure transmitter ma/hart
Hide thumbs Also See for SITRANS Series:
Table of Contents

Advertisement

Example
For the volume measurement, you set the following values, for example:
Damping value:
Lower range value:
Upper range value:
Application:
Unit:
Lower scaling point:
Upper scaling point:
9.2.4.5

Set application

Procedure
1. Navigate to the parameter view.
Navigating in the views (Page 71)
2. Select the "Application" parameter [05].
3. Select the parameter value.
Application [05] (Page 106)
Result
You have set the application of your device.
9.2.5

Application point [06]

Sets the application point from which scaling occurs according to the square root. Before the
application point, the scaling occurs in a linear relationship with the differential pressure.
This parameter is only visible when you have selected "Linear, square root" (VSLIN or MSLIN)
or "Hold at 0, square root" (VSOFF or MSOFF) using the "Application" parameter.
Setting range:
Factory setting:
See also
Volume and mass flow measurements (Page 111)
SITRANS P320/P420 (mA/HART)
Operating Instructions, 06/2018, A5E44852162-AA
9.2 Parameter assignment over device with display
2.0 s
0.0 mbar
500.0 mbar
Cylinder vessel (CYLIN)
m
3
0.0 m
3
10.0 m
3
5 to 15%
10%
Parameter assignment
115