Step 6: Verify removal of all dangerous voltages.

If the metal option mounting bracket is present, carefully remove
it. Remove and keep the two screws at the bottom of the shield.
A magnetic screw driver is helpful for this step.
Use an appropriate meter to verify the absence of AC line voltage
on the load side of the main disconnect or circuit breaker.
!
Warning! The main disconnect or circuit breaker for the unit is
BOTTOM FEED.
!
Warning! Even when power is removed as directed above, dan-
gerous voltages from customer supplied external sources may be
present, particularly on the relay outputs, Terminals 17 – 22. Mea-
sure the voltage at these terminals before continuing. If voltage is
present, identify and disconnect the source.

Step 7: Verify the version of the bypass control board.

These instructions are written for those units that have the cur-
rent version E-Bypass control board.
If your control board has two potentiometers as show in this pho-
tograph, it is the current version.
If your control board does not have two potentiometers as shown
in this photograph, it is the older version. These instructions are
NOT VALID for the older version E-Bypass control boards. If
your board is the older version, an upgrade kit can be purchased
separately.

Step 8: Remove the Control Panel from the drive.

Swing the panel out from either the top or bottom and remove it
from the connector.
7