Periphery board (4 loops) FCI2004-A1
Technical data
Monitored output
Fault
Changeover contacts
RT alarm
Monitored output
Alarm
Monitored horn outputs 1 and
2
74
Building Technologies
Fire Safety
Designation
Design
Output voltage
Output current
Guaranteed output current
(monitored for short circuit and open line)
Monitored for (if output inactive)
Nominal monitoring resistance
min. tolerance
Designation
Design
Switching voltage
Switching current
Designation
Design
Output voltage
Output current
Guaranteed output current
(monitored for short circuit and open line)
Monitored for (if output inactive)
Nominal monitoring resistance
min. tolerance
Designation
Design
Output voltage
Output current
Guaranteed output current:
(monitored for short circuit and open line)
Monitored for (if output inactive)
Nominal monitoring resistance
min. tolerance
'VSYS_O'; 'FAU_OUT'
Open drain
Failsafe
Activated in degraded mode
DC 21...28.6 V
Max. 0.3 A (safeguarded with 1 AT)
15 mA with U
= 16 V
out min
Short-circuit
Open line
1.6 ... 2.3 k
+/–
'AL_NO'; 'AL_COM'; 'AL_NC'
Relay output
Break or make contact
Activated in degraded mode
Max. DC 60 V
Max. 400 mA
'AL_OUT+'; 'AL_OUT-'
Relay reversed polarity
Activated in degraded mode
DC 21...28.6 V
Max. 1 A (protected with 1 AT)
20 mA with U
= 16 V
out min
Short-circuit
Open line
2.3...5.5 k
+/–
'SOUND1+'; 'SOUND1-'
'SOUND2+'; 'SOUND2-'
Relay reversed polarity
Activated in degraded mode
DC 21...28.6 V
1
Max. 1 A (protected with 1 AT)
20 mA with U
= 16 V
out min
Short-circuit
Open line
2.3...5.5 k
+/–