Connecting; Cables And Busbars - Siemens SENTRON 3VL160X System Manual

Iec molded case circuit breakers
Hide thumbs Also See for SENTRON 3VL160X:
Table of Contents

Advertisement

Connecting

7.1

Cables and busbars

The 3VL molded case circuit breaker can be connected using cables, flexible copper bars or
busbars.
Thermal and electrodynamic stresses affect these conductors in the event of a short-circuit.
To avoid dangerous effects, it is necessary to asses them correctly and to take appropriate
measures to suppress them.
The diagrams and tables below show the recommended maximum clearance between the
molded case circuit breaker and the first point.
Overview of cable and busbar mounting methods
Cable mounting
Table 7- 1
A cable mm
B cable mm
C bar mm
This table applies for all switching capacities.
3VL IEC molded case circuit breakers
System Manual, 11/2013, 110 0110 - 02 DS 03
Recommended cable mounting clearances
VL160X
VL160
100
100
400
400
Busbar mounting
VL250
VL400
VL630
130
150
400
400
250
7
VL800
VL1250
VL1600
300
600
89

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents