L09 Indoor Unit Capacity Not Set

(Cannot be detected when the water heat exchanger unit is connected.)
Error detection method
An error is determined when the indoor unit capacity is not set.
• When the indoor unit capacity setting was forgotten after installing a new nonvolatile memory (EEPROM).
• In the remote controller detailed settings mode, the indoor unit capacity is "invalid".
Troubleshooting
1
Indoor unit
In the remote controller detailed settings mode, check the indoor unit capacity setting (item
1-1
capacity
code 11). If set to "Invalid" (0), set the correct indoor unit capacity.
setting
● See "5. Reference Document" for detailed remote controller settings.
IV–73